2007-03-14 10:27:00 
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL FOR THE GENERATOR, EQUIPMENT
 (TRANSFER SWITCHES, PANELS ETC.)
 AND PAD PER 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN
 RESUBMITTING, AND GET A RECEIPT FROM THE
 PERMIT CLERK.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS AND
 ELECTRICAL SPEC'S FOR THE TRANSFER SWITCH.
  
 3} PLEASE INDICATE CONDUIT ROUTING FROM THE GENERATOR
 TO THE ATS, ON THE SITE PLAN.
  
 4} LOCATE THE ATS ON THE SITE PLAN.
  
 5} LOCATE THE DISCONNECT SHOWNON THE RISER, ON THE SITE
 PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER