Plan Review Notes
Plan Review Notes For Permit 07020735
Permit Number 07020735
Review Stop P
Sequence Number 1
Notes
Date Text
2007-04-02 18:30:41DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINSTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. A TITLE BLOCK MUST AT A
 MINIMUM CONTAIN THE FIRM LICENSE NUMBER. FAC
 61G1-16.004(2)
  
 2. IRRIGATION PERMIT AND PLANS ARE REQUIRED.
 (INFORMATIONAL)
  
 3. SHT A2.02 POOL EQUIPMENT ROOM SHALL BE VENTILATED.
 EITHER BY CROSS VENTILLATION OR BY FORCED DRAFT. PLEASE
 INDICATE METHOD. SECTION 424.1.5.4.
  
 4. SHT A2.03 NOT ALL TERRACES, DECK DRAINS AROUND THE
 POOL & WALKWAYS SHOW EOD'S. SECTIONS 1107.1 & 1107.2 .
 PLEASE INDICATE THE LOCATION OF ALL REQUIRED SECONDARY
 DRAINS.
  
 5. SHTS A2.03, A2.44 & A4.01 A URINAL IS REQUIRED IN
 THE MEN'S TOILET FOR THE POOL FACILITIES. TABLE
 424.1.6.1.
  
 6. SHT A2.05 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH
 DRAINALONG WITH 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS, STAIRWAYS, MECH ROOMS ECT. ALONG
 WITH ALL AREAS OF ROOFS THAT DRAIN TO THE ROOF AREA
 FROM ABOVE. TABLE 1106.3.
  
 7. SHS A2.38, A2.39, A2.40 & A2.41 W/C'S IN BOTH MASTER
 BATHS, THAT ARE COMPARTMENTALIZED, DO NOT HAVE THE
 CLEAR FLOOR SPACE REQUIRED AS SHOWN ON PAGE 7.43. THE
 WALL CAN NOT EXTEND PAST 2' PER PAGE 7.44. SCALES OUT
 PAST 2'.
  
 8. SHT A2.41 SHOW SECONDARY DRAINS FOR THE TERRACES AND
 WALKWAY.SECTIONS 1107.1 & 1107.2.
  
 9. SHTS A2.71 & A2.72 NO FINISH INDICATED FOR THE POOL
 TOILET ROOMS. PLEASE SEE SECTION 424.1.6.1.2 AND
 SECTION 1210.2.
  
 10. SHT A5.01 BLOCKING FOR THE SHOWER SHALL COMPLY WITH
 PAGE 6.12. ALSO SHOW BLOCKING ON ALL THREE SIDES AS
 REQUIRED.
  
 11. SHT A5.02 UNITS 1,2,3,3M,5,6 & 7 BACKING REQUIRED
 ON ALL SIDES OF THE TUB PER PAGES 6..8 & 6.9, AND FOR
 THE SHOWERS PER PAGE 6.12 IN UNITS 1,3,3M,5,6, & 7.
  
 12. SHT A5.03 BACKING REQUIRED ON ALL SIDES OF THE TUB
 IN UNITS 03R,8,9,10,10R & 12 PER PAGES 6.8 & 6.9, AND
 FOR THE SHOWERS PER PAGE 6.12 IN UNITS 03R,8 & 9.
  
 13. SHT A5.03 DETAIL 16, THE CLEAR FLOOR SPACE IS
 REQUIRED FOR THE URINAL PER SECTION 11-4.18.3. PLEASE
 SHOW ON THE FLOOR PLAN.
  
 14. SHTS A5.03 & A5.04. W/C'S IN THE POOL TOILET ROOMS
 AND THE RETAIL TOILET ROOM SHALL BE 18" OFF THE WALL TO
 THE CENTERLINE OF THE FIXTURE. FIG. 11-28. THE LAVS
 SHALL BE 15" MINIMUM OFF THE WALL TO THE CENTERLINE OF
 THE FIXTURE TO CENTER ON THE CLEAR FLOOR SPACE 30".
 MINIMUM 30" FROM CENTERLINE OF THE W/C TO THE
 CENTERLINE OF THE LAVREQUIRED PER SECTION 405.3.1 &
 FIGURE 405.3.1.
  
