Plan Review Notes
Plan Review Notes For Permit 07030026
Permit Number 07030026
Review Stop B
Sequence Number 1
Notes
Date Text
2007-03-30 12:27:33BUILDING PLAN REVIEW
 PERMIT: 07030026
 ADD: 1501 S FLAGLER DR
 CONT: SBA NETWORK SERVICES
 TEL: (352)629-1774
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET A-1 WIND LOAD INFORMATION IS MISSING THE
 IMPORTANCE FACTOR, NOTE NEXTEL CELL PHONES ARE USED IN
 THE HURRICANE ASSESMENT AND PART OF CITY'S
 EMERGENCY PREPAREDNESS AND COMMUNICATION SYSTEM
 CATEGORYIV = IMPORTANCE FACTOR 1.15
  
 4)IS THE 13'-3"X16'-2" CABINET A STATE MANUFACTURED
 BUILDING?PLEASE PROVIDE DETAILS ON THIS STRUCTURE.
 SHEET N-1 GENERAL NOTE 12 INDICATES THIS IS A
 PREMANUFACTURED BUILDING PROVIDE STATE APPROVED PLANS.
  
 5) PLANS INDICATE ROOFING WORK AND FLASHING, NOTE THERE
 IS NO ROOFING CONTRACTOR SIGNED ON AT THIS TIME.
  
 6)SHEET E-2 INDICATES THE ELECTRICAL RUNS FROM THE
 8TH FLOOR ELECTRIC ROOM, HOW OR WHERE WILL THESE RUNS
 CONTINUE TO THE ROOF ? NOTE NOT TO USE THE STAIR TOWERS
 FOR ACCESS.
 1019.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 AND ELECTRICAL RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M 2 ). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 712 . THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 NOTE THE INFORMATION FOR THE GENERATOR WAS STRUCK!
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  