Plan Review Notes
Plan Review Notes For Permit 07020735
Permit Number 07020735
Review Stop B
Sequence Number 2
Notes
Date Text
2007-08-26 10:45:35302 DATURA 2ND REVIEW,
 9 STORY R-2,MERCANTILE& S-2
  
 BUILDING PLAN REVIEW
 PERMIT: 07020735
 ADDRESS: 302 DATURA ST
 CONT: PEGASUS CONSTRUCTION
 TEL: (954)946-4227
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
 2) 2ND REQUEST, (3) ORIGINAL SIGNED AND SEALED SOILS
 REPORTS WILL BE REQUIRED ONLY (2) SUBMITTED. FBC
 1802.2.1 QUESTIONABLE SOILS,
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . REPORTS
 HAVE COPIED SIGNATURES, NOT ORIGINALS.
  
 3) NOTE,FL S S 713.13NOTICE OF COMMENCEMENT, TO BE
 FILED WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF
 THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4)2ND REQUEST,WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY S. 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561) 805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 5-6 COMPLIED.
  
 7) BUILDING PROVISO:109.3.10*IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PREFORMED IN A MANNERSO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO CONSENT BY THE APPLICABLE PROPERTY
 OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE
 FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING
 STANDARDS TO PRESERVE THE POSITIVE PATTERNS OF THE
 AFFECTED SITES. ACCORDINGLY, DEVELOPERS,CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL DEVELOPMENT,
 INCLUDING ADDITIONS, POOLS, PATIOS, DRIVEWAYS, DECKS,
 OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 DECREASE IN EXCESS OF 800SQ FT OF PERMEABLE LAND AREA
 ON ANY PARCEL SHALL AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO THE INSPECTOR
 IN ORDER TO RECEIVE APPROVAL OF THE FINAL INSPECTION.
  
  
 8) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE
 CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO
 MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR
 PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAIL TO
 COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS
 EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 9) THE ARCHITECTURAL COVERSHEET UNDER THE PROJECT DATA
 SUMMARY:
  
 9A)2ND REQUEST, LIFE SAFETY SHEET STILL INDICATES THE
 2004 WITHOUT UPDATES, PLANS ARE DESIGNED UNDER THE 2004
 FBC, PLANS SUBMITTED TO THE CITY AFTER DEC. 8, 2006 ARE
 TO BE DESIGNED TO THE 2006 FBC.
  
 9B) 2ND REQUEST, THE ARCHITECTURAL COVER SHEET BUILDING
 AREA CALCULATIONS STILL LIST MEZZANINE IN BODY OF TEXT.
 THEPLANS ALSO INDICATE THIS IS TO BE A 8 STORY
 BUILDING. THE SO CALLED MEZZANINE LEVEL DOES NOT MEET
 THE DEFINITION OF A MEZZANINE THIS IS THE SECOND STORY,
 CREATING A NINE STORY BUILDING. SEE 502 DEFINITION OF
 MEZZANINE.
  
 9C) COMPLIED.
  
 10) COMPLIED.
  
 11) THE LIFE SAFETY SHEET LS.1 DOES NOT CORRELATE WITH
 A2.31 ON THE SOUTH AND EAST GARAGE WALLS. SEE A2.31.
  
 12-13) COMPLIED.
  
 14)2ND REQUEST,A2.01INDICATES THE USE OF CAR
 LIFTS. PLEASE PROVIDE MANUFACTURERS SPECS ON THESE
 UNITS, ADDITIONAL COMMENTS MAY APPEAR ON LATTER REVIEWS
 WITH ADDITIONAL INFORMATION. NOT FOUND WITH THE PRODUCT
 APPROVALS. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
 11-4.3.8 CHANGES IN LEVEL.
 CHANGES IN LEVELS ALONG AN ACCESSIBLE ROUTE SHALL
 COMPLY WITH SECTION 11-4.5.2 . IF AN ACCESSIBLE ROUTE
 HAS CHANGES IN LEVEL GREATER THAN ? INCH (13 MM), THEN
 A CURB RAMP, RAMP, ELEVATOR, OR PLATFORM LIFT (AS
 PERMITTED IN SECTION 11-4.1.3 AND 11-4.1.6 ) SHALL BE
 PROVIDED THAT COMPLIES WITH SECTION 11-4.7 , 11-4.8 ,
 11-4.10 , OR 11-4.11 , RESPECTIVELY. AN ACCESSIBLE
 ROUTE DOES NOT INCLUDE STAIRS, STEPS, OR ESCALATORS.
 SEE DEFINITION OF "EGRESS, MEANS OF" IN SECTION 11-3.5
 [SEE FIGURE 7 (C) AND FIGURE 7 (D)].
  
 15) 2ND REQUEST, THIS COMMENT IS COMMON TO MANY SHEETS,
 THE PLANS FAIL TO IDENTIFY VARIOUS COMMON DOORS THROUGH
 OUT THE PROJECT, PLEASE LABEL DOORS TO IDENTIFY FOR
 REQUIRED DOOR RATINGS. 106.1.2.* ADDITIONAL INFORMATION
 REQUIRED, TABLE 715.3 ETC.
  
 15A) SHEET A2.30 THE STOREFRONT DOORS ARE NOT LABELED
 ON THE DOOR SCHEDULE FOUND ON
 A2.80- A2.80- A2.83.
  
 16) 2ND REVIEW, THIS IS A REQUIRED STAIRWAY WHEN AN
 OCCUPANT LOAD OF 93, A2.01 STAIRWAY# 3 IS INDICATED AS
 PART OF THE POOL DECK MEANS OF EGRESS PLEASE SEE: LS .
 3 THIS SHEET ALSO INDICATES THIS TO BE THE SECOND MEANS
 OF EGRESS FROM THE POOL DECK.
 1022.5 LOCATION.EXTERIOR EXIT RAMPS AND STAIRWAYS
 SHALL BE LOCATED IN ACCORDANCE WITH SECTION 1023.3 .
 1023.3 EXIT DISCHARGE LOCATION.EXTERIOR BALCONIES,
 STAIRWAYS AND RAMPS SHALL BE LOCATED AT LEAST 10 FEET
 (3048 MM) FROM ADJACENT LOT LINES AND FROM OTHER
 BUILDINGS ON THE SAME LOT UNLESS THE ADJACENT BUILDING
 EXTERIOR WALLS AND OPENINGS ARE PROTECTED IN ACCORDANCE
 WITH SECTION 704 BASED ON FIRE SEPARATION DISTANCE.
  
 THE PURPOSE OF THIS SECTION IS TO PROTECT THE USERS OF
 EXTERIOR STAIRWAYS FROM FIRE IN AN ADJACENT BUILDING BY
 REQUIRING SPECIFIC SEPARATION DISTANCE FROM THAT
 ADJACENT BUILDING. THE REASON FOR THE REQUIRED DISTANCE
 TO A LOT LINE IS TO PROVIDE FOR A FUTURE BUILDING THAT
 COULD BE BUILT ON THE ADJACENT LOT.TAKEN FROM THE
 2004 FBC BUILDING CODE COMMENTARY.
  
 1004.8 OUTDOOR AREAS.
 YARDS, PATIOS, COURTS AND SIMILAR OUTDOOR AREAS
 ACCESSIBLE TO AND USABLE BY THE BUILDING OCCUPANTS
 SHALL BE PROVIDED WITH MEANS OF EGRESS AS REQUIRED BY
 THIS CHAPTER. THE OCCUPANT LOAD OF SUCH OUTDOOR AREAS
 SHALL BE ASSIGNED BY THE BUILDING OFFICIAL IN
 ACCORDANCE WITH THE ANTICIPATED USE. WHERE OUTDOOR
 AREAS ARE TO BE USED BY PERSONS IN ADDITION TO THE
 OCCUPANTS OF THE BUILDING, AND THE PATH OF EGRESS
 TRAVEL FROM THE OUTDOOR AREAS PASSES THROUGH THE
 BUILDING, MEANS OF EGRESS REQUIREMENTS FOR THE BUILDING
 SHALL BE BASED ON THE SUM OF THE OCCUPANT LOADS OF THE
 BUILDING PLUS THE OUTDOOR AREAS.
  
  
 17) A2.01 THE NEW RAMP THAT IS LOCATED NEXT TO PARKING
 SPACE# 22 DOESN?T INDICATE THE LOWER LANDING AT THE
 GARAGE FLOOR. PLEASE INDICATE THE LOWER LANDING ON THE
 PLANS IT APPEARS THAT IT WILL STICK OUT INTO THE
 VEHICLE TRAFFIC LANE. 11-4.8.4.(2) LANDINGS. ALL
 LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM
 OF EACH RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARANCE.
  
 18) 2ND REQUEST, SHEET A2.01 THE PROPERTY LINE IS
 INDICATED ON THE EAST PORTION OF THE BUILDING, WHERE
 THERE ARE TWO DISPLAY CASES WHERE THE DOORS DO SWING
 OUT OVER THE PROPERTY LINE. 3202.2 ENCROACHMENTS ABOVE
 GRADE AND BELOW 8 FEET IN HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE
 PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1
 THROUGH 3202.2.3 . DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 19) COMPLIED, SHEET C-4 INDICATES GRADE ON THE EXTERIOR
 AND A2.32 FOR THE INTERIOR.
  
 20A) SHEET A9.20 DOES SHOW WALL CUT DETAILS WALL
 DESIGNATION 800 A 2HR BLOCK WALL INDICATES A TEST
 HW-D1003 BUT NOT WHAT LAB? PLEASE INDICATEU.L.,
 PLEASE ALSO INCLUDE THIS STANDARD SINCE THE INSPECTORS
 WILL NOT HAVE A U.L. BOOK AT THE JOB SITE. THIS
 PARTICULAR
 DETAIL LIST MANY COMPANY PRODUCTS FOR THE FORMING
 MATERIAL(3A) BUT ONLY 3M COMPANY FB-2000 FOR PART 3B.
  
  
 20B) SHEET A2.30 RETAIL UNIT R-301 INDICATES A WALL
 TYPE 105 NO SUCH WALL TYPE PLEASE CORRECT.
  
