2007-03-22 17:01:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)QUALITY ASSURANCE BY A THIRD PARTY ENTITY IS
 REQUIRED.THE APPLICATION STATES THE FLORIDA BUILDING
 COMMISSION APPROVED THIRD PARTY QUALITY ASSURANCE
 AGENCY IS RUSSELL GOULDY, PE, BUT I WAS UNABLE TO FIND
 THEIR APPROVAL NUMBER ON THE WEBSITE,
 WWW.FLORIDABIULDING.ORG.
  
 2.)THERE IS NO APPLICANT ON THE APPLICATION.THIS
 SHOULD BE THE WINDOW MANUFACTURER.
  
 3.)THE SHOP DRAWINGS ARE A PART OF THE EVALUATION
 REPORT AND SHOULD BE SIGNED, SEALED, AND DATED BY THE
 ENGINEER WHO IS DESIGNING THE WINDOW.ALL INFORMATION
 REQUIRED BY FAC61G15-23.002 SHOULD BE ON EACH SHEET.
  
 4.)WHEN SUBMITTING, PLEASE PUT ALL SHEETS IN THE
 PACKAGE FACING THE SAME DIRECTION.SOME SHEETS WERE
 UPSIDE DOWN.HAVING THE PACKAGE EASILY READABLE HELPS
 TO EXPEDITE PLAN REVIEW.
  
 5.)THE WINDOW DRAWINGS ARE NOT NUMBERED.THE
 EVAULATION REPORT SHOULD REFER TO THE DRAWINGS BY
 NUMBER, INCLUDING ALL SHEETS.THE DRAWINGS ARE
 DIFFICULT TO READ AND DO NOT HAVE ALL REQUIRED
 INFORMATION; SEE OTHER COMMENTS.
  
 6.)THE ENGINEER STATES THAT THIS IS A RATIONAL
 ANALYSIS; NO RATIONAL ANALYSIS WAS PROVIDED.
  
 7.)THIS APPEARS TO BE A COMPARATIVE ANALYSIS BUT IS
 INCOMPLETE.THE REPORT FROM THE ENGINEER STATES FOR
 MANY ITEMS "NOT RATED".THE ENGINEER IS TO SHOW THAT
 THIS PRODUCT IS MEETS OR EXCEEDS THE DESIGN PRESSURE OF
 THE PRODUCT HE IS COMPARING TO.FOR INSTANCE, THE
 WINDOW MATERIAL IS PROVIDED, BUT NO ANALYSIS WAS
 PROVIDED TO SHOW THAT 1 3/4" MAHOGANY & SPANISH CEDAR
 IS EQUAL OR SUPERIOR TO WOOD FIBER.THE ENGINEER
 SPECIFIES "HEAVY DUTY BRASS HINGES", NO SIZE SPECIFIED.
 THE PRODUCT APPROVAL FOR THE ANDERSON WINDOW USED STEEL
 HINGES, BUT THE ENGINEER'S APPROVED PRODUCT INFORMATION
 STATES ONLY "NOT RATED" FOR HINGE INFORMATION.
  
 8.)PROVIDE ALL COMPARATIVE INFORMATION FOR BOTH
 PRODUCTS.
  
 9.)THE DRAWINGS ARE TO INCLUDE ALL STRUCTURAL
 INFORMATION FOR ALL COMPONENTS.FOR INSTANCE, THE
 FIRST SHEET STATES "SCREW".WHAT TYPE OF SCREW, WHAT
 SIZE, DIAMETER, LENGTH?
  
 10.)A SET HAS BEEN RETAINED.A COMPLETE PLAN REVIEW
 CANNOT BE DONE AS INCOMPLETE INFORMATION WAS PROVIDED.
  
  
  