| 2007-07-21 20:03:21 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINSTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK - TO BE ADDRESSED BY MECHANICAL PLAN REVIEWER |
| | |
| | 4. SHT A2.03 NOT ALL TERRACES, DECK DRAINS AROUND THE |
| | POOL & WALKWAYS SHOW EOD'S. SECTIONS 1107.1 & 1107.2 . |
| | PLEASE INDICATE THE LOCATION OF ALL REQUIRED SECONDARY |
| | DRAINS. |
| | ****RESPONSE NOTED, BUT DECK DRAIN WEST OF COL. LINE |
| | B/23 , NORTH SIDE OF POOL & TERRACE ON COL. LINE J/4 |
| | SHOW NO SECONDARY DRAINAGE. |
| | |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | |
| | 8. SHT A2.41 SHOW SECONDARY DRAINS FOR THE TERRACES AND |
| | WALKWAY.SECTIONS 1107.1 & 1107.2. |
| | ****RESPONSE NOTED, BUT NO SECONDARY DRAIN IS SHOWN ON |
| | THE LAST TERRACE, (LN-1207). ALSO SHT A2.42 TERRACES |
| | LN-106, LN-111, LN-208, LN-307 SHOW NO DRAINAGE, BUT |
| | DETAIL 7/A801 (TYP) DOES NOT INDICATE DRAINAGE GAPS. |
| | PLEASE CLARIFY.-SHT A2.42 REFERS TO DETAIL 10/A807, |
| | BUT THAT DETAIL IS NOT FOUND. PLEASE CLARIFY. |
| | |
| | 9.OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | |
| | 17. SHT P0.00 KEY NOTE #4 INDICATES A PERFORATED CAP |
| | FOR THE SECONDARY DRAIN. PLEASE CLARIFY. SECTION |
| | 106.1.1. IF THE SECONDARY DRAIN IS FOR STORM, A FULL |
| | SIZE OPENING IS REQUIRED. |
| | ****RESPONSE NOTED, BUT WIRE MESH IS NOT APPROVED AS |
| | THIS CAN BE AN OBSTRUCTION. A CLEAR OPENING IS |
| | REQUIRED. SECTION 706.2. PLEASE REMOVE ALL OBSTRUCTIONS |
| | FROM THE END OF THE PIPE. |
| | |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | 24. OK |
| | 25. OK |
| | 26. OK |
| | 27. OK |
| | |
| | 28. SHT P1.03 TWO STORM LINES ARE NOT IDENTIFIED. |
| | SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| | |
| | 29. OK |
| | 30. OK |
| | 31. OK |
| | |
| | 32. SHT P1.03 KEY NOTE 19 SHOWN CONNECTING TO THE STORM |
| | RISER. CLARIFY. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT IT SEEMS LIKE 19 WAS CHANGED TO |
| | 17. MANY OTHER CHANGES TO PLANS BESIDES COMMENT |
| | RESPONSES. THERE SEEM TO BE PLAN DEVELOPMENT BETWEEN |
| | REVIEWS AND AFTER THE 101 COMMENT RESPONSES ARE |
| | REVIEWED, I WILL HAVE TO DO A COMPLETE REVIEW LOOKING |
| | FOR ANY OTHER CHANGES TO THE PLANS NOT IDENTIFIED AS |
| | COMMENT RESPONSES. |
| | |
| | 33. OK |
| | 34. OK |
| | 35. OK |
| | 36. OK - KEY NOTE 11 ADDED. |
| | 37. OK |
| | 38. OK |
| | 39. OK |
| | 40. OK |
| | 41. OK |
| | 42. OK |
| | 43. OK |
| | 44. OK |
| | 45. OK |
| | 46. OK |
| | 47. OK |
| | 48. OK |
| | 49. OK |
| | 50. OK |
| | 51. OK |
| | 52. OK |
| | 53. OK |
| | 54. OK |
| | 55. OK |
| | 56. OK |
| | |
| | 57. SHT P1.07 1 4" VTR IS SHOWN UNDER DUCT WORK FOR THE |
| | A/C SYSTEM. PLEASE CLARIFY. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT VTR WAS NOT MOVED. THE DUCT WAS |
| | DELETED FROM THE PLUMBING SHEETS, BUT UPON REVIEW OF |
| | THE MECHANICAL PLANS, THE DUCT IS STILL SHOWN OVER THE |
| | TOP OF THE VTR. PLEASE CLARIFY. |
| | |
| | 58. OK |
| | |
| | 59. SHT P1.07 KEY NOTES SEEM TO BE FOR MECHANICAL. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT NOTES 1 & 6 HAVE NOT BEEN |
| | FOUND. PLEASE CLARIFY. |
| | |
| | 60. OK |
| | 61. OK |
| | 62. OK |
| | 63. OK |
| | 64. OK |
| | 65. OK |
| | 66. OK |
| | 67. OK |
| | 68. OK |
| | 69. OK |
| | 70. OK |
| | 71. OK |
| | |
| | 72. SHT P2.02 THE SANITARY COLLECTION SHOWS THE VENT |
| | FROM THE SHOWER CONNECTING TO RISER S/74. RISER S/74 |
| | DOES NOT SHOW THE VENT CONNECTING TO THE RISER. PLEASE |
| | CLARIFY AND CORRELATE. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT SHT P2.02 HAS NOT BEEN REVISED. |
| | THERE ARE NOW 2 RISERS DESIGNATED S/74. PLEASE |
| | CLARIFY. |
| | |
| | |
| | 73. SHT P2.02 RISER S/20 ON THE COLLECTION RISER IS |
| | SHOWN AS 88 DFU, BUT THE RISER DIAGRAM SHOWS IT AS 86 |
| | DFU. PLEASE CLARIFY. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT NO CHANGE IS INDICATED ON S/20. |
| | PLEASE CLARIFY. |
| | |
| | 74. OK |
| | |
| | 75. SHT P2.06 2 RISERS ARE SUBMITTED FOR S/42. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THERE ARE STILL TWO S/42 |
| | RISERS. ONE ON SHT P2.05 & ONE ON SHT P2.06. PLEASE |
| | CLARIFY. |
| | |
| | 76. SHT P2.06 RISERS S/34, S/71, S/73, & S/41 ALL SHOW |
| | SHOWERS, BUT THE FLOOR PLAN SHOWS TUBS. PLEASE |
| | CORRELATE. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE SHOWERS WERE ALREADY SHOWN |
| | ON RISERS S/34, S/71 & S/73. NO CHANGE NOTED. |
| | |
| | 77. OK |
| | 78. OK |
| | 79. OK |
| | 80. OK |
| | 81. OK |
| | 82. OK |
| | 83. OK |
| | 84. OK |
| | 85. OK |
| | 86. OK |
| | 87. OK |
| | 88. OK |
| | 89. OK |
| | |
| | 90. SHT P2.13 THE SIZE OF THE DECK DRAINAGE PIPING |
| | SHALL NOT BE REDUCED IN THE DIRECTION OF FLOW. (6" TO |
| | 4"). SECTION 704.2. |
| | ****RESPONSE NOTED, BUT TWO AREAS SHOW 8" REDUCED TO 6" |
| | IN THE DIRECTION OF FLOW AND ONE 4" RD DRAINING INTO 3" |
| | PIPE. |
| | |
| | 91. SHT P2.13 THE TOTAL DRAINAGE AREA IS APPROX. |
| | 20,140SF. THE SECONDARY DRAINS ADD UP TO 6,880SF. |
| | PLEASE CLARIFY. THE SECONDARY DRAINS SHALL DRAIN THE |
| | SAME AMOUNT OF SQUARE FOOTAGE AS THE PRIMARY DRAINS. |
| | SECTION 1107.3. SCUPPERS SHALL BE SIZED TO PREVENT THE |
| | DEPTH OF PONDING WATER FROM EXCEEDING THAT FOR WHICH |
| | THE ROOF WAS DESIGNED AS DETERMINED BY SECTION 1101.7. |
| | PLEASE KEEP IN MIND THE DEPTH OF THE WATER BEFORE THE |
| | SECONDARY DRAINAGE STARTS TO REMOVE THE STORM WATER AND |
| | THE HEIGHT OF THE SLIDING DOORS TO THE UNITS OFF THE |
| | TERACES. |
| | ****RESPONSE NOTED, BUT PLEASE CLARIFY WHAT NATURAL |
| | OVERFLOW PRETAINS TO. THIS IS A TERM I AM UNFAMILIAR |
| | WITH.-SHEET P1.04 INDICATES THE SLOPE OF THE DECK |
| | TO THE DECK DRAINS, BUT ALSO INDICATES THE SLOPE AWAY |
| | FROM THE DECK DRAINS IN THE SAME AREAS TOWARD THE POOL. |
| | PLEASE CLARIFY. PER SECTIONS 424.1 DEFINITION OF "WET |
| | DECK AREA" & SECTION 424.1.3.1.2 THE WET DECK SHALL |
| | SLOPE AWAY FROM THE POOL. PLEASE CLARIFY. |
| | |
| | 92. SHT P2.14 INDICATES GAS PIPE SIZES BASED ON THE |
| | NFPA CHART. PIPING SHALL BE SIZED PER THE FBC-2004 FUEL |
| | GAS CODE. PLEASE CHANGE REFERENCE. |
| | ****RESPONSE NOTED, BUT REFERENCE NOTE NOT CHANGED. |
| | SINCE THE TOTAL DEVELOPED LENGTH IS NOW EXCEEDING THE |
| | 200FT MAX ON FBC-2004 FUEL GAS TABLE FOR 2PSI THE TABLE |
| | FROM NFPA WILL BE ACCEPTABLE. PLEASE SUBMIT THE TABLE |
| | INDICATED. PLEASE MAKE SURE REFERENCE TO NFPA IS |
| | INDICATED ON THE SHEET WITH THE TABLE. |
| | |
| | 93. SHT P2.14 THE LONGEST RUN IS INDICATED AS 58'0", |
| | BUT ADDITION INDICATES 62' WITHOUT COUNTING THE LENGTH |
| | OF PIPES FROM THE METER TO THE FIRST RISER. PLEASE |
| | RECHECK THE ADDITION AND ADD THE PIPE LENGTH FROM THE |
| | METER TO THE FIRST RISER. FBC-2004 FUEL GAS CODE |
| | APPENDIX A - USE OF CAPACITY TABLES A.3.1(4). |
| | ****RESPONSE NOTED. THIS COMMENT IS OK, BUT THE |
| | CONTINUING PLAN DEVELOPMENT BETWEEN REVIEWS HAS ADDED A |
| | GENERATOR THAT WILL GENERATE MORE COMMENTS. |
| | |
| | 94. SHT P2.14 INDICATE THE LENGTH OF PIPES FROM THE |
| | REGULATOR TO THE POOL HEATER. |
| | ****RESPONSE NOTED, BUT THE LENGTHS IN QUESTION HAVE |
| | NOT BEEN INDICATED. COMMENT NOT ADDRESSED. |
| | |
| | 95. OK |
| | |
| | 96. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | ****RESPONSE NOTED, BUT PLEASE INDICATE WHERE IN THE |
| | MECHANICAL PLANS THIS CAN BE FOUND. |
| | |
| | 97. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | ****RESPONSE NOTED, BUT PLEASE INDICATE WHERE IN THE |
| | MECHANICAL PLANS THIS CAN BE FOUND. |
| | |
| | 98. SHT P2.14 KEY NOTE #13 NOT APPROVED. SECTION |
| | 504.7.2. SHOW TERMINATION FOR PAN DRAIN. ****RESPONSE |
| | NOTED, BUT KEY NOTE #13 STILL INDICATES TERMINATION IN |
| | THE GARAGE. THIS IS NOT APPROVED. IT IS POSSIBLE FOR |
| | CARBON MONOXIDE TO ENTER THE UNITS FROM THESE OPEN |
| | LINES. SUBMIT A ISOMETRIC RISER DIAGRAM FOR THE PAN |
| | DRAINS SHOWING ALL PIPE SIZES, MATERIAL AND TERMINATION |
| | POINT. SECTION 106.3.1.5.3(4)(13). |
| | |
| | 99. SHT P3.02 INSTALLATION NOTES. SE SOVENT (SESCO) & |
| | TITE-RUFF SYSTEMS, DESIGN MANUAL 101/0 & TABLES. SUBMIT |
| | MANUF. SPECIFICATION FOR ALL. SHOW TESTING AND APPROVAL |
| | FOR ALL. |
| | ****RESPONSE NOTED, BUT THE SOVENT DETAILS DO NOT |
| | REFLECT THE DETAILS FROM THE DESIGN MANUAL 802. PLEASE |
| | CORRELATE DETAILS AND THE DESIGN MANUAL. |
| | |
| | 100. OK |
| | |
| | 101. PLEASE RESUBMIT THE SET OF PLUMBING PLANS WITH THE |
| | RED LINE MARK-UPS TO HELP EXPEDITE FOLLOWING PLAN |
| | REVIEWS. |
| | ****RESPONSE NOTED, BUT RED LINED MARK-UPS WERE NOT |
| | RESUBMITTED WITH THE PLANS. MANY EXTRA HOURS HAVE BEEN |
| | ADDED TO THE PLAN REVIEW AND BECAUSE OF THE PLAN |
| | DEVELOPMENT BETWEEN REVIEWS THIS WILL ADD TO THE REVIEW |
| | PROCESS. |
| | |
| | **********NEW COMMENTS*********** |
| | |
| | 1B. SHT P1.01 KEY NOTES #5 & #28 REMOVE REFERENCE TO |
| | WIRE MESH AS IT IS NOT APPROVED. SECTION 706.2. |
| | |
| | 2B. SHT P1.01 KEY NOTE #36. THE POOL OVERFLOW SHALL |
| | CONNECT TO THE STORM SYSTEM. |
| | |
| | 3B. SHT P1.01 KEY NOTES #28 & #29. PLEASE IDENTIFY WHAT |
| | WILL DRAIN INTO THESE DRAINS. SECTION 106.1.1. |
| | |
| | 4B. SHT P1.02 KEY NOTE #15. PLEASE IDENTYFY WHAT WILL |
| | DRAIN INTO THIS DRAIN. SECTION 106.1.1. |
| | |
| | 5B. SHT P1.02 REVISION #1 INDICATED ON SHEET IS NOT |
| | INDICATED ON THE REVISION INDEX. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 6B. SHT P1.02 KEY NOTES #22 THRU #25 ARE NEW ADDED TO |
| | INDEX BUT NOT INDICATED AS A REVISION WITH CLOUD OR |
| | REVISION NUMBER. PLEASE SHOW ALL REVISIONSWITH A |
| | CLOUD AND REVISION NUMBER. SECTION 106.1.3. |
| | |
| | 7B. SHT P1.03 KEY NOTE #21 FLOOR DRAINS ARE NOT |
| | APPROVED INDIRECT WASTE RECEPTORS. A FLOOR SINK OR HUB |
| | DRAIN IS APPROVED PER SECTIONS 802.3 & 802.3.2. |
| | |
| | 8B. SHT P1.03 KEY NOTE #23. PLEASE IDENTIFY WHAT WILL |