 20C) SHEET A2.38 ?A2.43 ALL INDICATE TENANT SEPARATION
 WALLS WITH ASSOCIATED WALL TAGS,
 A9.01 INDICATES THE ACTUAL U.L. ASSEMBLIES IN PICTORIAL
 BUT THE SOUND TEST REFERENCE ONLY PROVIDES A SOUND TEST
 STANDARD NOT THE ACTUAL RESULTS OF SAID SOUND TEST.
 PLANS INDICATE VARIOUS SOUNDTEST STANDARDS PLEASE
 PRODUCE THESE STANDARDS. WHEN INVESTIGATINGTHE **
 RAL-TL-90-166**EXTERIOR WALL SYSTEMS WITH EFIS
 FINISHES WAS BROUGHT UP. PLEASE PRODUCE THE TEST
 STANDARD THE NOTE AT THE BOTTOM OF THE SHEET NEEDS TO
 REFLECT THE DETAILS MEETING CODE COMPLIANCE.3 5/8?
 STUD WITH 1 LAYER OF 5/8? DRYWALL AND INSULATION HAS A
 STC RATING OF 46 NOT THE REQUIRED 50. SEE 1207.2.
  
 21) COMPLIED.
  
 22) SEMI-COMPLIED, PLEASE PROVIDE THE REQUIRED SIGNAGE
 FOR THE VAN ACCESSIBLE PARKING SPACES LOCATED WITHIN A
 PARKING STRUCTURE SHALL HAVE AN ADDITIONAL SIGN
 READING
 ** VAN ACCESSIBLE** MOUNTED BELOW THE SYMBOL OF
 ACCESSIBILITY. SUCH SIGNS SHALL NOT BE LOCATED SO THEY
 CAN NOT BE OBSCURED BY A VEHICLE PARKED IN THE SPACE.
  
 23) COMPLIED.
  
 24) WE ARE LOOKING FOR FOR A MANUFACTURERS SPEC NOT A
 SPEC NUMBER.) SHEET A2.03 H. C. LIFT PLEASE PROVIDE
 THE SPECS IN COMPLIANCE WITH:
 11-4.11 PLATFORM LIFTS (WHEELCHAIR LIFTS ). 11-4.11.1
 LOCATION.
 PLATFORM LIFTS (WHEELCHAIR LIFTS ) PERMITTED BY SECTION
 11-4.1 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION
 11-4.11 .
 11-4.11.2 OTHER REQUIREMENTS.
 IF PLATFORM LIFTS (WHEELCHAIR LIFTS ) ARE USED, THEY
 SHALL COMPLY WITH SECTIONS 11-4.2.4 , 11-4.5 , 11-4.27
 , AND ASME A17.1, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS , SECTION XX, 1990.
 11-4.11.3 ENTRANCE.
 IF PLATFORM LIFTS ARE USED THEN THEY SHALL FACILITATE
 UNASSISTED ENTRY, OPERATION, AND EXIT FROM THE LIFT IN
 COMPLIANCE WITH SECTION 11-4.11.2 .
 FAIR HOUSING : ANSI A117.1 ELEVATORS 4.10.
  
 25A-B) FAIR HOUSING GUIDELINE **PREFACE** NOTES THAT
 THE MANUAL (FAIR HOUSING GUIDELINE) USES TERMS SUCH AS
 RECOMMENDED, PREFERRED, SHOULD , COULD OR USES ITALICS
 THE DESIGNER MAY USE OTHER METHODS. SHEET A2.91DETAILS
 3& 6 BOTH INCORPORATE RAMPS TO TRY TO ACCOMPLISH THE
 INTENT OF FAIR HOUSING GUIDELINE. ONE OF THE ISSUES
 THAT WE SEE IS
 NOTE # 9. ATTACHED TO THIS REVIEW IS AN EXAMPLE OF THE
 DOCUMENT THAT WOULD NEED TO BE RECORDED TO ALLOW FUNDS
 TO BE AVAILABLE THROUGH ESCROW FOR ANYTIME IN THE
 FUTURE FOR ANY UNITS THAT MAY NEED TO BE CONVERTED FOR
 THE DISABLED. IT COULD POSSIBLY EFFECT EVERY SECONDARY
 DOOR (SLIDING GLASS DOORS) WITHIN THE ENTIRE PROJECT,
 SO FUNDS HAVE TO BE AVAILABLE FOR SUCH WORK TO BE
 ACCOMPLISHED AND NOT FINANCIALLY AFFECTING THE DISABLED
 PERSON MOVING INTO ANY UNIT.
  
 25C) DEPENDING ON THE ANSWER TO 25A-B, THE STRUCTURAL
 PLANS WILL ALSO NEED TO CORRELATE THEIR DETAIL SHEETS
 TO MEET THE REQUIREMENTS STATED ABOVE, FAIR HOUSING
 SECONDARY SLIDING GLASS DOORS.
  
 25D-E)COMPLIED.
  
 26-27) COMPLIED
  
 28) 2ND REQUEST,SHEET A2.03 ELEVATOR LOBBY DOORS ONE
 DOOR INDICATES A 20MIN RATING THE OTHER NONE. PLEASE
 SEE TABLE 715.3. THE 20 MIN AND ? HR FIRE PARTITIONS OR
 CORRIDOR WALLS REQUIRED BY SECTION 1016.1. THE MORE
 RESTRICTIVE ELEVATOR LOBBIES WOULD REQUIRE THE ? HR
 OPENING PROTECTIVE. SEE CODE COMMENTARY UNDER 709.5
 SMOKE BARRIERS STATING FIRE PARTITIONS, OTHER THAN
 CORRIDOR WALLS, ARE REQUIRED TO HAVE AN OPENING
 ASSEMBLY RATING OF 45 MINUTES IN ACCORDANCE WITH TABLE
 715.3. SEE LIFE SAFETY PLAN LS3 AND DOOR SCHEDULE
 A2.80.
 29-32) COMPLIED.
  
 33) 2ND REQUEST, A2.03 THE SAME ISSUE WITH THE GATE
 NEXT TO THE SYMBOL EOD, THIS GATE REQUIRES 18? ON THE
 LATCH SIDE. FAIR HOUSING TABLE 404.2.4.1, FIGURE
 404.2.1(A). RESPONSE INDICATED A REVISED SHEET AS
 REQUIRED BY SECTION 404.2.1 ?
  
 34-37) COMPLIED.
  
 38)2ND REQUEST,THE REVISED DETAIL STILL WILL HOLD
 2? AT THE OVERFLOW AND 6? AT THE DRAIN. IF THE MAXIMUM
 OF 4? IS HELD AT THE OVERFLOW, THEN 8? OF WATER WILL BE
 HELD AT THE ROOF DRAIN 16 FEET AWAY, WITH THE MINIMUM
 WATER LOCATED SHEET A2.05 DETAIL# 13 INDICATE AN
 EMERGENCY OVERFLOW, THE SITUATION IS THE WAY THE DETAIL
 IS DRAWN WITH A MINIMUM OF 4? BEFORE RAINWATER STARTS
 TO RUN INTO THE OVERFLOW, WHERE THE PLUGGED UP ROOF
 DRAIN IS THE WATER MAY 7? OR 8? DEEP DEPENDING ON THE
 LOCATION OF THE ROOF DRAIN FROM THE OVERFLOW. 1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 39) COMPLIED.
  
 40) SHEET A.205 MAINTENANCE SHOP OR STORAGE AS
 INDICATED IN THE RESPONSE, PLEASE SEE DEFINITION OF
 PENTHOUSE 1509.2,THIS USAGE WILL CLASSIFY THIS AS A
 10 STORY BUILDING. ALSO CHANGE COVERSHEET TO REFLECT
 THE NEW STORY PLUS PROVIDE THE FLOOR LIVE LOADING FOR
 LIGHT STORAGE. STRUCTURAL SHEETS WILL ALSO NEED TO
 REFLECT THE ADDITIONAL LOADING.
  
 41-42)COMPLIED.
  
 43) THE NEW DETAILS INDICATES THE USE OF CONCRETE
 MOLDINGS. PLEASE PROVIDE ATTACHMENT DETAILS.
 ARCHITECTURAL TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE SHALL BE CONSTRUCTED OF
 APPROVED NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED
 TO THE WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS.1406.2.2
  
 44) COMPLIED.
  
 45A) 2ND REQUEST, SHEET A2.30 PRE-CAST CONC. MOLDING
 DETAIL 3 OF A3.09PLEASE INDICATE SLAB SIZES AND
 ANCHORAGE. . ARCHITECTURAL TRIM THAT EXCEEDS 40 FEET
 (12 192 MM) IN HEIGHT ABOVE GRADE PLANE SHALL BE
 CONSTRUCTED OF APPROVED NONCOMBUSTIBLE MATERIALS AND
 SHALL BE SECURED TO THE WALL WITH METAL OR OTHER
 APPROVED NONCOMBUSTIBLE BRACKETS.1406.2.2
  
 1405.5 ANCHORED MASONRY VENEER.ANCHORED MASONRY
 VENEER SHALL COMPLY WITH THE PROVISIONS OF SECTIONS
 1405.5 , 1405.6 , 1405.7 AND 1405.8 AND SECTIONS 6.1
 AND 6.2 OF ACI 530/ASCE 5/TMS 402.
 1405.5 ANCHORED MASONRY VENEER.
 1405.6 STONE VENEER
 1405.7 SLAB-TYPE VENEER
 DESIGNERS CAN?T JUST RESTATE THE CODE SECTION FOR CODE
 COMPLIANCE.
 45B)PLEASE SEE DETAIL 4 SHEET A8.05 AT WHAT HEIGHT IS
 THIS EFIS BAND LOCATED?
  
 46-49) COMPLIED.
  
 50) FIRE COMMAND ROOM: )FIRE COMMAND ROOM PLEASE
 PROVIDE COMPLIANCE WITH: 403.8 FIRE COMMAND . A FIRE
 COMMAND CENTER COMPLYING WITH SECTION 911 SHALL BE
 PROVIDED IN A LOCATION APPROVED BY THE FIRE
 DEPARTMENT.
  
 WHERE REQUIRED BY OTHER SECTIONS OF THIS CODE, A FIRE
 COMMAND CENTER FOR FIRE DEPARTMENT OPERATIONS SHALL BE
 PROVIDED. THE LOCATION AND ACCESSIBILITY OF THE FIRE
 COMMAND CENTER SHALL BE SEPARATED FROM THE REMAINDER OF
 THE BUILDING BY NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE-RATED FIRE BARRIER. THE ROOM SHALL BE A
 MINIMUM OF 96 SQUARE FEET (9 M 2 ) WITH A MINIMUM
 DIMENSION OF 8 FEET (2438 MM). A LAYOUT OF THE FIRE
 COMMAND CENTER AND ALL FEATURES REQUIRED BY THE SECTION
 TO BE CONTAINED THEREIN SHALL BE SUBMITTED FOR APPROVAL
 PRIOR TO INSTALLATION. THE FIRE COMMAND CENTER SHALL
 COMPLY WITH NFPA 72 AND SHALL CONTAIN THE FOLLOWING
 FEATURES.
 1.THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 UNIT.
 2.THE FIRE DEPARTMENT COMMUNICATIONS UNIT.
 3.FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR
 UNIT.
 4.ANNUNCIATOR UNIT VISUALLY INDICATING THE
 LOCATION OF THE ELEVATORS AND WHETHER THEY ARE
 OPERATIONAL.
 5.STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING
 SYSTEMS.
 6.THE FIRE-FIGHTER?S CONTROL PANEL REQUIRED BY
 SECTION 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN
 THE BUILDING.
 7.CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY.
 8.SPRINKLER VALVE AND WATER-FLOW DETECTOR DISPLAY
 PANELS.
 9.EMERGENCY AND STANDBY POWER STATUS INDICATORS.
 10.A TELEPHONE FOR FIRE DEPARTMENT USE WITH
 CONTROLLED ACCESS TO THE PUBLIC TELEPHONE SYSTEM. 11.
 FIRE PUMP STATUS INDICATORS. SEE ELECTRICAL AND
 MECHANICAL COMMENTS THAT DEAL WITH THE FIRE PUMP. 12.
 SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL FLOOR
 PLAN AND DETAILING THE BUILDING CORE, MEANS OF EGRESS,
 FIRE PROTECTION SYSTEMS, FIRE-FIGHTING EQUIPMENT AND
 FIRE DEPARTMENT ACCESS.
 13.WORKTABLE.
 14.GENERATOR SUPERVISION DEVICES, MANUAL START AND
 TRANSFER FEATURES. SEE ELECTRICAL AND MECHANICAL
 COMMENTS ABOUT GENERATOR AND FUEL STORAGE.
 15.PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY
 REQUIRED BY OTHER SECTIONS OF THIS CODE.
  
  
 51-55) COMPLIED.
  
 56A) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 56B) WITH MULTIPLE PRODUCTS OF THE SAME TYPE LARGE
 MISSILE, SMALL MISSILE AND NON-MISSILE RATED, INTERIOR
 ZONES AND END ZONES A COLOR COORDINATED CHART ON THE
 S-12 & S-13 SHEETS WILL ONLY BE THE WAY TO DESIGNATE
 WHAT PRODUCT GOES WHERE WITH THE CORRECTNESS NEEDED FOR
 THIS PROJECT
  
 56C) THE STRUCTURAL S-12& S13 DO NOT ACCURATELY
 INDICATE THE END ZONES, THEY ARE TAKING THEM FROM
 AWNINGS PROTRUDING FROM THE BUILDING AND NOT THE
 CORNERS PLUS END ZONES ARE FIGURED USING 10 PERCENT OF
 THE LEAST HORIZONTAL DIMENSION ASCE 7-02, FIGURE 6-17
 NOTE
 8 (A).
  
  
 56D)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 A) FIXED GLASS
 B) STOREFRONT GLASS: WINDOW WALL
 * CRAWFORD TRACY CORP PROVIDE FLORIDA
 COVERSHEETLARGE MISSILE 100+-
 * R.C. ALUMINUM PROVIDE FLORIDA COVERSHEET
 LMI , PICK A GLASS TYPE
 * YKK YHS-50 FS PROVIDE FLORIDA COVERSHEET
 PLUS THE BACK UP REPORT, TYPE OF
 MULLION AND GLAZING.
 C) OPERABLE WINDOWS : CASEMENT
 *RC ALUMINUM WINDOWS , PROVIDE THE FLORIDA
 COVERSHEET, THE BACKUP REPORT IS A
 MIAMI-DADE NOA GOOD FOR LARGE MISSILE+-
 80 PSF SEE LIMITATION TO SIZE
 * EFCO 2700 PROVIDE FLORIDA COVERSHEET,
 GOOD TO -135 SEE LIMITATION SIZE WIND
 ONLY NO MISSILE TESTING
 * EFCO PROVIDE FLORIDA COVERSHEET, UPDATE
 NOA TO THE 2004 FBC VERSION, SEE
 SIZE LIMITATION
  
 C) OPERABLE WINDOWS: HOPPER/ PROJECT OUT STYLE
 * EFCO PROVIDE FLORIDA COVERSHEET +90/-100 LMI/ SMI
 *YKK YOW H PROVIDE FLORIDA COVERSHEET
 ACTUAL CASEMENT
  
 D) MULLIONS HORIZONTAL & VERTICAL
 E) SKYLIGHTS
 F) GLASS BLOCK
 G) LOUVERS
 * 4 MANUFACTURES WERE SUBMITTED PICKED
 PICK ONE
 H) HOLLOW METAL DOORS/ ROOF HATCHES
 * CURRIES 3070 PROVIDE FLORIDA
 COVERSHEET, +-80
 * DAYBAR PROVIDE FLORIDA COVERSHEET,
 +-90 SINGLE
 I) GLASS DOORS SWING
 * EFCO D300/318 PROVIDE FLORIDA COVERSHEET
 LMI/SMI +- 60
 *YKK 35H PROVIDE FLORIDA COVERSHEET, LMI
 HIGHLIGHT CHARTS SIZES TO BE USED FOR
 PRESSURES
 J) OVERHEAD DOORS/ COIL DOORS
 * BEST PROVIDE FLORIDA COVERSHEET HIGHLIGHT
 DOOR WIDTH TABLE 1 FOR PRESSURES
 K) SLIDING GLASS DOORS
 * EFCO 3005PROVIDE FLORIDA COVERSHEET,
 HIGHLIGHT CHARTS FOR REINFORCEMENT, AND
 * KAWNEER HPX PROVIDE FLORIDA COVERSHEET,
 +100/-125PRESSURES
 L) AUTOMATIC HORIZONTAL SLIDING DOORS
 M)PANEL WALL SYSTEM: SOFFITS, EFIS
 N) ROOFING ASSEMBLIES TO MANY TO LIST , ONCE
 CONTRACTOR HAS PICKED PRODUCT AND BEEN
 REVIEWED BY THE DESIGNER OF RECORD WE THEN WILL
 REVIEW THE DOCUMENTS SUBMITTED.
 4 DIFFERENT ROOF TILE MANUFACTURES SUBMITTED
 SARNAFIL 60 PAGE ROOF SUBMITTAL WITH NO SUB-SYSTEM
 HIGHLIGHTED AS TO WHICH WILL BE
 INSTALLED ON THIS STRUCTURE
 2 INSULATION BOARD COMPANIES
 O) PANEL WALL SYSTEMS- SIDING- NO PRODUCT
 APPROVALS
 57)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 58) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 59) THIS NEXT ISSUE HAS BECOME A LARGE ISSUE ON
 PROJECTS!!!! WINDOWS NOT BEING LABELED.
 TESTING AND LABELING. 1714.5.2.1EXTERIOR WINDOWS AND
 GLASS DOORS SHALL BE TESTED BY AN APPROVED INDEPENDENT
 TESTING LABORATORY, AND SHALL BE LABELED WITH AN
 APPROVED LABEL IDENTIFYING THE MANUFACTURER,
 PERFORMANCE CHARACTERISTICS AND APPROVED PRODUCT
 CERTIFICATION AGENCY, TESTING LABORATORY, EVALUATION
 ENTITY OR MIAMI-DADE PRODUCT APPROVAL TO INDICATE
 COMPLIANCE WITH THE REQUIREMENTS OF ONE OF THE
 FOLLOWING SPECIFICATIONS:ANSI/AAMA/NWWDA 101/I.S.2 OR
 101/I.S. 2/NAFS OR TAS 202 (HVHZ SHALL COMPLY WITH TAS
 202 UTILIZING ASTME E 1300 OR SECTION 2404 .
 GLASS STRENGTH: DETERMINATION OF LOAD RESISTANCE OF
 GLASS FOR SPECIFIED LOADS OF PRODUCTS TESTED AND
 CERTIFIED IN ACCORDANCE WITH SECTION 1714.5.2.1 SHALL
 BE DESIGNED TO COMPLY WITH ASTM E 1300 IN ACCORDANCE
 WITH SECTION 2404 .
  
 60)SHEET A2.90; THIS SHEET SHOWS MULLIONS USED BOTH
 VERTICALLY AND HORIZONTALLY, BEFORE A REVIEW OF THE
 PRODUCT APPROVALS WILL BE ABLE TO BEGIN THE DESIGN TEAM
 WILL NEED TO HIGHLIGHT WHICH MULLION WILL BE THE ONE
 THAT WILL CONTINUE FROM A STRUCTURAL FRAMING MEMBER TO
 THE OPPOSITE SIDE.
  
 1714.5.5 MULLIONS OCCURRING BETWEEN INDIVIDUAL WINDOW
 AND GLASS DOOR ASSEMBLIES. 1714.5.5.1 MULLIONS.
 MULLIONS, OTHER THAN MULLIONS WHICH ARE AN INTEGRAL
 PART OF A WINDOW OR GLASS DOOR ASSEMBLY TESTED AND
 LABELED IN ACCORDANCE WITH SECTION 1714.5.2.1 , SHALL
 BE TESTED BY AN APPROVED TESTING LABORATORY OR BE
 ENGINEERED IN ACCORDANCE WITH ACCEPTED ENGINEERING
 PRACTICE. BOTH METHODS SHALL USE PERFORMANCE CRITERIA
 CITED IN SECTIONS 1714.5.5.2 , 1714.5.5.3 AND
 1714.5.5.4 .
  
 1714.5.5.2 LOAD TRANSFER.
 MULLIONS SHALL BE DESIGNED TO TRANSFER THE DESIGN
 PRESSURE LOADS APPLIED BY THE WINDOW AND DOOR
 ASSEMBLIES TO THE ROUGH OPENING SUBSTRATE.
  
 1714.5.5.3 DEFLECTION.
 MULLIONS SHALL BE CAPABLE OF RESISTING THE DESIGN
 PRESSURE LOADS APPLIED BY THE WINDOW AND DOOR
 ASSEMBLIES TO BE SUPPORTED WITHOUT DEFLECTING MORE THAN
 L/175, WHERE L IS THE SPAN OF THE MULLION IN INCHES.
  
 1714.5.5.4 STRUCTURAL SAFETY FACTOR.
 MULLIONS SHALL BE CAPABLE OF RESISTING A LOAD OF
 ONE-AND-ONE-HALF TIMES THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW AND DOOR ASSEMBLIES TO BE
 SUPPORTED WITHOUT EXCEEDING THE APPROPRIATE MATERIAL
 STRESS LEVELS. IF TESTED BY AN APPROVED LABORATORY, THE
 ONE AND ONE-HALF TIMES THE DESIGN PRESSURE LOAD SHALL
 BE SUSTAINED FOR 10 SECONDS, AND THE PERMANENT
 DEFORMATION SHALL NOT EXCEED 0.4 PERCENT OF THE MULLION
 SPAN AFTER THE ONE-AND-ONE-HALF TIMES DESIGN PRESSURE
 LOAD IS REMOVED.
  
 61) 2ND REQUEST,ANOTHER BIG ISSUE WITH PRODUCT
 APPROVALS THAT THE DESIGN TEAM WILL SIGN OFF ON
 REVIEWED IS THEY WILL NOT ?HIGHLIGHT? WHICH GLAZING
 SYSTEM THEY HAVE APPROVED AND THE CORRESPONDING
 PRESSURES, NOR WILL THEY HIGHLIGHT IN SLIDING GLASS
 DOOR SYSTEMS WHICH
 RAIL SYSTEM WILL BE USED. THERE ARE 4 DESIGN CRITERIA
 USUALLY IN THESE PACKAGES. ONE WITH NO REINFORCEMENT,
 LIGHT , MEDIUM AND HEAVY REINFORCEMENT HIGHLIGHT WHICH
 SYSTEM IS TO BE USED.
  
 62)ROOF REPORT WAS SUBMITTED IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 (FLAT ROOF)
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. _X__
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED.
 _X__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
 SINCE THE ROOFING REPORT DOESN?T HAVE THE SUBSYSTEM
 HIGHLIGHTED THE NEXT 2 ITEMS ARE HIGHLIGHTED._X__ THE
 SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD THE
 FASTENERRESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THEBUILDING OFFICIAL, A REVISED
 FASTENERSPACING, PREPARED , SIGNED AND SEALED BY A
 FLORIDA REGISTEREDPROFESSIONAL ENGINEER,
 REGISTEREDARCHITECT OR REGISTERED ROOF CONSULTANT
 MAY BE SUBMITTED.
 _X__THE SYSTEM PROVIDED INDICATESLIMITATION#
 9, NO ENHANCEDFASTENING ALLOWED.
  
 63) SLOPED ROOF (7/ A8.06) INDICATES THE USE OF EITHER
 CLAY TILE OR CONCRETE TILE. SUBMIT REPORT AND HIGHLIGHT
 WHICH TYPE OF SYSTEM WILL BE USED TO RESIST THE MOMENT
 OF UPLIFT?
  
 64)PLEASE SUBMIT INFORMATION ON HOW THE RIDGE TILE
 ARE GOING TO BE SECURED TO THE ROOFING SYSTEM. 1507.3.7
 ATTACHMENT.
 CLAY AND CONCRETE ROOF TILES SHALL BE FASTENED IN
 ACCORDANCE WITH SECTION 1609 OR IN ACCORDANCE WITH
 FRSA/RTI INSTALLATION MANUAL.
 1507.3.8 APPLICATION.
 TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS OR RECOMMENDATIONS OF THE
 FRSA/RTI 07320- 04.
  
 65) A3.30 INDICATES THE USE OF METAL PANEL ROOFING
 PLEASE PROVIDE ROOFING REPORT.
  
 66)SHIMS FOR WINDOWS AND DOORS, SHEET A2.93 DETAIL#
 9.
 1714.5.4.3 WOOD OR OTHER APPROVED FRAMING MATERIALS.
 WHERE THE FRAMING MATERIAL IS WOOD OR OTHER APPROVED
 FRAMING MATERIAL, WINDOW AND GLASS DOOR ASSEMBLIES
 SHALL BE ANCHORED THROUGH THE MAIN FRAME OR BY JAMB
 CLIP OR SUBFRAME SYSTEM OR THROUGH THE FLANGE IN
 ACCORDANCE WITH THE MANUFACTURER?S PUBLISHED
 INSTALLATION INSTRUCTIONS. SHIMS SHALL BE MADE FROM
 MATERIALS CAPABLE OF SUSTAINING APPLICABLE LOADS,
 LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
  
 67-69) COMPLIED.
  
 70) CODE BACK UP STATEMENT FOR 56D) (H) MULTIPLE
 MANUFACTURERS PRODUCTS SUBMITTED,
 EXTERIOR DOOR ASSEMBLIES NOT COVERED BY SECTION
 1715.4.2 OR SECTION 1714.5.3.1 SHALL BE TESTED FOR
 STRUCTURAL INTEGRITY IN ACCORDANCE WITH ASTM E 330
 PROCEDURE A, AT A LOAD OF 1.5 TIMES THE REQUIRED DESIGN
 PRESSURE LOAD. THE LOAD SHALL BE SUSTAINED FOR 10
 SECONDS WITH NO PERMANENT DEFORMATION OF ANY MAIN FRAME
 OR PANEL MEMBER IN EXCESS OF 0.4 PERCENT OF ITS SPAN
 AFTER THE LOAD IS REMOVED. HIGH-VELOCITY HURRICANE
 ZONES SHALL COMPLY WITH TAS 202. AFTER EACH SPECIFIED
 LOADING, THERE SHALL BE NO GLASS BREAKAGE, PERMANENT
 DAMAGE TO FASTENERS, HARDWARE PARTS, OR ANY OTHER
 DAMAGE WHICH CAUSES THE DOOR TO BE INOPERABLE.
 THE MINIMUM TEST SIZES AND MINIMUM DESIGN PRESSURES
 SHALL BE AS INDICATED IN TABLE 1714.5.3 .
  
 71-73COMPLIED, WERE INFORMATIONAL FOR AWNINGS THAT ARE
 REQUIRED UNDER SEPARATE PERMIT.
  
 74-78) COMPLIED.
  
 79) )2ND REQUEST, A8.05 EXTERIOR SOFFITS, VARIOUS
 DETAILS INDICATE THE SOFFIT OR DROPPED CEILING, THERE
 IS NO INFORMATION ON THE TYPE OF STUDS, SPACING,
 ATTACHMENT TO DECK ABOVE OR TYPE OF LATH AND SPACING OF
 HORIZONTAL FRAMING MEMBERS IS THE WIRE LATH TIED UP OR
 SCREWED IN PLACE?
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 80) 2ND REQUEST,A8.06 DETAIL# 11 INDICATES THE USE OF
 5V METAL CRIMP SIDING DIRECTLY APPLIED TO THE METAL
 FRAMING, WHAT TYPE OF BRACING IS TO BE USED? PLEASE
 PROVIDE THE PRODUCT APPROVAL INDICATING THIS IS
 STRUCTURAL SHEATHING NO SHEATHING REQUIRED. THIS IS A
 PRODUCT THAT IS CONSIDERED COMPONENTS AND CLADDING BY
 RULE 9B-72 AND WILL BE ADDRESSED BEFORE A PERMIT WILL
 BE ISSUED. EVEN ALL METAL BUILDINGS WITH METAL SIDING
 AND ROOFING ARE REQUIRED TO PROVIDE PRODUCT APPROVALS
 WITH A THIRD PARTY QUALITY ASSURANCE PROGRAM APPROVED
 THROUGH THE STATE. THIS COMMENT ALSO REVERTS BACK TO
 COMMENTS
 56D,57 & 58.
  
 81)COMPLIED.
  
 82) SHEET A9.01:
  
 82A) 2ND REQUEST, YOU CAN NOT JUST QUOTE CODE SECTION
 AND SAY THIS SATISFIES THE REQUEST, 106.1.1, &
 106.1.2*. A9.01 VARIOUS DETAILS INDICATE A DESIGN SOUND
 TEST NUMBER, PLEASE INDICATE THE SOUND TRANSMISSION
 CLASS NUMERICALLY, 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED CABINETS;
 BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR EXHAUST
 DUCTS SHALL BE SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED RATINGS. THIS
 REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT ENTRANCE
 DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT FITTING TO
 THE FRAME AND SILL.
  
 82B)2ND REQUEST, YOU CAN NOT JUST QUOTE CODE SECTION
 AND SAY THIS SATISFIES THE REQUEST, 106.1.1, &
 106.1.2*. PLEASE PROVIDE COMPLIANCE WITH SOUND
 TRANSFERENCE THROUGH THE FLOOR SYSTEM?
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 83) A9.01 NOTES 2-4 ALL DEAL WITH THE BACKING BENEATH
 MARBLE AND TILE NOTE 2 INDICATES THE USE OF A
 CEMENTITITOUS BACKER BOARD AND NOTE 3 INDICATES THE USE
 OF GLASS MAT WATER RESISTANT BOARD BUT NOTE 4 INDICATES
 TILE BACKER BOARD, WHAT TYPE?
  
 84-86) COMPLIED.
  
  
  
  
 87) PROVISO: 87) ADJACENT TO EXCAVATIONS.
 EVERY EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR
 LESS FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A
 BARRIER NOT LESS THAN 6 FEET (1829 MM) HIGH. WHERE
 LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT
 LINE, A BARRIER SHALL BE ERECTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE
 STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN
 CHAPTER 16 .
  
 88) COMPLIED.
  
 89) SECOND REQUEST,S-8 INDICATES A TABLE OF CONCRETE
 COVERAGE HOW DOES THIS TABLE COMPLY WITH TABLE 601 THE
 HOUR RATINGS FOR STRUCTURAL FRAMES COLUMNS, GIRDERS OR
 BEAMS, FLOOR AND ROOF SLABS? THIS TABLE IS MINIMUM
 CONCRETE COVERAGE WHEN CONCRETE IS EXPOSED TO EARTH
 TABLE 1907.1.
  
 90) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 91) A2.3.2 THE HANDICAPPED RAMP PLAN DOESNOT INDICATE
 THE REQUIRED 6?-0? BOTTOM LANDING. 11-4.8.4.(2)
 LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT BE LESS THAN
 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL HAVE NOT LESS
 THAN 72" OF STRAIGHT & LEVEL CLEARANCE.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy