| 2007-06-04 14:30:17 | *****DENIED***** |
| | |
| | |
| | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FORMTHE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 3.THE DEMOLITION, RENOVATION, OR CONSTRUCTION |
| | OPERATIONS SHALL NOT HINDER OF INTERFERE WITH EMERGENCY |
| | RESPONSE ACCESS TO THE SAID PROPERTY OR VICINITY |
| | THEREOF (INCLUDING STREETS, ROADS ALLEYS, FIRE LANES). |
| | |
| | 4.ON THE APPROPIATE EXTERIOR ELEVATION FRONTING 7TH |
| | STREET, DISPLAY THE NUMERICAL ADDRESS FOR THIS |
| | STRUCTURE.AS PER WEST PALM BEACH CODE, THOSE NUMBERS |
| | SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" |
| | IN WIDTH. |
| | |
| | 5.ON PLAN SHEET 3, IT IS NOTICED THAT A SMOKE |
| | DETECTOR (SD) IS LOCATED IN EACH OF THE BEDROOMS, |
| | WHEREAS A SMOKE ALARM (SA) IS LOCATED IN THE LIVING |
| | ROOM AND DINING ROOM.PLEASE BE ADVISED THAT SMOKE |
| | DETECTORS (SD) ARE TIED INTO A FIRE ALARM SYSTEM. |
| | |
| | 6.IT IS NOTED ON SHEET 9 OF THE INTENT OF |
| | CONSTRUCTING A CBS WALL TO CREATE A STORAGE ROOM. |
| | PLEASE BE ADVISED THAT ROOMS OR SPACES FOR STORAGE |
| | (UNDERNEATH A EXIT STAIR) OF COMBUSTIBLE SUPPLIES AND |
| | EQUIPMENT SHALL BE SPRINKLERERED OR HAVE A 1 HOUR FIRE |
| | SEPARATION. |
| | |
| | 7.SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| | CLASSIFICATION IN THE EXITS, EXIT ACCESS CORRIDORS, AND |
| | ALL OTHER SPACES AS CLASS A, CLASS B, OR CLASS C. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |