Plan Review Notes
Plan Review Notes For Permit 07020735
Permit Number 07020735
Review Stop Z
Sequence Number 2
Notes
Date Text
2007-07-24 09:03:51ZONING REVIEW: FAILED
  
 1) SIDEWALK MATERIAL SHALL BE CONCRETE. PLEASE REVISE
 ARCHITECTURAL SITE PLAN TO MATCH LH-1, REMOVING PAVERS
 FROM SIDEWALK. PAVERS PERMITTED WITHIN PLAZA ONLY.
 2) PLEASE INDICATE PLANT SCREENING MATERIAL FOR
 BACKFLOW PREVENTER WITHIN PLAZA.
 3) FUEL STORAGE TANK INDICATED BELOW PLAZA. PLEASE
 CONFIRM LANDSCAPE ARCHITECT HAS REVIEWED LOCATION AND
 IMPACT TO HISTORIC TREE.
 4) PARKING TOTALS APPEAR INCORRECT IN TABLE. TABLE
 INDICATES 63 GROUND FLOOR SPACES, DRAWINGS SHOW ONLY
 62. PARKING TOTAL SHOULD BE REVISED TO 140 IF THIS IS
 THE CASE.
 5) COLUMNS APPEAR TO IMPINGE UPON SEVERAL PARKING
 SPACES. ESP. SEE SPACE #4 ON GROUND FLOOR. PLEASE
 PROVIDE DETAILS TO CONFIRM THIS IS WORKING.
 6) PLEASE SHOW DRIVE LANE STRIPING FOR LANE SHIFT ON
 2.01. AS VEHICLES ENTER GARAGE, THEY WILL SHIFT NORTH
 TO GET AROUND COLUMN. UNCLEAR IN CURRENT DRAWINGS.
 7) PLEASE SHOW ONE-WAY DIRECTIONAL MARKING ON 2.01 AND
 2.02 FOR 12' WIDE LANES.
 8) PROVIDE DIMENSION STRINGS TO CONFIRM SPACE #20 MEETS
 ADA. SPACE IS UP AGAINST WALL.
 9) DOORS AT CORNER RETAIL MAY NOT SWING INTO SIDEWALK
 AREA. ENTRY SHALL BE RECESSED OR DOORS SHOULD SWING
 IN.
 10) PLEASE DESCRIBE HOW VEHICULAR STACKING WILL WORK
 WITH ROLL-UP DOORS.
 11) AIR RIGHTS EASEMENTS WILL BE NECESSARY FOR
 BALCONIES AND OTHER OVERHANGS. PLEASE SUBMIT FINALIZED
 EASEMENT DRAWINGS TO PLANNING STAFF.
 12) PLEASE DETAIL ON PROJECT DATA SHEET THE INFORMATION
 CONFIRMING COMPLIANCE WITH RIP PROGRAM. THIS MUST BE
 PROVIDED IN TABLE FORM.
 13) MAIN LOBBY ENTRANCE DOOR SHALL BE ACCESSED DIRECTLY
 FROM THE SIDEWALK. THIS IS A CRIME PREVENTION CONCERN.
 14) PLEASE CONFIRM COMPLIANCE WITH DAC APPROVAL.
  
 MATT FLIS - 822-1445