| 2007-04-16 15:19:59 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | 1.)A DESIGN PRESSURE OF -58 REQUIRES USE OF THE -73 | | | ANCHOR SPACING, SEE SHEET 7 OF THE PRODUCT APPROVAL. | | | -57 IS NOT COMPLIANT FOR DESIGN PRESSURE OF -58. | | | REVISE THE ANCHOR SCHEDULE ACCORDINGLY. | | | | | | 2.)WOOD AND CONCRETE BLOCK SUBSTRATE ARE CIRCLED ON | | | THE PRODUCT APPROVAL.CIRCLE ONLY DETAILS SPECIFIC TO | | | THIS JOB. | | | | | | | | | |
|