| Date |
Text |
| 2007-07-09 19:52:34 | 2007-07-09 19:52:34 |
| | |
| | |
| | **** UNSAT2RDREVIEW **** |
| | |
| | *** DATURA & OLIVE *** |
| | |
| | |
| | ** PLEASE SEE THERE ARE STILL SEVERAL ITEMS FROM THE |
| | PREVIOUS REVIEW WHICHIS STILL IN NEED OF ADDRESSING. |
| | |
| | ** PLEASE SEE THERE ARE SOME NEW COMMENTS BASED ON |
| | CHANGES, REVISIONS NOW MADE TO PLANS WHICH WERE NOT ON |
| | PREVIOUS REVIEWED PLANS. |
| | PLEASE ALSO SEE NEW NOTES. |
| | |
| | ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT BEEN |
| | SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE NEXT REVIEW. |
| | |
| | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE LETTER SUBMITTED BY MR. ROBERT |
| | SWEDROE FOR SIGNATURE VERIFICATION NEEDS TO BE |
| | NOTARIZED CORRECTLY PER FS 117.05. |
| | THIS WAS IN NOTE #5 FROM PREVIOUS REVIEW. |
| | PLEASE SEE THIS SECTION OF THE FS WHICH CONTAINS |
| | INFORMATION ON WHAT IS REQUIRED FOR NOTARY STATEMENT(S) |
| | ETC. |
| | |
| | 2) NOTE: PLEASE SEE FBC 2004 W/ 2006 FOR THE FLORIDA |
| | ENERGY CODE AND RELEVANT CODES FOR THIS BUILDING. |
| | PLEASE SEE THERE IS INFORMATION NOT YET PROVIDED FOR |
| | LIGHTING CONTROLS. |
| | PLEASE SEE MISSING MAXIMUM TIMES ON OS TYPE DEVICES. |
| | PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE |
| | WITH THE PLANS COMPLETELY. PLEASE SEE THE FIXTURE |
| | LEGEND AND ENERGY CALCULATIONS FOR WATTAGE, TYPE AND |
| | CONTROLS. PLEASE SEE IT IS NOT POSSIBLE FOR THE |
| | LIGHTING CONTROL METHODS TO BE SHOWN AS *MANUAL ON/OFF* |
| | WHEN MANY OF THESE ARE IN FACT AUTOMATED CONTROLS. |
| | PLEASE SEE THE ENERGY CALCULATIONS WOULD ACTUALLY BE |
| | MORE DETAILED FOR AREAS IN WHICH THESE LUMINARIES ARE |
| | LOCATED, THE NUMBER OF LUMINARIES, TYPES ETC. PLEASE |
| | SEE THE SUMMARY SHEETS AND INPUT DATA REPORTS DO NOT |
| | INDICATE ANY EXTERIOR LIGHTING. HOW IS THIS POSSIBLE |
| | WHEN THE PLANS CONTAIN NUMEROUS EXTERIOR LIGHT |
| | FIXTURES? 13-415.ABC.2, 13-415.1.ABC.1.4, |
| | 13-415.ABC.1.3. |
| | PLEASE SEE 13-415.1.AB.1, 13-415.1.A, AND 13-415.2 |
| | |
| | ** PLEASE SEE THE OWNER AGENT WAS NOT SIGNED ON THE |
| | CERTIFICATION SHEETS OF ENERGY CALCULATIONS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THERE ARE AREAS WHICH DO NOT SHOW LIGHTING |
| | CONTROLS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2 AND |
| | .1.3. |
| | PLEASE SEE THAT THE ENERGY CALCULATIONS DO NOT INDICATE |
| | AUTOMATED CONTROLS FOR LIGHTING. SHOWS MANUAL ON/OFF |
| | FOR CONTROL METHODS. |
| | PLEASE SEE 13-415.2 FOR PERFORMANCE OF INTERIOR |
