| 2007-08-11 16:03:31 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 92. SHT P2.14 INDICATES GAS PIPE SIZES BASED ON THE |
| | NFPA CHART. PIPING SHALL BE SIZED PER THE FBC-2004 FUEL |
| | GAS CODE. PLEASE CHANGE REFERENCE. |
| | ****RESPONSE NOTED, BUT SINCE THE PLANS HAVE BEEN |
| | FURTHER DEVELOPED SINCE THE FIRST REVIEW, THE TOTAL |
| | DEVELOPED LENGTH HAS EXCEEDED 200FT. FBC-2004 FUEL GAS |
| | CODE ONLY SHOWS 200FT OR LESS. PLEASE SUBMIT THE TABLE |
| | FROM NFPA-54 INDICATED ON COMMENT RESPONSE AND SHT |
| | P2.14 AND MAKE SURE NFPA-54 IS INDICATED ON THE TABLE. |
| | |
| | 93. OK - SEE COMMENT 92. |
| | |
| | 94. SHT P2.14 INDICATE THE LENGTH OF PIPES FROM THE |
| | REGULATOR TO THE POOL HEATER. |
| | ****RESPONSE NOTED, BUT NO PIPE LENGHTS ARE INDICATED. |
| | |
| | 95. SHT P2.14 SUBMIT THE MANUF. SPECIFICATION SHEETS |
| | FOR THE POOL HEATER, AND THE REGULATOR. INDICATE THE |
| | MODEL FOR EACH AND SHOW THE LISTING. STANDARDS NFPA 54, |
| | NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT NO MANUF. SPECIFICATION SHEETS |
| | FOR THE REGULATORS HAVE BEEN FOUND. - NOW A GENERATOR |
| | HAS BEEN ADDED TO THE SYSTEM. SUBMIT MANUF LISTING FOR |
| | THE BI-FUEL ADAPTORS FOR THE DIESEL GENERATOR. SUBMIT |
| | MANUF. INSTALLATION INSTRUCTIONS FOR THE GENERATOR |
| | SHOWING ALL CLEARANCES. |
| | |
| | 96. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | ****RESPONSE NOTED. INDICATE WHERE IN THE MECHANICAL |
| | DRAWINGS THE CALCULATIONS CAN BE FOUND. |
| | |
| | 97. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| | AND TERMINATION OF THE GAS VENTS PER FBC-2004 FUEL GAS |
| | CODE SECS. 502 THRU 505. |
| | ****RESPONSE NOTED. INDICATE WHERE IN THE MECHANICAL |
| | DRAWINGS THE INFORMATION CAN BE LOCATED. |
| | |