 15. SHT A5.04 SHOW THE WATER CLOSET FLUSH CONTROLS AS
 REQUIRED IN SECTION 11-4.16.5, (WIDE SIDE).
  
 16. ALL PLUMBING, MECHANICAL, AND ELECTRICAL SHEETS.
 THE SIGNATURE OF THE ENGINEER IS REQUIRED. INITIALS ARE
 SHOWN. FAC 61G15-23.002(2) AND FS 471.025
  
 17. SHT P0.00 KEY NOTE #4 INDICATES A PERFORATED CAP
 FOR THE SECONDARY DRAIN. PLEASE CLARIFY. SECTION
 106.1.1. IF THE SECONDARY DRAIN IS FOR STORM, A FULL
 SIZE OPENING IS REQUIRED.
  
 18. SHT P1.01 INDICATE ALL RISER NUMBERS AT THE BASE OF
 EACH STACK AND THROUGH THE BUILDING TO TRACK EACH
 RISER. (EXAMPLE S/1, S/2, RWL/1, RWL/2, ETC.). SECTION
 106.1.2.
  
 19. SHT P1.01 KEY NOTES #5 & #12 NOT FOUND. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 20. SHT P1.01 STAIR 1 FIRE DRAIN IS LABELED "SD".
 PLEASE CLARIFY. SECTION 106.1.1.
  
 21. SHT P1.01 ONE "SD" LINE IS INDICATED AS A 6" SANT.
 LINE (6). PLEASE CLARIFY. SECTION 106.1.1.
  
 22. SHT P1.01 IDENTIFY THE RISER BETWEEN THE DRINKING
 FOUNTAIN AND THE FOUNTAIN DRAIN. (NO KEY NOTE NUMBER).
 SECTION 106.1.1.
  
 23. SHT P1.01 ONE CONDENSATE LINE TURNS INTO A STORM
 LINE. PLEASE CLARIFY. SECTION 106.1.1.
  
 24. SHT P1.01 "SD" LINE DOES NOT REFLECT THE RISER IN
 THE AREA OF THE THE GAS LINE & BY STAIR 2. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 25. SHT P1.01 THE SANT. LINE BY SWITCHGEAR ROOM DOES
 NOT REFLECT THE RISER. PLEAE CORRELATE. SECTION
 106.1.1.
  
 26. SHT P1.02 IDENTYFY ALL RISERS FOR ALL SYSTEMS.
 SECTION 106.1.1.
  
 27. SHT P1.02 KEY NOTES. THE FOLLOWING KEY NOTES WERE
 NOT FOUND. 4,11, & 15. NOTE 10 INDICATES IRRIGATION,
 COLD WATER AND "GAS PIPE".PLEASE CLARIFY. SECTION
 106.1.1.
  
 28. SHT P1.03 TWO STORM LINES ARE NOT IDENTIFIED.
 SECTION 106.1.1.
  
 29. SHT P1.03 RISERS D/3 & CD/3 ARE MISLABELED. SECTION
 106.1.1.
  
 30. SHT P1.03 ONE RISER IS LABELED AS BOTH KEY NOTES
 (17) & (18). PLEASE CLARIFY. SECTION 106.1.1.
  
 31. SHT P1.03W/1 DESIGNATIONAND KEY NOTE NUMBER
 NEAR A/C UNIT IN TENANT STORAGE ROOM ARE NOT LEGIBLE.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 32. SHT P1.03 KEY NOTE 19 SHOWN CONNECTING TO THE STORM
 RISER. CLARIFY. SECTION 106.1.1.
  
 33. SHT P1.03 KEY NOTES 3,9,11,13,16 & 20 WERE NOT
 FOUND. PLEASE CLARIFY. SECTION 106.1.1.
  
 34. SHT P1.03 RWL/4 DOES NOT LINE UP WITH THE RISERS ON
 THE NEXT LEVEL. SHOW OFFSET ON THE RISER DIAGRAM.
 SECTION 106.1.1.
  
 35. SHT P1.04 SHOWS THE URINAL IN THE WOMEN'S TOILET
 ROOM. THIS IS REQUIRED IN THE MEN'S TOILET ROOM PER
 SECTION 424.1.6.1.
  