| | LIGHTING. |
| | PLEASE PROVIDE INFORMATION IN DETAIL FOR THIS. PLEASE |
| | SEE THE LIGHTING SHOWN ON PLANS DOES NOT CORRELATE WITH |
| | THE ENERGY CALCULATIONS. |
| | PLEASE SEE ALL OF THE REVISED CHAPTER 13 ITEMS ALONG |
| | WITH THE EXISTING IN THE 2004. |
| | |
| | 3) NOTE:PLEASE SUBMIT THE MANUFACTURE'S SPECS/CUT |
| | SHEETS FOR THE FOLLOWING.FIRE PUMP, FIRE PUMP |
| | CONTROLLER, GENERATOR, ATS, FUEL TANK(S). |
| | PLEASE KNOW ANY OTHER EQUIPMENT SPECS MAY BE REQUESTED |
| | FROM OTHER TRADES. |
| | PLEASE SEE ONLY ONE COPY OF THE GENERATOR SPECS/CUT |
| | SHEETS WAS SUBMITTED. NO OTHER SHEETS FOR ANY OTHER |
| | EQUIPMENT ETC. THIS WAS REQUESTED ON PREVIOUS NOTE #8. |
| | 110.3, 90.7. |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE CLARIFY THE NEW SPECS WHICH INDICATES |
| | THE GENERATOR AS BEING *BI-FUEL*. THIS SEEMS AS THIS IS |
| | INSTALLING AN AFTERMARKET PRODUCT ON THE GENERATOR |
| | UNIT. THISIS A LIFE SAFETY/EMERGENCY SYSTEMS AND |
| | LEGALLY REQUIRED GENERATOR AND ANY ALTERATION OF |
| | EQUIPMENT WITH AFTER MARKER PRODUCTS WILL VOID EPA |
| | CERTIFICATIONS, ANY LISTING STANDARD AND POSSIBLY |
| | WARRANTY OF UNIT. |
| | PLEASE KNOW THE WARRANTY IS NOT AN ISSUE FOR THE AHJ |
| | HOWEVER ANY VOIDING OF EPA AND LISTING STANDARD IS NOT |
| | PERMITTED PER 110.3. |
| | ** PLEASE SEE NOTES WITH RESPECT TO FUEL CONSUMPTION. |
| | |
| | 5) NOTE: PLEASE SEE THE FUEL CONSUMPTION MAY NOT BE |
| | BASED ON THE USE OF NATURAL GAS. ANY LEGALLY REQUIRED, |
| | OR EMERGENCY/LIFE SAFETY SYSTEM MAY NOT DEPEND ON THE |
| | UTILITY. |
| | PLEASE SEE 701.11B3. |
| | PLEASE SEE THE TIME OF 100% IS BASED ON THE MINIMUM |
| | TIMES AS REQUIRED IN NFPA-110, NFPA-101 AND NFPA-20. |
| | THE OTHER RUNNING TIMES FOR LOADS REQUIRED UNDER THE |
| | NEW HOUSE BILL 7121 IS THAT OF THE OTHER LEGALLY |
| | REQUIRED LOADS. |
| | PLEASE ADJUST CALCULATIONS. |
| | |
| | 6) NOTE: PLEASE CORRELATE PLANS FOR ON-SITE FUEL. |
| | PLEASE SEE THE PLANS REFERENCE TO SEE *P* SHEETS FOR |
| | FUEL PIPING ETC HOWEVER THE *P* SHEET P.3.04 SHOWS A |
| | NOTE #27 WHICH INDICATES 500 GALLON DAY TANK, YET RISER |
| | SHOWS A 50 GALLON DAY TANK. PLEASE SEE THE OTHER SHEETS |
| | IN ELECTRICAL PLANS CONTAIN A NOTE AND INFORMATION FOR |
| | THIS SAME TANK AS 500 GALLONS. |
| | PLEASE COORDINATE ALL INFORMATION. |
| | PLEASE SEE NOTE #5 ABOVE WITH RESPECT TO THE FUEL |
| | CONSUMPTION AS THE SUMMARY ON THE RISER SHEET E4.01 |
| | STATES 1500 GALLONS OF FUEL PROVIDED. HOW IS THIS |
| | POSSIBLE WHEN THE PLANS INDICATE 2000 GALLONS OF FUEL? |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT |
| | TO THE TANK, PIPING ETC WHERE DESIGN OF FUEL PIPING |
| | SHOULD BE PART OF THE MECHANICAL PLANS. |
| | PLEASE ALSO SEE COMMENTS WITH RESPECT TO THE SIZE OF |
| | THE TANK AND NEEDING DERM REVIEW, AND STAMPED PLANS FOR |
| | SUBMITTAL. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 7) NOTE: PLEASE SEE THE PREVIOUS NOTE #9 REQUESTED |
| | EMERGENCY BACK UP LIGHTS IN SOME OF THE ROOMS LISTED |
| | BELOW, HOWEVER ONLY THE GENERATOR ROOM NEEDED THE 30FT |
| | CANDLE LEVEL. |
| | PLEASE SEE THE NUMBER OF FIXTURES IS NOT PROHIBITED |
| | JUST UNUSUALLY HIGH IN SOME ROOMS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE FOLLOWING LOCATIONS SHALL CONTAIN |
| | EMERGENCY BATTERY BACK UP LIGHTS OF SOME KIND. |
| | GENERATOR ROOM (TO A LEVEL OF 30FT CANDLES), FIRE |
| | COMMAND ROOM, MAIN ELECTRICAL ROOM, METER CENTER ROOMS, |
| | ELEVATOR EQUIPMENT ROOM(S). |
| | PLEASE SEE NEXT NOTE WITH RESPECT TO STAIRS.NFPA-70 |
| | 110.26, 700.16, 700.12E, NFPA-110 7.3, NFPA-20 5.12.3, |
| | AND .4, NFPA-72 CHAPTER 2 FOR FCRM. |
| | |
| | 8) NOTE:PLEASE SEE PREVIOUS REVIEW NOTES #10 AND |
| | #21. |
| | PLEASE SEE MANY OF THE BATTERY BACK UP FIXTURES WERE |
| | ADDED TO PLANS HOWEVER THE FIXTURES WHICH WERE ADDED DO |
| | NOT COORDINATE WITH THE PHOTO-METRIC PLANS. |
| | PLEASE SEE OTHER AREAS OF PLANS WHERE LIGHTING LEVELS |
| | WERE NOT ADDED TO EGRESS AREAS OF STAIRS AND PATHS. |
| | PLEASE SEE EXIT STAIRS AROUND POOL AREAS, AND OUTSIDE |
| | THE REAR OF BUILDING. |
| | PLEASE BE SURE ALL LEVELS ARE SHOWN UNDER NORMAL AND |
| | EMERGENCY LEVELS. |
| | PLEASE SEE REAR EXIST STAIRS AND REQUIRED BATTERY BACK |
| | UP FIXTURE OF SOME TYPE WILL BE REQUIRED. |
| | |
| | ** PREVIOUS REVIEW NOTE #10** |
| | PLEASE SEE THE STAIRS AS ONE OF THE LIGHTING FIXTURES |
| | ON EACH LEVEL WILL BE REQUIRED TO CONTAIN A BATTERY |
| | BACK UP FIXTURE OF SOME TYPE. PLEASE ALSO PROVIDE THE |
| | MINIMUM PHOTO-METRICS FOR STAIRS UNDER NORMAL AND UNDER |
| | EMERGENCY CONDITIONS. |
| | PLEASE SEE NFPA-101, 7.8., 7.9 |
| | ** PREVIOUS REVIEW NOTE # 21 |
| | PLEASE PROVIDE THE NORMAL AND EMERGENCY PHOTO-METRICS |
| | FOR ALL EGRESS PATHS. PLEASE KNOW THIS WOULD ALSO |
| | INCLUDE POOL DECK AREAS. ETC |
| | LS 101 7.8, 7.9 |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE SEE PREVIOUS NOTE #14 AS NO |
| | MANUFACTURES SPECS/CUT SHEETS WERE SUBMITTED FOR |
| | REVIEW. |
| | PLEASE SUBMIT. FBC 106.1.2, NEC 110.3, 90.7 |
