Date Text
2007-07-09 19:52:342007-07-09 19:52:34
  
  
 **** UNSAT2RDREVIEW ****
  
 *** DATURA & OLIVE ***
  
  
 ** PLEASE SEE THERE ARE STILL SEVERAL ITEMS FROM THE
 PREVIOUS REVIEW WHICHIS STILL IN NEED OF ADDRESSING.
  
 ** PLEASE SEE THERE ARE SOME NEW COMMENTS BASED ON
 CHANGES, REVISIONS NOW MADE TO PLANS WHICH WERE NOT ON
 PREVIOUS REVIEWED PLANS.
 PLEASE ALSO SEE NEW NOTES.
  
 ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT BEEN
 SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE: PLEASE SEE THE LETTER SUBMITTED BY MR. ROBERT
 SWEDROE FOR SIGNATURE VERIFICATION NEEDS TO BE
 NOTARIZED CORRECTLY PER FS 117.05.
 THIS WAS IN NOTE #5 FROM PREVIOUS REVIEW.
 PLEASE SEE THIS SECTION OF THE FS WHICH CONTAINS
 INFORMATION ON WHAT IS REQUIRED FOR NOTARY STATEMENT(S)
 ETC.
  
 2) NOTE: PLEASE SEE FBC 2004 W/ 2006 FOR THE FLORIDA
 ENERGY CODE AND RELEVANT CODES FOR THIS BUILDING.
 PLEASE SEE THERE IS INFORMATION NOT YET PROVIDED FOR
 LIGHTING CONTROLS.
 PLEASE SEE MISSING MAXIMUM TIMES ON OS TYPE DEVICES.
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE
 WITH THE PLANS COMPLETELY. PLEASE SEE THE FIXTURE
 LEGEND AND ENERGY CALCULATIONS FOR WATTAGE, TYPE AND
 CONTROLS. PLEASE SEE IT IS NOT POSSIBLE FOR THE
 LIGHTING CONTROL METHODS TO BE SHOWN AS *MANUAL ON/OFF*
 WHEN MANY OF THESE ARE IN FACT AUTOMATED CONTROLS.
 PLEASE SEE THE ENERGY CALCULATIONS WOULD ACTUALLY BE
 MORE DETAILED FOR AREAS IN WHICH THESE LUMINARIES ARE
 LOCATED, THE NUMBER OF LUMINARIES, TYPES ETC. PLEASE
 SEE THE SUMMARY SHEETS AND INPUT DATA REPORTS DO NOT
 INDICATE ANY EXTERIOR LIGHTING. HOW IS THIS POSSIBLE
 WHEN THE PLANS CONTAIN NUMEROUS EXTERIOR LIGHT
 FIXTURES? 13-415.ABC.2, 13-415.1.ABC.1.4,
 13-415.ABC.1.3.
 PLEASE SEE 13-415.1.AB.1, 13-415.1.A, AND 13-415.2
  
 ** PLEASE SEE THE OWNER AGENT WAS NOT SIGNED ON THE
 CERTIFICATION SHEETS OF ENERGY CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THERE ARE AREAS WHICH DO NOT SHOW LIGHTING
 CONTROLS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE SEE THAT THE ENERGY CALCULATIONS DO NOT INDICATE
 AUTOMATED CONTROLS FOR LIGHTING. SHOWS MANUAL ON/OFF
 FOR CONTROL METHODS.
 PLEASE SEE 13-415.2 FOR PERFORMANCE OF INTERIOR
 LIGHTING.
 PLEASE PROVIDE INFORMATION IN DETAIL FOR THIS. PLEASE
 SEE THE LIGHTING SHOWN ON PLANS DOES NOT CORRELATE WITH
 THE ENERGY CALCULATIONS.
 PLEASE SEE ALL OF THE REVISED CHAPTER 13 ITEMS ALONG
 WITH THE EXISTING IN THE 2004.
  