 36. SHT P1.04 KEY NOTE (11) INDICATED ON THE FLOOR PLAN
 IS NOT SHOWN ON THE KEY NOTE SCHEDULE. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 37. SHT P1.04 THE PRL LINE FOR RISER S/64 IS NOT SHOWN
 ON THE FLOOR PLAN. THIS DOES NOT REFLECT THE RISER
 DIAGRAM. PLEASE CORRELATE. SECTION 106.1.1.
  
 38. SHT P1.04 THE PIPING FOR S/16 DOES NOT REFLECT THE
 RISER DIAGRAM. CORRELATE RISER & FLOOR PLAN. SECTION
 106.1.1.
  
 39. SHT P1.04 S/7 DESIGNATION SHOWN BUT DOES NOT POINT
 TO ANY RISER. PLEASE CLARIFY. SECTION 106.1.1.
  
 40. SHT P1.04 THE SINK INDICATED ON RISER S/10 IS NOT
 SHOWN ON THE FLOOR PLAN. PLEASE CLARIFY. SECTION
 106.1.1.
  
 41. SHT P1.04 MANY PLANTER DRAINS & DECK DRAIN AREAS
 SHOW WHAT APPEARS TO BE EXTRA DRAINS. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 42. SHT P1.04 THE OVERFLOW SCUPPERS SHALL BE LOCATED AS
 NEAR AS PRACTICAL TO THE REQUIRED VERTICAL LEADERS OR
 DOWNSPOUTS. SOME AREAS HAVE NOOVERFLOW SCUPPERS.
 SECTION 1503.4.3. OVERFLOW SCUPPERS SHALL BE SIZED PER
 SECTIONS 1101.7 & 1107.3 AS WELL AS TABLE 1106.7.
  
 43. SHT P1.04 SOME AREAS HAVE NO SECONDARY DRAINS ON
 THE DECK. SOME AREAS APPEAR TO BE ABLE TO DRAIN INTO
 THE THE UNIT BEFORE DRAINING INTO THE SECONDARY DRAIN
 BECAUSE OF THE DISTANCE FROM THE MAIN DRAIN TO THE
 OVERFLOW DRAIN. PLEASE CLARIFY. SECTIONS 106.1.1 AND
 1107.1.
  
 44. SHT P1.04 SOME PLANTER DRAINS, DECK DRAINS SIZES
 AND SQUARE FOOTAGE ARE NOT LEGIBLE AS THEY ARE
 SUPERIMPOSED OVER OTHER PLAN INFORMATION. PLEASE MAKE
 ALL INFORMATION LEGIBLE. SECTION 106.1.1.
  
 45. SHT P1.04 PIPING ON THE FLOOR PLAN DOES NOT REFLECT
 THE RISER AT THE BASE OF RISERS S/44, S/45, S/69 (W/M).
 PLEASE CORRELATE. SECTION 106.1.1.
  
 46. SHT P1.04 RISER CD/4 DESIGNATION NOT SHOWN. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 47. SHT P1.05 PIPING ON THE FLOOR PLAN DOES NOT REFLECT
 THE RISER AT RISERS S/4 (SINK), S/7, S/10 (SINK), S/11
 (W/M), S/23 (LAV), S/44, S/32. PLEASE CORRELATE
 INFORMATION. SECTION 106.1.1.
  
 48. SHT P1.05 RISER S/56 DESIGNATION IN NOT LEGIBLE.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 49. SHT P1.05 RISER CD/4 DESIGNATION NOT INDICATED.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 50. SHT P1.05 RWL/10 NOT SHOWN. PLEASE CLARIFY. SECTION
 106.1.1.
  
 51. SHT P1.06 PIPING ON THE FLOOR PLAN DOES NOT REFLECT
 THE RISER DIAGRAMS FOR S/4, S/7, S/10, S/11 & S/50.
 CORRELATE. SECTION 106.1.1.
  
 52. SHT P1.06 RISER S/56 DESIGNATION IS NOT LEGIBLE.
 CLARIFY. SECTION 106.1.1.
  
 53. SHT P1.06 RISER CD/4 NOT SHOWN. SECTION 106.1.1.
  
 54. SHT P1.07INDICATE THE STACK NUMBER FOR EACH VTR
 TO VERIFY ALL VENTS THRU THE ROOF. SECTION 106.1.1.
  
 55. SHT P1.07 INDICATE THE RWL NUMBER FOR EACH ROOF
 DRAIN. SECTION 106.1.1.
  
 56. SHT P1.07 MANY VTR'S, RD'S, SF AREAS, ETC ARE
 PRINTED OVER OTHER INFORMATION AND ARE NOT LEGIBLE.
 PLEASE CLEAR UP ALL INFORMATION. SECTION 106.1.1.
  
 57. SHT P1.07 1 4" VTR IS SHOWN UNDER DUCT WORK FOR THE
 A/C SYSTEM. PLEASE CLARIFY. SECTION 106.1.1.
  
 58. SHT P1.07 SOME AREAS FOR THE ROOF DRAINS DO NOT
 SHOW ALL THE AREAS THAT CONTRIBUTE TO THE TOTAL SF.
 SOME UPPER ROOFS (SUCH AS STAIR ROOFS, MAINT. ROOM
 ROOF, CIRCULAR ROOF), VERTICAL WALLS (SUCH AS STAIRS OR
 MAINTENANCE ROOM), DO NOT SHOW ANY CONTRIBUTION. PLEASE
 RECHECK ALL AREAS TO VERIFY TOTAL AREA FOR EACH DRAIN.
 TABLE 1106.3 AND SECTION 106.1.1.
  
 59. SHT P1.07 KEY NOTES SEEM TO BE FOR MECHANICAL.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 60. SHT P2.01 THE 3" BRANCH LINE DOWNSTREAM OF RISER
 S/72 DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 61. SHT P2.01 PIPING LAYOUT ON THE FLOOR PLAN TO RISERS
 S/45 & S/46 DOES NOT REFLECT THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 62. SHT P2.01 INDICATE WHERE RISER S/41 CONNECTS TO THE
 BUILDING DRAIN/BRANCH LINE. SECTION 106.1.1.
  
 63. SHT P2.01 THE COLLECTION RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN DOWNSTREAM OF 6" HD. (SHOWS AN
 EXTRA FLOOR DRAIN). CORRELATE. SECTION 106.1.1.
  
 64. SHT P2.01 HUB DRAIN INDICATES A 10"X72" HUB PIPE
 SEALED AT THE TOP. THE FIRE LINE DRAIN SHALL DRAIN TO
 AN INDIRECT WASTE RECEPTOR, AND BY SEALING THE TOP, IT
 WILL BE A DIRECTION CONNECTION. PLEASE CLARIFY. SECTION
 802.1.5.
  
 65. SHT P2.01 A SECOND RISER S/31 IS INDICATED AS RISER
 S/28 ON THE FLOOR PLAN. PLEASE CORRELATE & CLARIFY.
 SECTION 106.1.1.
  
 66. SHT P2.01 PLEASE GIVE A DESIGNATION TO EACH
 BUILDING DRAIN INTO THE BUILDING IN ORDER TO TRACK THE
 PIPING AND EXPEDITE THE REVIEW PROCESS. SECTION
 106.1.1.
  
 67. SHT P2.02 RISERS S/62, S/67 & S/17 WERE NOT FOUND.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 68. SHT P2.02 SECTION (A) INDICATES THE REVENT
 CONNECTING TO RISER S/6. RISER S/6 DOES NOT SHOW VENT
 CONNECTION TO RISER. PLEASE CLARIFY. SECTION 106.1.1 &
 TABLE 916.1.
  
 69. SHT P2.02 RISER S/58 SHOWS DFU AS 70, BUT THE
 COLLECTION RISER INDICATES DFU AS 86. PLEASE CLARIFY.
 SECTION 106.1.1. & TABLES 710.1(1) & 710.1(2).
  
 70. SHT P2.02 THE SANITARY COLLECTION RISER DOES NOT
 REFLECT THE FLOOR PLAN BY THE SECOND RISER (S/74).
 PLEASE CORRELATE. SECTION 106.1.1.
  
 71. SHT P2.02 RISER S/18 IS SHOWN AS 84 DFUON THE
 COLLECTION RISER, BUT ONLY 14 DFU ON THE RISER DIAGRAM.
 PLEASE CLARIFY & CORRELATE. SECTION 106.1.1.
  
 72. SHT P2.02 THE SANITARY COLLECTION SHOWS THE VENT
 FROM THE SHOWER CONNECTING TO RISER S/74. RISER S/74
 DOES NOT SHOW THE VENT CONNECTING TO THE RISER. PLEASE
 CLARIFY AND CORRELATE. SECTION 106.1.1.
  
 73. SHT P2.02 RISER S/20 ON THE COLLECTION RISER IS
 SHOWN AS 88 DFU, BUT THE RISER DIAGRAM SHOWS IT AS 86
 DFU. PLEASE CLARIFY. SECTION 106.1.1.
  
 74. SHT P2.06 2 RISERS FOR S/2 AND S/59 ARE SHOWN. ONE
 IS A SOVENT SYSTEM AND THE OTHER IS A CONVENTIONAL
 SYSTEM.THE FLOOR PLAN INDICATES A SOVENT SYSTEM.
 PLEASE CORRELATE AND DELETE THE SYSTEM NOT USED.
 SECTION 106.1.1.
  
 75. SHT P2.06 2 RISERS ARE SUBMITTED FOR S/42. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 76. SHT P2.06 RISERS S/34, S/71, S/73, & S/41 ALL SHOW
 SHOWERS, BUT THE FLOOR PLAN SHOWS TUBS. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 77. SHT P2.09 KEY NOTE #1 & RISER DIAGRAM INDICATE AIR
 CHAMBERS. AIR CHAMBERS ARE NOT APPROVED. DELETE FROM
 THE RISER AND THE NOTES. SECTION 604.9 & PDI-WH 201.
  
 78. SHT P2.09 RISERS W/4, W/5, W/6, W/8, W/9, W/11,
 W/13, W/17 & W/18 SHOW 1" SUPPLY TO EACH UNIT, BUT ONLY
 ARE BEING FED BY 3/4" ON THE RISER AT THE 8TH FLOOR.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 79. SHT P2.09 RISER W/7 SHOWS 3/4" TO THE 8TH FLOOR &
 3/4"SUPPLY TO THE UNIT, BUT THE UNIT RISER SHOWS 1"
 SUPPLY TO THE UNIT. PLEASE CLARIFY. SECTION 106.1.1.
  
 80. SHT P2.09 RISER W/14 INDICATES A UNIT 14, BUT NO
 UNIT 14 HAS BEEN FOUND. PLEASE CLARIFY. SECTION
 106.1.1.
  
 81. SHT P2.10 RISER W/15 SHOWS 1-1/4" AT THE BASE OF
 THE RISER, BUT 1-1/2" IS SHOWN ON THE RISER ON SHT
 P2.09. PLEASE CLARIFY. SECTION 106.1.1.
  
 82. SHT P2.11 RWL/16 RISER SHOWS 750SF, BUT THE ROOF
 PLAN SHOWS 930SF. PLEASE CORRELATE. SECTION 106.1.1 &
 TABLE 1106.3.
  
 83. SHT P2.11 RWL/15 RISER SHOWS 930SF, BUT THE ROOF
 PLAN SHOWS 1440SF. PLEASE CORRLEATE. SECTION 106.1.1. &
 TABLE 1106.3.
  
 84. THE CONNECTION OF RWL/16 TO RWL/15 ON THE RISER
 DOES NOT REFLECT THE ISOMETRIC. ONE SHOWS THE
 CONNECTION ON THE HORIZONTAL AND THE OTHER SHOWS THE
 CONNECTION ON THE VERTICAL. CORRELATE. SECTION 106.1.1
 & TABLE 1106.3.
  
 85. THE SECTION OF HORIZONTAL PIPE BETWEEN RISERS RWL/8
 & RWL/11 SHALL BE A MINIMUM 5" PER TABLE 1106.3.
  
 86. SHT P2.12 THE RISER DOES NOT REFLECT THE FLOOR PLAN
 PIPING IN 3 AREAS ON THE GROUND FLOOR. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 87. SHT P2.13 RECHECK SQUARE FOOTAGE OF EACH AREA. SF
 OF ONE DECK DRAIN SHOWS 80SF, BUT BY SCALING THE AREA
 IT IS MORE. PLEASE CLARIFY. SECTION 106.1.1 & TABLE
 1106.3.
  
 88. SHT P2.13 ONE LINE SHOWS 4" @1700SF. A MINIMUM OF
 5" IS REQUIRED UNLESS THE SLOPE IS GREATER THAN
 1/8"/FT. PLEASE CLARIFY. TABLE 1106.3.
  
 89. SHT P2.13 THE RISER DOES NOT REFLECT THE FLOOR PLAN
 PIPING IN 3 AREAS. PLEASE CORRELATE. SECTION 106.1.1.
  
 90. SHT P2.13 THE SIZE OF THE DECK DRAINAGE PIPING
 SHALL NOT BE REDUCED IN THE DIRECTION OF FLOW. (6" TO
 4"). SECTION 704.2.
  
 91. SHT P2.13 THE TOTAL DRAINAGE AREA IS APPROX.
 20,140SF. THE SECONDARY DRAINS ADD UP TO 6,880SF.
 PLEASE CLARIFY. THE SECONDARY DRAINS SHALL DRAIN THE
 SAME AMOUNT OF SQUARE FOOTAGE AS THE PRIMARY DRAINS.
 SECTION 1107.3. SCUPPERS SHALL BE SIZED TO PREVENT THE
 DEPTH OF PONDING WATER FROM EXCEEDING THAT FOR WHICH
 THE ROOF WAS DESIGNED AS DETERMINED BY SECTION 1101.7.
 PLEASE KEEP IN MIND THE DEPTH OF THE WATER BEFORE THE
 SECONDARY DRAINAGE STARTS TO REMOVE THE STORM WATER AND
 THE HEIGHT OF THE SLIDING DOORS TO THE UNITS OFF THE
 TERACES.
  
 92. SHT P2.14 INDICATES GAS PIPE SIZES BASED ON THE
 NFPA CHART. PIPING SHALL BE SIZED PER THE FBC-2004 FUEL
 GAS CODE. PLEASE CHANGE REFERENCE.
  
 93. SHT P2.14 THE LONGEST RUN IS INDICATED AS 58'0",
 BUT ADDITION INDICATES 62' WITHOUT COUNTING THE LENGTH
 OF PIPES FROM THE METER TO THE FIRST RISER. PLEASE
 RECHECK THE ADDITION AND ADD THE PIPE LENGTH FROM THE
 METER TO THE FIRST RISER. FBC-2004 FUEL GAS CODE
 APPENDIX A - USE OF CAPACITY TABLES A.3.1(4).
  
 94. SHT P2.14 INDICATE THE LENGTH OF PIPES FROM THE
 REGULATOR TO THE POOL HEATER.
  
 95. SHT P2.14 SUBMIT THE MANUF. SPECIFICATION SHEETS
 FOR THE POOL HEATER, AND THE REGULATOR. INDICATE THE
 MODEL FOR EACH AND SHOW THE LISTING. STANDARDS NFPA 54,
 NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2.
  
 96. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 97. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 98. SHT P2.14 KEY NOTE #13 NOT APPROVED. SECTION
 504.7.2. SHOW TERMINATION FOR PAN DRAIN.
  
 99. SHT P3.02 INSTALLTION NOTES. SE SOVENT (SESCO)&
 TITE-RUFF SYSTEMS, DESIGN MANUAL 101/0 & TABLES. SUBMIT
 MANUF. SPECIFICATION FOR ALL . SHOW TESTING AND
 APPROVAL FOR ALL.
  
 100. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION
 607.3.2. PLEASE INDICATE METHOD.
  
 101. PLEASE RESUBMIT THE SET OF PLUMBING PLANS WITH THE
 RED LINE MARK-UPS TO HELP EXPEDITE FOLLOWING PLAN
 REVIEWS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved