| 2007-06-11 14:36:53 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2), FBC | | | R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE C | | | HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC | | | R301.2.1.4. | | | | | | 2.)THE INSTALLATION SCHEDULE STATES THAT THE BUILDING | | | IS 90' HIGH, BUT YOU'VE CIRCLED 25-30' ON THE | | | ENGINEERING. | | | | | | 3.)OPENING 3 REQUIRES 5" ANCHOR SPACING FOR C2 AND | | | C4, SPAN UP TO 8', BUT THE INSTALLATION SCHEDULE | | | SPECIFIES 12"/6". |
|