| 2007-03-06 20:05:29 | *** UNSAT *** |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN |
| | SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE ALL SHEETS IN BOTH SETS OF PLANS |
| | CONTAIN A *RUBBER STAMP* INSTEAD OF THE REQUIRED |
| | ORIGINAL SIGNATURE FROM THE ARCHITECT OF RECORD. THIS |
| | COMMENT HAS BEEN MADE BY THIS OFFICE/REVIEWER ON OTHER |
| | PROJECTS AND PREVIOUSLY TO THIS DESIGN PROFESSIONAL. |
| | PLEASE KNOW AS THIS IS STILL BEING DONE ON PLANS, ONE |
| | SET OF PLANS WILL BE RETAINED BY THIS OFFICE, PLACE |
| | WITH OTHER PREVIOUSLY HELD PLANS FOR THE SAME COMMENT |
| | AND FORWARDED TO THE STATE'S LEGAL COUNSEL TO THE |
| | FLORIDA BOARD OF ARCHITECTS FOR REVIEW. |
| | PLEASE SEE FS 481.221(2) |
| | *ALL FINAL CONSTRUCTION DOCUMENTS AND INSTRUMENTS OF |
| | SERVICE WHICH INCLUDE DRAWINGS, PLANS, SPECIFICATIONS, |
| | OR REPORTS PREPARED OR ISSUED BY THE REGISTERED |
| | ARCHITECT AND BEING FILED FOR PUBLIC RECORD SHALL BEAR |
| | THE SIGNATURE AND SEAL OF THE REGISTERED ARCHITECT WHO |
| | PREPARED OR APPROVED THE DOCUMENT AND THE DATE ON WHICH |
| | THEY WERE SEALED. THE SIGNATURE, DATE, AND SEAL SHALL |
| | BE EVIDENCE OF THE AUTHENTICITY OF THAT TO WHICH THEY |
| | ARE AFFIXED* |
| | |
| | 3) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE |
| | SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS |
| | SMOKE DETECTORS. |
| | PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN |
| | SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY |
| | INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS |
| | ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN |
| | THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS |
| | OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE |
| | ALARMS. |
| | THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| | OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY |
| | THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| | FOR OTHER NEW HOMES. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE*. |
| | PLEASE SEE NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | 4) NOTE: PLEASE SEE AH#2 AS THE CONDUCTOR SIZE TO THE |
| | 5KW AHU IS SHOWN AS #6. PLEASE KNOW AS IT IS |
| | PERMISSIBLE BY THE NEC TO INCREASE THE CONDUCTORS, THE |
| | #6 AS INDICATED WILL NOT FIT UNDER A 30AMP BREAKER AS |
| | THE CONNECTIONS ARE NOT LISTED FOR THIS SIZE |
| | CONDUCTOR. |
| | 110.3 |
| | |
| | 5) NOTE: PLEASE SEE MISSING DISCONNECT FOR CU #2 AS |
| | REQUIRED PER 440.11. |
| | |
| | 6) NOTE: PLEASE CORRELATE ELECTRICAL PLANS WITH |
| | MECHANICAL PLANS FOR THE OVER CURRENT PROTECTION DEVICE |
| | FOR THE CU #3. ELECTRICAL PLANS INDICATE 30AMP AND THE |
| | MECHANICAL PLANS 50AMP. |
| | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION |
| | AND COORDINATION. |
| | |
| | 7) NOTE: PLEASE SEE THE WASHER AND DRYER IN THE UTILITY |
| | ROOM. ONE OR THE OTHER DOES NOT CONTAIN ANY ELECTRICAL |
| | RECEPTACLE FOR CONNECTION OF THE APPLIANCE.? PLEASE SEE |
| | PANEL SCHEDULE MENTIONS ONLY A 1-POLE 20AMP CIRCUIT FOR |
| | DRYER IS THIS GAS? |
| | PLEASE COMPLETE AND CORRELATE. |
| | FBC106.3.5.4 ADMIN SECTION. |
| | |
| | 8) NOTE: PLEASE SEE 210.8A7 FOR REQUIRED GFI PROTECTED |
| | RECEPTACLES WITHIN 6FT OF A SINK IN LAUNDRY ROOMS. |
| | PLEASE KNOW THAT THIS INCLUDES *ALL* 15/20AMP 125VOLT , |
| | EVEN WASHER. (WASHER BECAME INCLUDE IN THIS CODE CYCLE |
| | EVEN IF A SINGLE USE DEDICATED OUTLET) |
| | |
| | 9) NOTE: PLEASE SEE MISSING RECEPTACLE FOR 2FT OR MORE |
| | OF WALL SPACE IN DINING ROOM PER 210.52. |
| | |
| | 10) NOTE: PLEASE SEE THE SECTION FOR THE 2004 FBC |
| | CHAPTER 13 FOR RECESSED LIGHT FIXTURES IS NOW |
| | 13-606.1.ABC.1.2.4. |
| | |
| | 11) NOTE: PLEASE LABEL ALL APPLIANCES WHICH ARE GAS |
| | POWERED ON THE PANEL SCHEDULE AS SUCH. |
| | COOKTOP, DRYER ETC. |
| | 408.4. |
| | |
| | 12) NOTE: PLEASE SEE FS 472.025(1) FOR THE SITE/SURVEYS |
| | WHICH ARE REQUIRED TO CONTAIN AN ORIGINAL SIGNATURE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |