| 2007-04-29 10:59:12 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| | FBC2004 |
| | FACFLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | |
| | 1.)SEE ATTACHED.THERE IS A BALANCE OF $2883.60 FROM |
| | A 4X PLAN REVIEW FEE ONPERMIT APPLICATION 03111034. |
| | SEE NOTES REGARDING THIS FEE ON THE FRONT SCREEN OF |
| | PERMIT 03111034.THIS FEE MUST BE PAID WHEN |
| | RESUBMITTING. |
| | |
| | 2.)THE PERMIT FOR THE ROOF FRAMING, SHEATHING, AND |
| | FLOOR FRAMING IS EXPIRED, AS WELL AS THE WINDOW AND |
| | DOOR PERMIT (04070723, 04050602).INCLUDE THIS SCOPE |
| | OF WORK IN THIS PERMIT AND IN THE VALUE. |
| | |
| | 3.)ENERGY CALCS WERE SUBMITTED.FORM 600 A-01 WAS |
| | USED.GOVERNING CODE IS FBC2004, PLEASE SEE FBC13 AND |
| | USE THE CORRECT FORM. |
| | |
| | 4.)ENERGY CALCS REQUIRED FOR THE FIRST FLOOR ALSO, |
| | WHICH IS NOT RESIDENTIAL, FBC13-101.1, FBC13-202, FBC |
| | EB 708.1.ENERGY CALCS REQUIRED FOR SHELL BUILDINGS, |
| | FBC13-101.2. |
| | |
| | 5.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3. |
| | |
| | 6.)INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6, |
| | BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, |
| | OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY. |
| | |
| | 7.)THE PLANS DO NOT PROVIDE ENOUGH INFORMATION TO |
| | DETERMINE CODE COMPLIANCE.FOR INSTANCE, SHEET 1 SHOWS |
| | A 5? AND 10? DISTANCE TO DOTTED LINES.IF THIS IS AN |
| | ASSUMED PROPERTY LINE, YOU NEED TO SHOW THE ADJACENT |
| | BUILDINGS AND THEIR DISTANCE TO THE PROPERTY LINE AS |
| | WELL AS BUILDING TYPE AND OCCUPANCY.A NOTE ON SHEET 2 |
| | STATES THAT THESE WALLS EXCEED 1 HOUR FIRE RATING, BUT |
| | COMPLIANCE WITH FBC TABLE 704.8 (0 UNPROTECTED OPENINGS |
| | PERMITTED), FBC TABLE 503, FBC TABLES 601, 602 HAS NOT |
| | BEEN SHOWN.PLEASE CONTACT ME IF YOU NEED ASSISTANCE. |
| | |
| | |
| | 8.)INFORMATION WAS NOT PROVIDED FOR THE FIRST FLOOR. |
| | THE BOARD ORDER WAS TO BRING THE ENTIRE BUILDING UP TO |
| | 100% CODE COMPLIANCE.AREN?T THERE WINDOWS, DOORS, |
| | ETC. ON THE FIRST FLOOR?IT IS UNDERSTOOD THAT THIS |
| | WILL BE A SHELL BUT CODE COMPLIANCE FOR THE SHELL MUST |
| | BE ON THE PLAN; EGRESS, INCLUDING ACCESSIBLE |
| | ENTRANCE/EXIT FBC 13.NOTHING WAS SHOWN ON THE PLAN. |
| | |
| | |
| | 9.)USE OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS |
| | REQUIRES APPROVAL BY THE BUILDING OFFICIAL, SEE |
| | ATTACHED POLICY, ITEM 13.PROVIDE A PRE STORM |
| | INSTALLATION PLAN INCLUDING ALL INFORMATION IN THE |
| | POLICY.THIS PROCESS MAY (AND SHOULD) BE COMPLETED |
| | SEPARATELY FROM THE RESUBMITTAL.A DRAFT MAY BE |
| | SUBMITTED VIA EMAIL. |
| | |
| | 10.)PROVIDE A DETAIL FOR THE STAIR GUARDRAIL/HANDRAIL |
| | ON THE OPEN SIDE, FBC1012, 1009, 1009.11.1 EXCEPTION. |
| | |
| | 11.)SEE FBC 1019.1.5 REGARDING STORAGE UNDER THE |
| | STAIRS AND SHOW COMPLIANCE ON THE PLAN. |
| | |
| | 12.)THE FIRST RISER FOR THE STAIRS (SHEET 8) IS SHOWN |
| | AT 4?.SEE FBC1009.3.1, DIMENSIONAL UNIFORMITY. |
| | |
| | 13.)DESIGN PRESSURES FOR COMPONENTS AND CLADDING ARE |
| | NOT ON THE PLAN; PLEASE PROVIDE.ALSO PROVIDE WIND |
| | DESIGN CRITERIA FBC1603.1.4. |
| | |
| | 14.)A COMPLETE REVIEW OF PRODUCT APPROVALS CANNOT BE |
| | DONE WITHOUT DESIGN PRESSURES.HOWEVER, PLEASE NOTE |
| | THE FOLLOWING: |
| | |
| | A. THE STEEL DOOR IS INSWING, BUT OUTSWING IS SHOWN ON |
| | THE PLAN FOR THE SECOND FLOOR.NO INFORMATION PROVIDED |
| | FOR THE FIRST FLOOR.THIS DOOR IS NOT APPROVED WHERE |
| | WATER INFILTRATION IS REQUIRED.IT IS NOT CLEAR WHERE |
| | THIS DOOR WILL BE INSTALLED. |
| | |
| | B. THE SINGLE HUNG WINDOW IS SMALL MISSILE IMPACT |
| | RATED.LARGE MISSILE IS REQUIRED, FBC1609.1.4(1). |
| | |
| | C. SUBMIT PRODUCT APPROVALS FOR THE WINDOWS FOR THE |
| | FIRST FLOOR. |
| | |
| | D. EITHER COMPLETE THE SAMPLE INSTALLATION SCHEDULE |
| | (LAST PAGE OF THE POLICY) OR PROVIDE ALL INFORMATION IN |
| | ANOTHER FORMAT. |
| | |
| | 15.)SEE FBC1023.3 AND SHOW COMPLIANCE (DISTANCE OF |
| | STAIRS TO OTHER BUILDINGS). |
| | |
| | 16.)PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY. |
| | |