Plan Review Notes
Plan Review Notes For Permit 07020826
Permit Number 07020826
Review Stop B
Sequence Number 3
Notes
Date Text
2007-06-11 14:36:53****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2), FBC
 R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE C
 HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  
 2.)THE INSTALLATION SCHEDULE STATES THAT THE BUILDING
 IS 90' HIGH, BUT YOU'VE CIRCLED 25-30' ON THE
 ENGINEERING.
  
 3.)OPENING 3 REQUIRES 5" ANCHOR SPACING FOR C2 AND
 C4, SPAN UP TO 8', BUT THE INSTALLATION SCHEDULE
 SPECIFIES 12"/6".