| | ** PREVIOUS REVIEW NOTE #14 ** |
| | PLEASE PROVIDE INFORMATION ON CAR LIFTS AND BE SURE |
| | EQUIPMENT INDICATES LISTING ON EQUIPMENT FROM A NRTL. |
| | 110.3, 90.7 |
| | |
| | 10) NOTE: PLEASE SEE PREVIOUS NOTE #16 WHICH REQUESTED |
| | THE REQUIRED HEIGHT OF THE EPSS EQUIPMENT TO BE STATED |
| | ON PLANS FOR MINIMUM ELEVATION OF EQUIPMENT. PLEASE SEE |
| | THE RESPONSE PLACED A NOTE ON PLANS FOR THIS SECTION OF |
| | THE CODE TO BE MET. PLEASE KNOW THAT QUOTING THE CODE |
| | IN LIEU OF DESIGN DETAILS OR SPECIFIC INFORMATION IS |
| | NOT ACCEPTED BY THE FBC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE ELEVATIONS FOR THE EPSS SYSTEM WHICH |
| | MUST MEET THE ELEVATIONS AS SET-FORTH ON THE 100YEAR |
| | STORM SURGE CHARTS OR *SLOSH* CHARTS PER CHAPTER 7, |
| | 7.3.1 NFPA-110. |
| | |
| | 11) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #25 WHICH |
| | REQUESTED THE MINIMUM WIND LOADS FOR POLES TO BE STATED |
| | ON PLANS AS WELL AS CALCULATIONS FOR THE POLES SPECIFIC |
| | TO THE INSTALLATION. |
| | PLEASE SEE THE RESPONSE TAKES THE REVIEW TO THE *S* |
| | SHEETS WHICH ONLY STATES THE DESIGNS (FOR PROJECT) ARE |
| | TO BE PER FBC EXPOSURE C ETC YET NO SPECIFIC |
| | INFORMATION WAS LOCATED FOR THESE. |
| | PLEASE PROVIDE MORE INFORMATION. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE WIND LOADS AND INFORMATION FOR SITE/ROOF |
| | TOP POLES WHICH ARE REQUIRED TO MEET FBC 140MPH. THIS |
| | WILL BE REVIEWED ONCE SUBMITTED BY THE STRUCTURAL |
| | REVIEWER. PLEASE KNOW THE EFFECTIVE PROJECTED AREA |
| | (EFA) OF FIXTURE. |
| | FBC 106.1.2 |
| | |
| | 12) NOTE: PLEASE SEE PREVIOUS NOTE #27 WHICH REQUESTED |
| | ALL ROOM AND AREA DESIGNATIONS TO BE PLACED ON PLANS. |
| | PLEASE SEE ONE OF THE MAIN LOCATIONS IS FOR |
| | DETERMINATION OF THE DINING ROOM/AREA CIRCUITING ALONG |
| | WITH OTHER AREAS FO THE LIKE AS STATED IN NEC 210.52B1. |
| | PLEASE SEE 210.11C1 AND 220.52 FOR LOADS AS THESE AREAS |
| | ARE NOT YET CONFIRMED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE TO PROVIDE ALL ROOM AND AREA |
| | DESIGNATIONS ON PLANS. PLEASE KNOW SOME AREA |
| | DESIGNATIONS ARE NEEDED TO DETERMINE ARE USE AND REVIEW |
| | FOR CIRCUITING CODE COMPLIANCE AND USE. |
| | FBC 106.1.2 |
| | |
| | 13) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #29. PLEASE |
| | SEE THE RESPONSE MENTIONS THE CONDUCTORS WERE ADJUSTED, |
| | HOWEVER BASED ON THE NEC 310.15B2A, 310.16 ETC THE SIZE |
| | OF THE CONDUCTORS FOR SOME OF THE FEEDERS PARTICULARLY |
| | THE FEEDERS TO REL AND RL ARE OF CONCERN. PLEASE SEE |
| | THESE FEEDERS AS SHOWN ARE NOT RATED FOR THE SIZE AND |
| | LOADS AS SHOWN. |
| | PLEASE SEE COMMENTS ALSO WITH RESPECT TO VOLTAGE DROP |
| | ETC WHICH WILL BE ADJUSTED. |
| | 240.4, 310.16, ETC |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE COMPLETE DE-RATING CALCULATIONS FOR |
| | CONDUITS AND FEEDERS BEING RUN ACROSS ROOF-TOP AREA. |
| | PLEASE KNOW THE TYPE OF ROOF ALONG WITH OTHER FACTORS |
| | WILL HAVE AN AFFECT ON THE TEMPERATURE. PLEASE SEE NEC |
| | 310.16, TABLES FOR DE-RATING AND THE NUMBER OF CURRENT |
| | CARRYING CONDUCTORS. |
| | THE FEEDERS AS SHOWN ON RISER AND PANELS FEEDING THESE |
| | OTHER PANELS ARE NOT OF SUFFICIENT SIZE AS SHOWN ON |
| | PLANS. |
| | PLEASE ADJUST. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | NEC 215.5, 215.3 ETC |
| | |
| | 14) NOTE: PLEASE SEE PREVIOUS NOTE #30 WILL REMAIN AS |
| | THE NOTE ABOVE WHICH IS NOW #13 NEEDS ADJUSTMENT TO |
| | PLANS AND FEEDERS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE VOLTAGE DROP FOR THE SAME FEEDERS AS |
| | NOTED IN NOTE #29. |
| | PLEASE SEE FBC 13-413.ABC.1 |
| | PLEASE ALSO PROVIDE WORST CASE VOLTAGE DROP FOR BRANCH |
| | CIRCUITS AND FEEDERS AS ON PLANS FOR LONGEST RUNS. |
| | |
| | 15) NOTE: PLEASE SEE PREVIOUS NOTE #31. PLEASE SEE THE |
| | RESPONSE MENTIONS THAT A SMOKE DETECTOR DETAIL WAS |
| | ADDED TO FA SHEET. PLEASE SEE THERE MUST HAVE BEEN SOME |
| | MISCOMMUNICATION ON THE PREVIOUS REVIEW NOTE. PLEASE |
| | SEE THE DEVICES AS STATED AND SHOWN ON PLANS WOULD |
| | ACTUALLY BE SMOKE ALARMS. |
| | PLEASE SEE THE PLANS AND NOTES EVEN STATE THE DEVICES |
| | WILL INTERCONNECT AND SOUND AN ALARM FOR ALL DEVICES |
| | INSIDE UNIT. THIS MAKES THE DEVICE WHICH ARE SHOWN AS |
| | SD (SMOKE DETECTORS) ACTUALLY SA (SMOKE ALARMS). THIS |
| | WAS CONFIRMED LAST YEAR AT THE NFPA PANEL SECTION |
| | MEETING AS THE GENERAL ACCEPTED USE OF SD FOR SMOKE |
| | DETECTORS HAS BEEN ACCEPTED WHEN IN FACT THESE DEVICES |
| | SHOULD HAVE BEEN SA FOR SMOKE ALARMS. PLEASE ADJUST |
| | PLANS. |
| | PLEASE SEE IF THESE WERE INDEED *SMOKE DETECTORS* THESE |
| | WOULD REQUIRE OTHER EQUIPMENT ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE NFPA-72, FBC FOR THE DEFINITIONS OF SMOKE |
| | DEVICES. PLEASE DETERMINE IF THESE ARE INDEED DEVICES |
| | WHICH ONLY DETECT AND DO NOT SOUND. |
| | IF DEVICES DETECT AND ONLY PROVIDE SIGNALING TO |
| | HORN/SIREN DEVICES THEN THESE WOULD BE SD/ SMOKE |
| | DETECTORS. |
| | IF DEVICES ARE 120V BATTERY BACK AS SHOWN ON PLANS |
| | WHICH DETECT AND SOUND, THEN THESE DEVICES WOULD BE |
| | CONSIDERED SA/ SMOKE ALARMS. |
| | PLEASE ADJUST PLANS. |
| | NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | 16) NOTE: PLEASE SEE PREVIOUS NOTE #35 FOR ADJUSTMENT |
| | OF THE NOTES FOR SMOKE DEVICES AND PLACEMENT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INCLUDE NOTE ON PLANS FOR PLACEMENT OF SA/SD |
| | DEVICES PER NFPA-72 2002 11.5.1.1, 11.8.3 |
| | |
| | 17) NOTE:PLEASE CLARIFY RESPONSE TO COMMENT #38 FORM |
| | PREVIOUS REVIEW. THE NOTE WAS FOR ARC FAULT PROTECTION |
| | REQUIRED AND THE RESPONSE STATES ONLY BEDROOMS AND THE |
| | BATHROOM IS NOT INCLUDED? PLEASE SEE THE PREVIOUS |
| | COMMENT DID NOT REQUEST FOR BATHROOMS TO BE INCLUDED. |
| | THIS IS TO CLARIFY NOTE MADE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THAT ARC FAULT IS REQUIRED FOR ALL OUTLETS |
| | INCLUDINGRECETPS, LTS, FANS AND SMOKE ALARMS. PLEASE |
| | SEE 210.12. |
| | |
| | 18) NOTE: PLEASE SEE PREVIOUS NOTE #42 WHICH REQUESTED |
| | FOR COORDINATION FO ALL CIRCUITS WITH THE PANEL |
| | SCHEDULES. PLEASE SEE 408.4. PLEASE SEE THE FOLLOWING |
| | TEXT IS EXTRACTED FROM THE NEC COMMENTARY AS THE USE OF |
| | GENERAL LIGHTING AND GENERAL RECEPTACLES ETC IS NOT |
| | PERMITTED. THIS IS PART OF THE REASON FOR COMMENT |
| | NUMBER 12 ABOVE. |
| | * |
| | SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | PLEASE ADJUST CIRCUITING TO BE SPECIFIC TO ALL ROOMS |
| | AND AREAS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COMPLETE ALL CIRCUITING ON PLANS AND CORRELATE |
| | WITH THE PANEL SCHEDULES AND OTHER CIRCUITS ON PLANS. |
| | PLEASE SEE THAT MOST OF THE CIRCUITS ARE SHOWN HOWEVER |
| | SEE REDLINED PLANS AND SEE 9, L8, L9 FOR SOME |
| | EXAMPLES. |
| | 408.4, 310.16, 240.4. |
| | FBC 106.1.2 |
| | |
| | 19) NOTE: PLEASE SEE THIS IS A NEW NOTE. PLEASE SEE |
| | 210.4B AS ALL CIRCUITS ON PANEL WHICH CONTAINS BREAKERS |
| | FEEDING THE SAME YOKE ON MULTI-WIRE BRANCH CIRCUITS |
| | REQUIRES A 2-POLE BREAKER. PLEASE ADJUST PANEL |
| | SCHEDULE. |
| | |
| | 20) NOTE: PLEASE SEE PREVIOUS COMMENT #46. PLEASE SEE |
| | THE NOTE WAS MIS-TYPED WHICH SHOULD HAVE READ ( PLEASE |
| | PROVIDE ALL GENERATOR, ATS, FIRE PUMP AND FIRE PUMP |
| | CONTROLLER INFORMATION ON THE PLANS. |
| | FBC 106.3.5.1.2 |
| | |
| | ** PREVIOUS REVIEW COMMENTS ** |
| | PLEASE PROVIDE ALL GENERATOR, ATS, FIRE PUMP, FIRE |
| | PUMP CONTROLLER ON PLANS. |
| | FBC 106.3.5.1.2 |
| | |
| | 21) NOTE:PLEASE COORDINATE THE FIRE PUMP SIZE AND |
| | LOAD. PLEASE SEE NEC 430 TABLES AND THE LOAD SHOWN ON |
| | THE RISER LOAD SUMMARY. |
| | FBC 106.1.2 |
| | |
| | 22) NOTE: PLEASE SEE THE FEEDERS FROM THE MAIN |
| | ELECTRICAL ROOM RUNNING TO THE EAST ARE BEING SHOWN |
| | GOING THROUGH THE FIRE RATED EXIT CORRIDOR WHICH IS NOT |
| | PERMITTED. PLEASE SEE THIS IS A BUILDING CODE COMMENT. |
| | FBC 1019.1.2 |
| | |
| | 23) NOTE: PLEASE SEE RISER NOW HAS COMPLETED THE |
| | EQUIPMENT FOR MOST THE RETAIL SERVICE. |
| | PLEASE SEE THE RISER STILL SHOWS THIS AS MAIN #6, WHEN |
| | THE MAIN ELECTRICAL ROOM, LOAD SUMMARY ETC INDICATES |
| | THIS AS MAIN #5 WHICH IT IS. |
| | PLEASE ADJUST. |
| | 230.2E |
| | |
| | 24) NOTE: PLEASE SEE THE LOAD SUMMARY FOR THE RETAIL IS |
| | NOT COMPLETE FOR SPACE/RETAIL #5. |
| | |
| | 25) NOTE: PLEASE SEE THE RISER DOES NOT GIVE ANY |
| | INFORMATION FOR NEW MAIN WHICH FEEDS TO NEW R5. PLEASE |
| | SEE NO OCP, SIZE, VOLTAGE, AIC RATINGS ETC IS SHOWN. |
| | PLEASE INCLUDE THE TAPPED FEEDERS FROM THE GUTTER AS |
| | NONE SHOWN ON RISER. |
| | PLEASE COMPLETE. |
| | 230.70, 240, 240.21, 310.16,110.9 ETC. |
| | |
| | 26) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR |
| | RETAIL UNIT AND CORRELATE WITH THE PANEL SCHEDULE. |
| | EXAMPLE: A/C SYSTEM AND EQUIPMENT. |
| | |
| | 27) NOTE: PLEASE SEE MISSING WALL FOR THIS SAME RETAIL |
| | #5 WHERE THERE ARE RECEPTACLES SHOWN AT THE EAST SIDE |
| | HOWEVER NO WALL IS PRESENT. |
| | FBC 106.1.2 |
| | |
| | 28) NOTE: PLEASE SEE THE EXIT LIGHT IN THIS RETAIL |
| | SPACE IS BEING SHOWN ON THE HOUSE PANEL WHICH SHOULD BE |
| | CIRCUITED PER 700.12F OF THE NEC. |
| | |
| | 29) NOTE: PLEASE SEE MISSING SIGN CIRCUIT PER 600.5 AND |
| | LOAD REQUIRED FOR SIGN CIRCUIT. |
| | |
| | 30) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES |
| | PER 210.62, LOADS PER 220.53 ETC. |
| | PLEASE COMPLETE. |
| | |
| | 31) NOTE: PLEASE SEE THE OTHER FUTURE RETAIL SPACES |
| | WILL BE REQUIRED TO CONTAIN A MINIMUM LIGHT FIXTURE AND |
| | CONTROL.THIS WILL BE REQUIRED BY THE FIRE MARSHAL. |
| | PLEASE SEE LS 101 7.8. PLEASE SEE DEPENDING ON THE SIZE |
| | OF THE SPACE,AND FIRE MARSHAL REVIEW A BATTERY BACK |
| | UP LIGHT MAY BE REQUIRED. PLEASE SEE FBC |
| | 13-415.1.ABC.1.1 AND .1.2 FOR AUTOMATED LIGHTING |
| | CONTROLS REQUIRED. |
| | PLEASE ADJUST PLANS. PLEASE BE SURE TO DELETE EXIT LT |
| | FROM RETAIL #5. |
| | |
| | 32) NOTE: PLEASE SEE THE LOADS ON RDP ARE NOT COMPLETED |
| | AND PLEASE CORRELATE WITH THE SUMMARY ON E4.01. NEC |
| | 220. |
| | |
| | 33) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED |
| | FOR ALL CONTINUOUS LOADS TO BE SHOWN AT 125%. PLEASE |
| | SEE DUE TO SOME OF THE COMMENTS ABOVE THE NOTE REMAINS |
| | AND ADJUSTMENTS WILL BE NEEDED. |
| | PLEASE ALSO SEE THE ALL CONTINUOUS LOADS WHICH ARE THAT |
| | AS DEFINED AT 3 OR MORE HOURS ARE TO BE FIGURED. PLEASE |
| | SEE THIS WOULD INCLUDE MOTOR LOADS SUCH AS POOL PUMPS |
| | ETC. |
| | 215.3, 230.42 ETC,. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE ALL CONTINUOUS LOADS AND LARGEST MOTOR |
| | LOADS AT 125% ON EACH PANEL AND THEN FOR THE SERVICE |
| | LOADS. |
| | 230.42, 215.3 ETC. |
| | PLEASE SHOW IN LOAD CALCULATIONS |
| | |
| | 34) NOTE: PLEASE SEE THE ELEVATOR ROOM LAYOUT OF |
| | DISCONNECTS DO NOT SEEM TO MEET 110.26 BASED ON THE |
| | SCALE ON PLANS. |
| | PLEASE ADJUST. |
| | |
| | 35) NOTE: PLEASE SEE THE RESPONSE FOR PREVIOUS NOTE # |
| | 18 MENTIONS TO SEE LETTER FROM MR. STEVEN FELLER PE. |
| | PLEASE SEE THAT NO LETTER IN THE SUBMITTED PACKAGE AND |
| | SUPPORTING DOCUMENTS COULD LOCATE ANY LETTER FOR A |
| | RESPONSE. |
| | THIS PREVIOUS NOTE WAS FOR THE MENTIONED HOUSE BILL |
| | 7121 AND REQUIRED FUEL. |
| | PLEASE CLARIFY. |
| | |
| | 36) NOTE: PLEASE KNOW ALL LOW VOLTAGE SYSTEMS ASSHOWN |
| | ON PLANS ARE REQUIRED TO BE UNDER SEPARATE PERMITS. |
| | PLEASE SEE THE CATV, PHONE, CAMERAS AS SHOWN MAY BE ON |
| | ONE PERMIT AND MAY REFERENCE BACK TO THESE PLANS |
| | HOWEVER THE VALUE AND PERMIT FEES FOR THIS SCOPE OF |
| | WORK WILL BE REQUIRED TO BE SEPARATE. |
| | PLEASE SEE THE LOW VOLTAGE FOR FIRE ALARM WILL REQUIRE |
| | SEPARATE PLANS FOR PERMITTING. |
| | PLEASE SEE THAT ANY LOW VOLTAGE SECURITY/BURGLAR ALARMS |
| | SYSTEMS IS SEPARATE PERMIT AS THESE SYSTEMS ARE |
| | REPORTED THROUGH THE POLICE DEPT. |
| | ** THIS NOTE WAS GIVEN FOR INFORMATIONAL PURPOSE AND NO |
| | CHANGES ARE NEEDED TO PLANS. |
| | |
| | 37) NOTE: PLEASE SEE AS SOME COMMENTS ARE REPEATED FROM |
| | PREVIOUS REVIEW, PLEASE SEE COPY OF FS 553.80(2)(B) IS |
| | GIVEN AS A NOTICE ONLY AT THIS TIME. |
| | |
| | ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET |
| | SUBMITTED FOR REVIEW, THERE ARE ITEMS WHICH CAN NOT BE |
| | REVIEWED AT THIS TIME. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-09 07:29:45 | 2007-07-09 07:29:45 |
| | REVIEW IN PROGRESS |
| 2007-07-07 19:16:47 | 2007-07-07 19:16:47 |
| | ON ROLL OF ELECTRICAL AN ARCHITECTURAL IN ELEC FOR |
| | REVIEW. REMOVED FROM INCOMING AND WILL BE RETURNED TO |
| | INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW |
| | IS COMPLETED. |