| 2007-03-30 12:27:33 | BUILDING PLAN REVIEW |
| | PERMIT: 07030026 |
| | ADD: 1501 S FLAGLER DR |
| | CONT: SBA NETWORK SERVICES |
| | TEL: (352)629-1774 |
| | |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2 ) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. |
| | NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLY |
| | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| | SUCH NOTICE IS |
| | NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE |
| | OF COMMENCEMENT |
| | AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) SHEET A-1 WIND LOAD INFORMATION IS MISSING THE |
| | IMPORTANCE FACTOR, NOTE NEXTEL CELL PHONES ARE USED IN |
| | THE HURRICANE ASSESMENT AND PART OF CITY'S |
| | EMERGENCY PREPAREDNESS AND COMMUNICATION SYSTEM |
| | CATEGORYIV = IMPORTANCE FACTOR 1.15 |
| | |
| | 4)IS THE 13'-3"X16'-2" CABINET A STATE MANUFACTURED |
| | BUILDING?PLEASE PROVIDE DETAILS ON THIS STRUCTURE. |
| | SHEET N-1 GENERAL NOTE 12 INDICATES THIS IS A |
| | PREMANUFACTURED BUILDING PROVIDE STATE APPROVED PLANS. |
| | |
| | 5) PLANS INDICATE ROOFING WORK AND FLASHING, NOTE THERE |
| | IS NO ROOFING CONTRACTOR SIGNED ON AT THIS TIME. |
| | |
| | 6)SHEET E-2 INDICATES THE ELECTRICAL RUNS FROM THE |
| | 8TH FLOOR ELECTRIC ROOM, HOW OR WHERE WILL THESE RUNS |
| | CONTINUE TO THE ROOF ? NOTE NOT TO USE THE STAIR TOWERS |
| | FOR ACCESS. |
| | 1019.1.2 PENETRATIONS. |
| | PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT |
| | ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, |
| | ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION |
| | AND ELECTRICAL RACEWAY SERVING THE EXIT ENCLOSURE AND |
| | TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE |
| | INCHES (0.010 M 2 ). SUCH PENETRATIONS SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 712 . THERE SHALL |
| | BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER |
| | PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES. |
| | |
| | NOTE THE INFORMATION FOR THE GENERATOR WAS STRUCK! |
| | |