Plan Review Notes
Plan Review Notes For Permit 07030020
Permit Number 07030020
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-18 15:26:18BUILDING PLAN REVIEW
 PERMIT: 07030020
 ADD: 2216 PALM BEACH LAKES BLVD
 CONT: CRAMER & BREEN BUILD
 TEL: (561)541-9844
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS ( ADMINISTRATIVE)
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE INDICATE IN DETAIL WHAT SCOPE OF WORK WILL BE
 COVERED UNDER THIS PERMIT, WHAT INSPECTIONS WILL BE
 NEEDED?DEPENDING ON THE ABOVE
 STATEMENT THE VALUEOF THIS PROJECT MAY BE LOW!
  
 4) PLANS FAIL TO INDICATE:
 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OF T HE CODE UNDER WHICH
 THIS PERMIT WILL BE ISSUED. PLANS INDICATE THE 2001
 FBC PLEASE CORRECT TO THE 2004 FBC.
 ALSO 2004 EXISTING BUILDING CODE, LEVEL OF ALTERATION.
  
  
 5) IF THE SCOPE OF WORK INCLUDED UNDER THIS PERMIT
 INCLUDES THE EXTERIOR ENVELOPE:
 ) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 6)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) COMPLIED.
  
 8) NEW COMMENT DEALS WITH LETTER STATING DOOR HEIGTH OF
 DOORS 120,121, 122,126,140,141&141 ARE 75 " TALL.
 PLEASE SEE 1008.1.1THE HEIGHT OF DOORS SHALL NOT BE
 LESS THAN 80 INCHES (2032 MM).
 EXCEPTIONS LISTED DO NOT INCLUDE KENNELS.
  
 9) NEW COMMENT DEALS WITH LIGHT POLES, THERE ARE TWO
 DIFFERENT POLE MANUFACTURER'S SUBMITTED SHAKESPEARE
 POLES ARE CALCULATED TO ASCE 7-98. PCSI POLES ARE
 CALCULATED TO ASCE 7-04. PLEASE SEE CHAPTER 35OF THE
 2004 FBC, THE REFRENCED STANDARD IS ASCE 7-02. ALSO IF
 TWO REOPRTS ARE SUBMITTED THEN BOTH REPORTS WILL NEED
 TO BE ORIGINAL SIGNATURE, DATE AND RAISED EMBOSSED
 SEAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
2007-04-02 07:51:20BUILDING PLAN REVIEW
 PERMIT: 07030020
 ADD: 2216 PALM BEACH LAKES BLVD
 CONT: CRAMER & BREEN BUILD
 TEL: (561)541-9844
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS ( ADMINISTRATIVE)
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE INDICATE IN DETAIL WHAT SCOPE OF WORK WILL BE
 COVERED UNDER THIS PERMIT, WHAT INSPECTIONS WILL BE
 NEEDED?DEPENDING ON THE ABOVE
 STATEMENT THE VALUEOF THIS PROJECT MAY BE LOW!
  
 4) PLANS FAIL TO INDICATE:
 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OF T HE CODE UNDER WHICH
 THIS PERMIT WILL BE ISSUED.
 ALSO 2004 EXISTING BUILDING CODE, LEVEL OF ALTERATION.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601& TABLE 503.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) SQ. FT. A/C SPACE/ FL
 H) SQ. FT. FOOTPRINT
 I) SQ. FT. UNDER ROOF (TOTAL)
  
 5) IF THE SCOPE OF WORK INCLUDED UNDER THIS PERMIT
 INCLUDES THE EXTERIOR ENVELOPE:
 ) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 6)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) PLANS SUBMITTED ARE LOOSE LEAF, COMPILE INTO
 STAPBLED SETS OF PLANS, 106.1.2* & 106.3.5.1.2* .
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]