 3) NOTE:PLEASE SUBMIT THE MANUFACTURE'S SPECS/CUT
 SHEETS FOR THE FOLLOWING.FIRE PUMP, FIRE PUMP
 CONTROLLER, GENERATOR, ATS, FUEL TANK(S).
 PLEASE KNOW ANY OTHER EQUIPMENT SPECS MAY BE REQUESTED
 FROM OTHER TRADES.
 PLEASE SEE ONLY ONE COPY OF THE GENERATOR SPECS/CUT
 SHEETS WAS SUBMITTED. NO OTHER SHEETS FOR ANY OTHER
 EQUIPMENT ETC. THIS WAS REQUESTED ON PREVIOUS NOTE #8.
 110.3, 90.7.
 FBC 106.1.2
  
 4) NOTE: PLEASE CLARIFY THE NEW SPECS WHICH INDICATES
 THE GENERATOR AS BEING *BI-FUEL*. THIS SEEMS AS THIS IS
 INSTALLING AN AFTERMARKET PRODUCT ON THE GENERATOR
 UNIT. THISIS A LIFE SAFETY/EMERGENCY SYSTEMS AND
 LEGALLY REQUIRED GENERATOR AND ANY ALTERATION OF
 EQUIPMENT WITH AFTER MARKER PRODUCTS WILL VOID EPA
 CERTIFICATIONS, ANY LISTING STANDARD AND POSSIBLY
 WARRANTY OF UNIT.
 PLEASE KNOW THE WARRANTY IS NOT AN ISSUE FOR THE AHJ
 HOWEVER ANY VOIDING OF EPA AND LISTING STANDARD IS NOT
 PERMITTED PER 110.3.
 ** PLEASE SEE NOTES WITH RESPECT TO FUEL CONSUMPTION.
  
 5) NOTE: PLEASE SEE THE FUEL CONSUMPTION MAY NOT BE
 BASED ON THE USE OF NATURAL GAS. ANY LEGALLY REQUIRED,
 OR EMERGENCY/LIFE SAFETY SYSTEM MAY NOT DEPEND ON THE
 UTILITY.
 PLEASE SEE 701.11B3.
 PLEASE SEE THE TIME OF 100% IS BASED ON THE MINIMUM
 TIMES AS REQUIRED IN NFPA-110, NFPA-101 AND NFPA-20.
 THE OTHER RUNNING TIMES FOR LOADS REQUIRED UNDER THE
 NEW HOUSE BILL 7121 IS THAT OF THE OTHER LEGALLY
 REQUIRED LOADS.
 PLEASE ADJUST CALCULATIONS.
  
 6) NOTE: PLEASE CORRELATE PLANS FOR ON-SITE FUEL.
 PLEASE SEE THE PLANS REFERENCE TO SEE *P* SHEETS FOR
 FUEL PIPING ETC HOWEVER THE *P* SHEET P.3.04 SHOWS A
 NOTE #27 WHICH INDICATES 500 GALLON DAY TANK, YET RISER
 SHOWS A 50 GALLON DAY TANK. PLEASE SEE THE OTHER SHEETS
 IN ELECTRICAL PLANS CONTAIN A NOTE AND INFORMATION FOR
 THIS SAME TANK AS 500 GALLONS.
 PLEASE COORDINATE ALL INFORMATION.
 PLEASE SEE NOTE #5 ABOVE WITH RESPECT TO THE FUEL
 CONSUMPTION AS THE SUMMARY ON THE RISER SHEET E4.01
 STATES 1500 GALLONS OF FUEL PROVIDED. HOW IS THIS
 POSSIBLE WHEN THE PLANS INDICATE 2000 GALLONS OF FUEL?
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT
 TO THE TANK, PIPING ETC WHERE DESIGN OF FUEL PIPING
 SHOULD BE PART OF THE MECHANICAL PLANS.
 PLEASE ALSO SEE COMMENTS WITH RESPECT TO THE SIZE OF
 THE TANK AND NEEDING DERM REVIEW, AND STAMPED PLANS FOR
 SUBMITTAL.
 FBC 106.1.2 FOR COORDINATION.
  
 7) NOTE: PLEASE SEE THE PREVIOUS NOTE #9 REQUESTED
 EMERGENCY BACK UP LIGHTS IN SOME OF THE ROOMS LISTED
 BELOW, HOWEVER ONLY THE GENERATOR ROOM NEEDED THE 30FT
 CANDLE LEVEL.
 PLEASE SEE THE NUMBER OF FIXTURES IS NOT PROHIBITED
 JUST UNUSUALLY HIGH IN SOME ROOMS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE FOLLOWING LOCATIONS SHALL CONTAIN
 EMERGENCY BATTERY BACK UP LIGHTS OF SOME KIND.
 GENERATOR ROOM (TO A LEVEL OF 30FT CANDLES), FIRE
 COMMAND ROOM, MAIN ELECTRICAL ROOM, METER CENTER ROOMS,
 ELEVATOR EQUIPMENT ROOM(S).
 PLEASE SEE NEXT NOTE WITH RESPECT TO STAIRS.NFPA-70
 110.26, 700.16, 700.12E, NFPA-110 7.3, NFPA-20 5.12.3,
 AND .4, NFPA-72 CHAPTER 2 FOR FCRM.
  
 8) NOTE:PLEASE SEE PREVIOUS REVIEW NOTES #10 AND
 #21.
 PLEASE SEE MANY OF THE BATTERY BACK UP FIXTURES WERE
 ADDED TO PLANS HOWEVER THE FIXTURES WHICH WERE ADDED DO
 NOT COORDINATE WITH THE PHOTO-METRIC PLANS.
 PLEASE SEE OTHER AREAS OF PLANS WHERE LIGHTING LEVELS
 WERE NOT ADDED TO EGRESS AREAS OF STAIRS AND PATHS.
 PLEASE SEE EXIT STAIRS AROUND POOL AREAS, AND OUTSIDE
 THE REAR OF BUILDING.
 PLEASE BE SURE ALL LEVELS ARE SHOWN UNDER NORMAL AND
 EMERGENCY LEVELS.
 PLEASE SEE REAR EXIST STAIRS AND REQUIRED BATTERY BACK
 UP FIXTURE OF SOME TYPE WILL BE REQUIRED.
  
 ** PREVIOUS REVIEW NOTE #10**
 PLEASE SEE THE STAIRS AS ONE OF THE LIGHTING FIXTURES
 ON EACH LEVEL WILL BE REQUIRED TO CONTAIN A BATTERY
 BACK UP FIXTURE OF SOME TYPE. PLEASE ALSO PROVIDE THE
 MINIMUM PHOTO-METRICS FOR STAIRS UNDER NORMAL AND UNDER
 EMERGENCY CONDITIONS.
 PLEASE SEE NFPA-101, 7.8., 7.9
 ** PREVIOUS REVIEW NOTE # 21
 PLEASE PROVIDE THE NORMAL AND EMERGENCY PHOTO-METRICS
 FOR ALL EGRESS PATHS. PLEASE KNOW THIS WOULD ALSO
 INCLUDE POOL DECK AREAS. ETC
 LS 101 7.8, 7.9
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE PREVIOUS NOTE #14 AS NO
 MANUFACTURES SPECS/CUT SHEETS WERE SUBMITTED FOR
 REVIEW.
 PLEASE SUBMIT. FBC 106.1.2, NEC 110.3, 90.7
 ** PREVIOUS REVIEW NOTE #14 **
 PLEASE PROVIDE INFORMATION ON CAR LIFTS AND BE SURE
 EQUIPMENT INDICATES LISTING ON EQUIPMENT FROM A NRTL.
 110.3, 90.7
  
 10) NOTE: PLEASE SEE PREVIOUS NOTE #16 WHICH REQUESTED
 THE REQUIRED HEIGHT OF THE EPSS EQUIPMENT TO BE STATED
 ON PLANS FOR MINIMUM ELEVATION OF EQUIPMENT. PLEASE SEE
 THE RESPONSE PLACED A NOTE ON PLANS FOR THIS SECTION OF
 THE CODE TO BE MET. PLEASE KNOW THAT QUOTING THE CODE
 IN LIEU OF DESIGN DETAILS OR SPECIFIC INFORMATION IS
 NOT ACCEPTED BY THE FBC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ELEVATIONS FOR THE EPSS SYSTEM WHICH
 MUST MEET THE ELEVATIONS AS SET-FORTH ON THE 100YEAR
 STORM SURGE CHARTS OR *SLOSH* CHARTS PER CHAPTER 7,
 7.3.1 NFPA-110.
  
 11) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #25 WHICH
 REQUESTED THE MINIMUM WIND LOADS FOR POLES TO BE STATED
 ON PLANS AS WELL AS CALCULATIONS FOR THE POLES SPECIFIC
 TO THE INSTALLATION.
 PLEASE SEE THE RESPONSE TAKES THE REVIEW TO THE *S*
 SHEETS WHICH ONLY STATES THE DESIGNS (FOR PROJECT) ARE
 TO BE PER FBC EXPOSURE C ETC YET NO SPECIFIC
 INFORMATION WAS LOCATED FOR THESE.
 PLEASE PROVIDE MORE INFORMATION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE WIND LOADS AND INFORMATION FOR SITE/ROOF
 TOP POLES WHICH ARE REQUIRED TO MEET FBC 140MPH. THIS
 WILL BE REVIEWED ONCE SUBMITTED BY THE STRUCTURAL
 REVIEWER. PLEASE KNOW THE EFFECTIVE PROJECTED AREA
 (EFA) OF FIXTURE.
 FBC 106.1.2
  
 12) NOTE: PLEASE SEE PREVIOUS NOTE #27 WHICH REQUESTED
 ALL ROOM AND AREA DESIGNATIONS TO BE PLACED ON PLANS.
 PLEASE SEE ONE OF THE MAIN LOCATIONS IS FOR
 DETERMINATION OF THE DINING ROOM/AREA CIRCUITING ALONG
 WITH OTHER AREAS FO THE LIKE AS STATED IN NEC 210.52B1.
 PLEASE SEE 210.11C1 AND 220.52 FOR LOADS AS THESE AREAS
 ARE NOT YET CONFIRMED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TO PROVIDE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS. PLEASE KNOW SOME AREA
 DESIGNATIONS ARE NEEDED TO DETERMINE ARE USE AND REVIEW
 FOR CIRCUITING CODE COMPLIANCE AND USE.
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #29. PLEASE
 SEE THE RESPONSE MENTIONS THE CONDUCTORS WERE ADJUSTED,
 HOWEVER BASED ON THE NEC 310.15B2A, 310.16 ETC THE SIZE
 OF THE CONDUCTORS FOR SOME OF THE FEEDERS PARTICULARLY
 THE FEEDERS TO REL AND RL ARE OF CONCERN. PLEASE SEE
 THESE FEEDERS AS SHOWN ARE NOT RATED FOR THE SIZE AND
 LOADS AS SHOWN.
 PLEASE SEE COMMENTS ALSO WITH RESPECT TO VOLTAGE DROP
 ETC WHICH WILL BE ADJUSTED.
 240.4, 310.16, ETC
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE COMPLETE DE-RATING CALCULATIONS FOR
 CONDUITS AND FEEDERS BEING RUN ACROSS ROOF-TOP AREA.
 PLEASE KNOW THE TYPE OF ROOF ALONG WITH OTHER FACTORS
 WILL HAVE AN AFFECT ON THE TEMPERATURE. PLEASE SEE NEC
 310.16, TABLES FOR DE-RATING AND THE NUMBER OF CURRENT
 CARRYING CONDUCTORS.
 THE FEEDERS AS SHOWN ON RISER AND PANELS FEEDING THESE
 OTHER PANELS ARE NOT OF SUFFICIENT SIZE AS SHOWN ON
 PLANS.
 PLEASE ADJUST.
 FBC 106.3.5.1.2, 106.1.2
 NEC 215.5, 215.3 ETC
  
 14) NOTE: PLEASE SEE PREVIOUS NOTE #30 WILL REMAIN AS
 THE NOTE ABOVE WHICH IS NOW #13 NEEDS ADJUSTMENT TO
 PLANS AND FEEDERS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE VOLTAGE DROP FOR THE SAME FEEDERS AS
 NOTED IN NOTE #29.
 PLEASE SEE FBC 13-413.ABC.1
 PLEASE ALSO PROVIDE WORST CASE VOLTAGE DROP FOR BRANCH
 CIRCUITS AND FEEDERS AS ON PLANS FOR LONGEST RUNS.
  
 15) NOTE: PLEASE SEE PREVIOUS NOTE #31. PLEASE SEE THE
 RESPONSE MENTIONS THAT A SMOKE DETECTOR DETAIL WAS
 ADDED TO FA SHEET. PLEASE SEE THERE MUST HAVE BEEN SOME
 MISCOMMUNICATION ON THE PREVIOUS REVIEW NOTE. PLEASE
 SEE THE DEVICES AS STATED AND SHOWN ON PLANS WOULD
 ACTUALLY BE SMOKE ALARMS.
 PLEASE SEE THE PLANS AND NOTES EVEN STATE THE DEVICES
 WILL INTERCONNECT AND SOUND AN ALARM FOR ALL DEVICES
 INSIDE UNIT. THIS MAKES THE DEVICE WHICH ARE SHOWN AS
 SD (SMOKE DETECTORS) ACTUALLY SA (SMOKE ALARMS). THIS
 WAS CONFIRMED LAST YEAR AT THE NFPA PANEL SECTION
 MEETING AS THE GENERAL ACCEPTED USE OF SD FOR SMOKE
 DETECTORS HAS BEEN ACCEPTED WHEN IN FACT THESE DEVICES
 SHOULD HAVE BEEN SA FOR SMOKE ALARMS. PLEASE ADJUST
 PLANS.
 PLEASE SEE IF THESE WERE INDEED *SMOKE DETECTORS* THESE
 WOULD REQUIRE OTHER EQUIPMENT ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-72, FBC FOR THE DEFINITIONS OF SMOKE
 DEVICES. PLEASE DETERMINE IF THESE ARE INDEED DEVICES
 WHICH ONLY DETECT AND DO NOT SOUND.
 IF DEVICES DETECT AND ONLY PROVIDE SIGNALING TO
 HORN/SIREN DEVICES THEN THESE WOULD BE SD/ SMOKE
 DETECTORS.
 IF DEVICES ARE 120V BATTERY BACK AS SHOWN ON PLANS
 WHICH DETECT AND SOUND, THEN THESE DEVICES WOULD BE
 CONSIDERED SA/ SMOKE ALARMS.
 PLEASE ADJUST PLANS.
 NFPA-72 11.5.1.1, 11.8.3
  
 16) NOTE: PLEASE SEE PREVIOUS NOTE #35 FOR ADJUSTMENT
 OF THE NOTES FOR SMOKE DEVICES AND PLACEMENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE NOTE ON PLANS FOR PLACEMENT OF SA/SD
 DEVICES PER NFPA-72 2002 11.5.1.1, 11.8.3
  
 17) NOTE:PLEASE CLARIFY RESPONSE TO COMMENT #38 FORM
 PREVIOUS REVIEW. THE NOTE WAS FOR ARC FAULT PROTECTION
 REQUIRED AND THE RESPONSE STATES ONLY BEDROOMS AND THE
 BATHROOM IS NOT INCLUDED? PLEASE SEE THE PREVIOUS
 COMMENT DID NOT REQUEST FOR BATHROOMS TO BE INCLUDED.
 THIS IS TO CLARIFY NOTE MADE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT ARC FAULT IS REQUIRED FOR ALL OUTLETS
 INCLUDINGRECETPS, LTS, FANS AND SMOKE ALARMS. PLEASE
 SEE 210.12.
  
 18) NOTE: PLEASE SEE PREVIOUS NOTE #42 WHICH REQUESTED
 FOR COORDINATION FO ALL CIRCUITS WITH THE PANEL
 SCHEDULES. PLEASE SEE 408.4. PLEASE SEE THE FOLLOWING
 TEXT IS EXTRACTED FROM THE NEC COMMENTARY AS THE USE OF
 GENERAL LIGHTING AND GENERAL RECEPTACLES ETC IS NOT
 PERMITTED. THIS IS PART OF THE REASON FOR COMMENT
 NUMBER 12 ABOVE.
 *
 SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 PLEASE ADJUST CIRCUITING TO BE SPECIFIC TO ALL ROOMS
 AND AREAS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE ALL CIRCUITING ON PLANS AND CORRELATE
 WITH THE PANEL SCHEDULES AND OTHER CIRCUITS ON PLANS.
 PLEASE SEE THAT MOST OF THE CIRCUITS ARE SHOWN HOWEVER
 SEE REDLINED PLANS AND SEE 9, L8, L9 FOR SOME
 EXAMPLES.
 408.4, 310.16, 240.4.
 FBC 106.1.2
  
 19) NOTE: PLEASE SEE THIS IS A NEW NOTE. PLEASE SEE
 210.4B AS ALL CIRCUITS ON PANEL WHICH CONTAINS BREAKERS
 FEEDING THE SAME YOKE ON MULTI-WIRE BRANCH CIRCUITS
 REQUIRES A 2-POLE BREAKER. PLEASE ADJUST PANEL
 SCHEDULE.
  
 20) NOTE: PLEASE SEE PREVIOUS COMMENT #46. PLEASE SEE
 THE NOTE WAS MIS-TYPED WHICH SHOULD HAVE READ ( PLEASE
 PROVIDE ALL GENERATOR, ATS, FIRE PUMP AND FIRE PUMP
 CONTROLLER INFORMATION ON THE PLANS.
 FBC 106.3.5.1.2
  
 ** PREVIOUS REVIEW COMMENTS **
 PLEASE PROVIDE ALL GENERATOR, ATS, FIRE PUMP, FIRE
 PUMP CONTROLLER ON PLANS.
 FBC 106.3.5.1.2
  
 21) NOTE:PLEASE COORDINATE THE FIRE PUMP SIZE AND
 LOAD. PLEASE SEE NEC 430 TABLES AND THE LOAD SHOWN ON
 THE RISER LOAD SUMMARY.
 FBC 106.1.2
  
 22) NOTE: PLEASE SEE THE FEEDERS FROM THE MAIN
 ELECTRICAL ROOM RUNNING TO THE EAST ARE BEING SHOWN
 GOING THROUGH THE FIRE RATED EXIT CORRIDOR WHICH IS NOT
 PERMITTED. PLEASE SEE THIS IS A BUILDING CODE COMMENT.
 FBC 1019.1.2
  
 23) NOTE: PLEASE SEE RISER NOW HAS COMPLETED THE
 EQUIPMENT FOR MOST THE RETAIL SERVICE.
 PLEASE SEE THE RISER STILL SHOWS THIS AS MAIN #6, WHEN
 THE MAIN ELECTRICAL ROOM, LOAD SUMMARY ETC INDICATES
 THIS AS MAIN #5 WHICH IT IS.
 PLEASE ADJUST.
 230.2E
  
 24) NOTE: PLEASE SEE THE LOAD SUMMARY FOR THE RETAIL IS
 NOT COMPLETE FOR SPACE/RETAIL #5.
  
 25) NOTE: PLEASE SEE THE RISER DOES NOT GIVE ANY
 INFORMATION FOR NEW MAIN WHICH FEEDS TO NEW R5. PLEASE
 SEE NO OCP, SIZE, VOLTAGE, AIC RATINGS ETC IS SHOWN.
 PLEASE INCLUDE THE TAPPED FEEDERS FROM THE GUTTER AS
 NONE SHOWN ON RISER.
 PLEASE COMPLETE.
 230.70, 240, 240.21, 310.16,110.9 ETC.
  
 26) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR
 RETAIL UNIT AND CORRELATE WITH THE PANEL SCHEDULE.
 EXAMPLE: A/C SYSTEM AND EQUIPMENT.
  
 27) NOTE: PLEASE SEE MISSING WALL FOR THIS SAME RETAIL
 #5 WHERE THERE ARE RECEPTACLES SHOWN AT THE EAST SIDE
 HOWEVER NO WALL IS PRESENT.
 FBC 106.1.2
  
 28) NOTE: PLEASE SEE THE EXIT LIGHT IN THIS RETAIL
 SPACE IS BEING SHOWN ON THE HOUSE PANEL WHICH SHOULD BE
 CIRCUITED PER 700.12F OF THE NEC.
  
 29) NOTE: PLEASE SEE MISSING SIGN CIRCUIT PER 600.5 AND
 LOAD REQUIRED FOR SIGN CIRCUIT.
  
 30) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES
 PER 210.62, LOADS PER 220.53 ETC.
 PLEASE COMPLETE.
  
 31) NOTE: PLEASE SEE THE OTHER FUTURE RETAIL SPACES
 WILL BE REQUIRED TO CONTAIN A MINIMUM LIGHT FIXTURE AND
 CONTROL.THIS WILL BE REQUIRED BY THE FIRE MARSHAL.
 PLEASE SEE LS 101 7.8. PLEASE SEE DEPENDING ON THE SIZE
 OF THE SPACE,AND FIRE MARSHAL REVIEW A BATTERY BACK
 UP LIGHT MAY BE REQUIRED. PLEASE SEE FBC
 13-415.1.ABC.1.1 AND .1.2 FOR AUTOMATED LIGHTING
 CONTROLS REQUIRED.
 PLEASE ADJUST PLANS. PLEASE BE SURE TO DELETE EXIT LT
 FROM RETAIL #5.
  
 32) NOTE: PLEASE SEE THE LOADS ON RDP ARE NOT COMPLETED
 AND PLEASE CORRELATE WITH THE SUMMARY ON E4.01. NEC
 220.
  
 33) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED
 FOR ALL CONTINUOUS LOADS TO BE SHOWN AT 125%. PLEASE
 SEE DUE TO SOME OF THE COMMENTS ABOVE THE NOTE REMAINS
 AND ADJUSTMENTS WILL BE NEEDED.
 PLEASE ALSO SEE THE ALL CONTINUOUS LOADS WHICH ARE THAT
 AS DEFINED AT 3 OR MORE HOURS ARE TO BE FIGURED. PLEASE
 SEE THIS WOULD INCLUDE MOTOR LOADS SUCH AS POOL PUMPS
 ETC.
 215.3, 230.42 ETC,.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL CONTINUOUS LOADS AND LARGEST MOTOR
 LOADS AT 125% ON EACH PANEL AND THEN FOR THE SERVICE
 LOADS.
 230.42, 215.3 ETC.
 PLEASE SHOW IN LOAD CALCULATIONS
  
 34) NOTE: PLEASE SEE THE ELEVATOR ROOM LAYOUT OF
 DISCONNECTS DO NOT SEEM TO MEET 110.26 BASED ON THE
 SCALE ON PLANS.
 PLEASE ADJUST.
  
 35) NOTE: PLEASE SEE THE RESPONSE FOR PREVIOUS NOTE #
 18 MENTIONS TO SEE LETTER FROM MR. STEVEN FELLER PE.
 PLEASE SEE THAT NO LETTER IN THE SUBMITTED PACKAGE AND
 SUPPORTING DOCUMENTS COULD LOCATE ANY LETTER FOR A
 RESPONSE.
 THIS PREVIOUS NOTE WAS FOR THE MENTIONED HOUSE BILL
 7121 AND REQUIRED FUEL.
 PLEASE CLARIFY.
  
 36) NOTE: PLEASE KNOW ALL LOW VOLTAGE SYSTEMS ASSHOWN
 ON PLANS ARE REQUIRED TO BE UNDER SEPARATE PERMITS.
 PLEASE SEE THE CATV, PHONE, CAMERAS AS SHOWN MAY BE ON
 ONE PERMIT AND MAY REFERENCE BACK TO THESE PLANS
 HOWEVER THE VALUE AND PERMIT FEES FOR THIS SCOPE OF
 WORK WILL BE REQUIRED TO BE SEPARATE.
 PLEASE SEE THE LOW VOLTAGE FOR FIRE ALARM WILL REQUIRE
 SEPARATE PLANS FOR PERMITTING.
 PLEASE SEE THAT ANY LOW VOLTAGE SECURITY/BURGLAR ALARMS
 SYSTEMS IS SEPARATE PERMIT AS THESE SYSTEMS ARE
 REPORTED THROUGH THE POLICE DEPT.
 ** THIS NOTE WAS GIVEN FOR INFORMATIONAL PURPOSE AND NO
 CHANGES ARE NEEDED TO PLANS.
  
 37) NOTE: PLEASE SEE AS SOME COMMENTS ARE REPEATED FROM
 PREVIOUS REVIEW, PLEASE SEE COPY OF FS 553.80(2)(B) IS
 GIVEN AS A NOTICE ONLY AT THIS TIME.
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET
 SUBMITTED FOR REVIEW, THERE ARE ITEMS WHICH CAN NOT BE
 REVIEWED AT THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-09 07:29:452007-07-09 07:29:45
 REVIEW IN PROGRESS
2007-07-07 19:16:472007-07-07 19:16:47
 ON ROLL OF ELECTRICAL AN ARCHITECTURAL IN ELEC FOR
 REVIEW. REMOVED FROM INCOMING AND WILL BE RETURNED TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW
 IS COMPLETED.