2007-03-15 14:51:34DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS/CLARIFICATIONS ARE REQUIRED
 FOR GAS PLAN REVIEW ON THE RESUBMITTAL:
  
 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL THE ZONING
 ISSUES HAVE BEEN RESOLVED DUE TO THE FACT THAT THE
 LOCATION OF THE GENERATOR AND PROPANE TANK MIGHT
 CHANGE.
  
 2. PLEASE NOTE THAT THERE ARE TWO DIFFERENT SETS OF GAS
 DRAWINGS THAT HAVE BEEN SUBMITTED. ONE SET IS BY THE
 CONTRACTOR SIGNED ONTHE GAS PERMIT APPLICATION
 (FLORIDA PUBLIC UTILITIES) WITH A COMPLETE DRAWING OF
 THE GAS SYSTEM TO BE INSTALLED INCLUDING THE 500 GAL.
 U/G LP TANK, GENERATOR, FUTURE POOL HEATER, WATER
 HEATER, RANGE, GRILL, AND FIREPLACE. THE OTHER SET IS
 FROM MAKO ENGINEERING CONSULTANTS, INC. FL. CA 26916
 AND SIGNED AND SEALED BY JAMES L. MAKO FL.PE 54111 WITH
 GAS TO THE GENERATOR FROM THE LP TANK. IT IS SUGGESTED
 TO DELETE THE GAS INFORMATION ON THE ENGINEERED
 DRAWINGS ON THE RESUBMITTAL DUE TO THE FACT THAT THE
 CONTRACTORS DRAWINGS INDICATE THE COMPLETE GAS SYSTEM
 OF THE RESIDENCE.
  
 3. PLEASE PROVIDE GENERATOR MANUFACTURER'S
 SPECIFICATIONS INDICATING RECOMMENDED SETBACKS TO
 STRUCTURES.
  
 4. THE VALUE ON THE PERMIT APPLICATION IS WAY TO LOW.
 VALUE ON THE APPLICATION MUST INCLUDE EVERYTHING ON
 ELECTRICAL COMMENT NUMBER ONE PLUS ALL OF THE GAS
 PERMIT APPLICATION MATERIALS, LABOR,AND DESIGN.
  
 END OF COMMENTS:
  