2007-07-10 11:02:25****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)RUSSELL GOULDE PE IS NOT A QUALITY ASSURANCE
 ENTITY AUDITED BY THE FLORIDA BUILDING COMMISSION.A
 SIGNED, SEALED LETTER OF COMMITMENT STATING THAT HE
 WILL INSPECT THE INSTALLATION ON THE JOBSITE AND THEN
 SUBMIT A LETTER OF CODE COMPLIANCE TO THIS OFFICE WILL
 BE REQUIRED TO SATISFY THE REQUIREMENT FOR QUALITY
 ASSURANCE FAC9B72.
  
 2.)REGARDING THE HINGES, SHEET 5 OF 5, COMPARISON
 PRODUCT NOA STATES THAT TWO STEEL HINGES REF 1361409 BY
 AMEROCK CORP. WILL BE USED.WHAT IS THE SIZE OF THOSE
 STEEL HINGES AND WHAT IS THE SIZE OF THE THREE HEAVY
 DUTY BRASS HINGES PROPOSED?THE ENGINEER MUST SPECIFY
 SO THE CONTRACOTR AND INSPECTOR WILL KNOW IF THE
 CORRECT ONE IS BEING INSTALLED.
  
 3.)NO RESUB FEE (PRODUCT APPROVAL APPLICATION
 COMMENTS, NOT A PLAN REVIEW).
  