| 2007-09-05 13:19:33 | 1. NO RESPONSES PROVIDED WITH APPLICATION PACKET |
| | ADDRESSING PREVIOUS PLAN REVIEW COMMENTS PROVIDED BY |
| | FIRE RESCUE. REQUESTED THIS INFORMATION. |
| | |
| | 2. GROUND LEVEL SITE PLAN ON PAGE A1.00 DOES NOT |
| | DISPLAY NEW OR EXISTING FIRE HYDRANTS. |
| | |
| | 3. IT APPEARS THAT THE FIRE DEPARTMENT CONNECTIONS |
| | EXTEND BEYOND THE PROPERTY LINE. |
| | |
| | 4. THE FIRE DEPARTMENT CONNECTIONS ARE REQUIRED TO BE |
| | EQUIPPED WITH KNOX-BOX LOCKING CAPS. |
| | |
| | 5. ALL FABRIC CANOPIES ILLUSTRATED ON THE PLANS SHALL |
| | BE FLAME RETARDANT WHEN SUBMITTED UNDER A SEPARATE |
| | PERMIT. |
| | |
| | 6. FIRE PUMP ROOM SHOWN ON PAGE A2.02. PLEASE EXPLAIN |
| | THE LOCATION CHOSEN. |
| | |
| | 7. THE WORD MEZZANINE STILL APPEARS ON THE PLANS. |
| | PLEASE ADVISE RATIONALE. |
| | |
| | 8. PLEASE INDICATE ON PLANS THE STRETCHER ACCESSIBLE |
| | ELEVATOR(S). THE APPROPRIATE ELEVATORS SHALL BE |
| | IDENTIFIED WITH NECESSARY SIGNAGE. |
| | |
| | 9. PORTIONS OF THE ROOF APPEAR TO OVERHANG THE PROPERTY |
| | LINE. PLEASE PROVIDE INFORMATION. |
| | |
| | 10. WALL SEPARATING GARAGE AND RETAIL SPACES ON PAGE |
| | A2.30 APPEARS TO BE ONLY ONE HOUR FIRE RATED. THIS WALL |
| | SHALL BE AT LEAST TWO HOUR FIRE RATED. |
| | |
| | 11. BUILDING ADDRESS NOT DISPLAYED ON ANY ELEVATION |
| | DRAWINGS. |
| | |
| | 12. PLAN NOTE REVISION CLOUD # 3 ON PAGES E1.01- E1.03 |
| | NEEDS TO BE FURTHER CLARIFIED. NOTE DOES NOT CLEARLY |
| | DESCRIBE THE CODE REQUIREMENTS UNDER SPECIAL LOCKING |
| | ARRANGEMENTS. |
| | |
| | 13. DUCT DETECTOR NOTE ON PAGE FA1.08 IS INCORRECT. |
| | ACTIVATION OF A DUCT SMOKE DETECTOR SHALL CAUSE AN |
| | ALARM CONDITION. |
| | |
| | 14. WHAT WINDOWS ARE PLANNED TO BE USED AS SMOKE |
| | OPENINGS IDENTIFIED IN THE DRAWINGS. |
| | |
| | 15. SINCE NO RESPONSE COMMENT SHEETS WERE PROVIDED NOT |
| | ALL PREVIOUS COMMENTS COULD BE VERIFIED IF THEY HAVE |
| | BEEN CORRECTED. |
| | |
| | 16. SEPARATE PLANS AND PERMITS REQUIRED FOR UNDERGROUND |
| | FUEL STORAGE TANK DISPLAYED ON THE PLANS. |
| | |
| | 17. PLEASE EXPLAIN WHY THE ROOM CONTAINING THE FUEL DAY |
| | TANKS ARE NOT TWO HOUR FIRE RATED. |
| | |
| | 18. COULD NOT LOCATE "STACK EFFECT" WORDING ON THE |
| | MECHANICAL PLANS. PLEASE ADVISE WHERE THIS CAN BE |
| | LOCATED. |
| | |
| | 19. COULD NOT LOCATE ANY SPECIFIC LABELING OR SAFETY |
| | MARKINGS FOR THE DAY FUEL TANKS BEING PROPOSED. |
| | |
| | |