| | DRAIN INTO THIS LINE. SECTION 106.1.1. |
| | |
| | 9B. SHT P1.03 KEY NOTES #25 THRU #27 ARE ADDED NEW |
| | WITHOUT A CLOUD OR REVISION NUMBER. PLEASE SHOW ALL |
| | REVISIONSWITH A CLOUD AND REVISION NUMBER. SECTION |
| | 106.1.3. |
| | |
| | 10B. SHT P1.03 IDENTIFY THE DRAIN THAT WAS INDICATED AS |
| | A PLANTER DRAIN ON PRIOR REVIEW SUBMITTAL, BUT IS NOW |
| | CONNECTED TO THE STORM OVERFLOW DRAIN LINE. SECTION |
| | 106.1.1. |
| | |
| | 11B. SHT P1.03 TWO 3" DRAINS SHOWN WITH NO INDICATION |
| | OF WHAT THEY DRAIN. PLEASE IDENTIFY THE DRAINS. |
| | |
| | 12B. SHT P1.03A, (NEW SHEET), INTERSTITIAL LEVEL SHOWS |
| | TWO 4" DRAINS. PLEASE INDICATE WHAT SYSTEMS THESE |
| | CONNECT TO AND WHERE THEY CAN BE FOUND ON THE ISOMETRIC |
| | RISER DIAGRAMS. |
| | |
| | 13B. SHT P1.04. SEE DEFINITION OF "WET DECK AREA" IN |
| | SECTION 424.1 OF THE BUILDING CODE AND SECTION |
| | 424.1.3.1.2 THE REQUIREMENT FOR THE WET DECK AREA TO BE |
| | SLOPED AWAY FROM THE POOL. SLOPE INDICATORS ARE SHOWN |
| | TO BE SLOPING AWAY FROM THE POOL AND TOWARD THE POOL IN |
| | THE SAME AREAS. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 14B. SHT P2.05 RISER S/45 DOES NOT REFLECT THE FLOOR |
| | PLAN ON FLOORS 3 THRU 8. PLEASE CORRELATE RISER AND |
| | FLOOR PLAN INFORMATION. SECTION 106.1.1. |
| | |
| | 15B. SHT P2.10 BACKFLOW PROTECTION REQUIRED FOR THE |
| | WATER SUPPLY LINE TO THE FOUNTAIN. PLEASE INDICATE |
| | METHOD. SECTION 608.1. |
| | |
| | 16B. SHT P2.14 KEY NOTE #13 IS NOT APPROVED. IT IS |
| | POSSIBLE FOR CARBON MONOXIDE TO ENTER THE UNITS FROM |
| | THESE OPEN LINES. |
| | |
| | 17B. SHT P2.14 KEY NOTES 16, 17, 18, 19, 20 & 22 WERE |
| | NOT FOUND. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 18B. SHT P3.04, (NEW SHEET), IS SHOWN WITH INFORMATION |
| | FOR THE DIESEL TANKS AND SYSTEM. THIS IS INFORMATION |
| | REQUIRED BY THE MECHANICAL PLAN REVIEWER ONLY. PLEASE |
| | RESUBMIT WITH THE INFORMATION ON THE MECHANICAL SHEETS |
| | ONLY. |
| | |
| | 19B. NEW GAS COMMENT. SUBMIT MANUF. SPECIFICATIONS FOR |
| | THE GAS REGULATORS. INDICATE MODEL NUMBER AND SHOW |
| | LISTING. |
| | |
| | 20B. MANUF. SPECIFICATIONS SHEETS FOR THE GENERATOR |
| | INDICATES THE GENERATOR WILL BE DIESEL. NO NATURAL GAS |
| | IS INDICATED. PLEASE SUBMIT MANUF. SPECIFICATIONS |
| | SHOWING LISTING FOR GAS, THE BTU'S AT 100% LOAD AND |
| | INSTALLATION INSTRUCTIONS WITH REQUIRED CLEARANCES. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |