| 2007-04-13 17:00:02 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 2- ARCHITECT TO SIGN DRAWINGS WITH ORIGINAL SIGNATURE, |
| | NOT RUBBER STAMP AS REQUIRED BY SEC. 61G1-16.003 |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 3- SHEET T1:UPDATE STRUCTURECONSTRUCTION TYPE.USE |
| | FBC 2004 FOR CORRECT TYPE OF CONSTRUCTION AND REVISE AS |
| | REQUIRED. |
| | |
| | 4- PROVIDE DRAINAGE PLAN AS REQUIRED BY SEC. R401.3OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | ***NOTE: WATER NEED TO BE DIVERTED SO IT DOESN'T GO TO |
| | THE NEIGHBOR'S PROPERTY. |
| | |
| | 5- SHEET A1:FOOTING SHOW ON FOUNDATION PLAN BY ONE |
| | CAR GARAGE DOESN'T MATCH DETAIL 5. REVISE AS REQUIRED. |
| | |
| | 6- SHEET A2:A) SPECIFY INSULATION FOR WALL BETWEEN |
| | ONE CAR GARAGE AND CLUB ROOM.CHAPTER 13 FBC 2004. |
| | |
| | B) CLEARLY SPECIFY THAT ROOM NEXT TO THE GARAGE |
| | (CLUB ROOM) CAN'T BE USED FOR SLEEPING PURPOSES. SEC. |
| | R309.1 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | |
| | 7- SHEET A4: |
| | A)FRONT ELEVATION IS MISSING THE DESIGN PRESSURES |
| | FOR DOORS AND WINDOWS.PROVIDE SUCH INFORMATION. |
| | |
| | B) REVISE BUILDING CONSTRUCTION TYPE. SEE FBC 2004 |
| | FOR CORRECT CONSTRUCTION TYPE. |
| | |
| | 8- SHEET A6: |
| | A) GARAGE JAMB DETAIL: SPECIFY HOW MUCH EMBEDMENT IS |
| | REQUIRED FOR THE WEDGE ANCHORS. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | B) PROVIDE COMPLETE SCREEN ENCLOSURE ENGINEERED |
| | INFORMATION OR SPECIFY UNDER A SEPARATE PERMIT. |
| | |
| | 9- SPECIFY ROOF SHEATHING NAIL TYPE AND SIZE. SEE SEC. |
| | R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 10- ENERGY CALCULATIONS: |
| | A)NEED TO USE REVISED FORM 600A-2004 R. REVISE AS |
| | REQUIRED. |
| | |
| | B) CONTRACTOR IS THE RIF GROUP, NOT KENCO |
| | COMMUNITIES. REVISE AS REQUIRED. |
| | |
| | 11- PROVIDE COMPLETE UL LISTING AND SPECS FOR EXTERIOR |
| | HOOD ABOVE BBQ.ONLY BBQ INFORMATION WAS PROVIDED AT |
| | THIS TIME. |
| | |
| | 12- SURVEY TO HAVE ORIGINAL SIGNATURE, NOT COPY, AS |
| | REQUIRED BY CHAPTER 472 FLORIDASTATUTE. |
| | |
| | 13- SOIL TEST REPORT:PROVIDE THE ENGINEERING FIRM |
| | CERTIFICATE OF AUTHORIZATION NUMBER IN ALL SHEETS AS |
| | REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE |
| | CODE. |
| | |
| | 14- THERE WAS A PRODUCT APPROVAL FOR 4", 6" AND 12" |
| | PRECAST LINTELS. CLARIFY WHERE ARE THESE LINTELS GOING |
| | TO BE USED. WHY IT WAS APPROVED IF IT DOESN'T APPLY TO |
| | THIS PROJECT? |
| | |
| | 15-NOA #03-0605.05 SUBMITTED FOR 8" PRECAST LINTELS |
| | EXPIRED ON 05/21/06. PROVIDE CURRENT PRODUCT APPROVAL |
| | AND DESIGNER OF RECORD TO REVIEW AND APPROVE PRIOR TO |
| | SUBMITTAL. |
| | |
| | 16-DESIGNER OF RECORD TO REVIEW AND APPROVE NOA |
| | #05-1121.08 SUBMITTED FOR THE SLIDING GLASS DOORS. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |