| Date |
Text |
| 2007-04-02 18:30:41 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINSTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL ARCHITECTURAL SHEETS. A TITLE BLOCK MUST AT A |
| | MINIMUM CONTAIN THE FIRM LICENSE NUMBER. FAC |
| | 61G1-16.004(2) |
| | |
| | 2. IRRIGATION PERMIT AND PLANS ARE REQUIRED. |
| | (INFORMATIONAL) |
| | |
| | 3. SHT A2.02 POOL EQUIPMENT ROOM SHALL BE VENTILATED. |
| | EITHER BY CROSS VENTILLATION OR BY FORCED DRAFT. PLEASE |
| | INDICATE METHOD. SECTION 424.1.5.4. |
| | |
| | 4. SHT A2.03 NOT ALL TERRACES, DECK DRAINS AROUND THE |
| | POOL & WALKWAYS SHOW EOD'S. SECTIONS 1107.1 & 1107.2 . |
| | PLEASE INDICATE THE LOCATION OF ALL REQUIRED SECONDARY |
| | DRAINS. |
| | |
| | 5. SHTS A2.03, A2.44 & A4.01 A URINAL IS REQUIRED IN |
| | THE MEN'S TOILET FOR THE POOL FACILITIES. TABLE |
| | 424.1.6.1. |
| | |
| | 6. SHT A2.05 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH |
| | DRAINALONG WITH 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS, STAIRWAYS, MECH ROOMS ECT. ALONG |
| | WITH ALL AREAS OF ROOFS THAT DRAIN TO THE ROOF AREA |
| | FROM ABOVE. TABLE 1106.3. |
| | |
| | 7. SHS A2.38, A2.39, A2.40 & A2.41 W/C'S IN BOTH MASTER |
| | BATHS, THAT ARE COMPARTMENTALIZED, DO NOT HAVE THE |
| | CLEAR FLOOR SPACE REQUIRED AS SHOWN ON PAGE 7.43. THE |
| | WALL CAN NOT EXTEND PAST 2' PER PAGE 7.44. SCALES OUT |
| | PAST 2'. |
| | |
| | 8. SHT A2.41 SHOW SECONDARY DRAINS FOR THE TERRACES AND |
| | WALKWAY.SECTIONS 1107.1 & 1107.2. |
| | |
| | 9. SHTS A2.71 & A2.72 NO FINISH INDICATED FOR THE POOL |
| | TOILET ROOMS. PLEASE SEE SECTION 424.1.6.1.2 AND |
| | SECTION 1210.2. |
| | |
| | 10. SHT A5.01 BLOCKING FOR THE SHOWER SHALL COMPLY WITH |
| | PAGE 6.12. ALSO SHOW BLOCKING ON ALL THREE SIDES AS |
| | REQUIRED. |
| | |
| | 11. SHT A5.02 UNITS 1,2,3,3M,5,6 & 7 BACKING REQUIRED |
| | ON ALL SIDES OF THE TUB PER PAGES 6..8 & 6.9, AND FOR |
| | THE SHOWERS PER PAGE 6.12 IN UNITS 1,3,3M,5,6, & 7. |
| | |
| | 12. SHT A5.03 BACKING REQUIRED ON ALL SIDES OF THE TUB |
| | IN UNITS 03R,8,9,10,10R & 12 PER PAGES 6.8 & 6.9, AND |
| | FOR THE SHOWERS PER PAGE 6.12 IN UNITS 03R,8 & 9. |
| | |
| | 13. SHT A5.03 DETAIL 16, THE CLEAR FLOOR SPACE IS |
| | REQUIRED FOR THE URINAL PER SECTION 11-4.18.3. PLEASE |
| | SHOW ON THE FLOOR PLAN. |
| | |
| | 14. SHTS A5.03 & A5.04. W/C'S IN THE POOL TOILET ROOMS |
| | AND THE RETAIL TOILET ROOM SHALL BE 18" OFF THE WALL TO |
| | THE CENTERLINE OF THE FIXTURE. FIG. 11-28. THE LAVS |
| | SHALL BE 15" MINIMUM OFF THE WALL TO THE CENTERLINE OF |
| | THE FIXTURE TO CENTER ON THE CLEAR FLOOR SPACE 30". |
| | MINIMUM 30" FROM CENTERLINE OF THE W/C TO THE |
| | CENTERLINE OF THE LAVREQUIRED PER SECTION 405.3.1 & |
| | FIGURE 405.3.1. |
| | |
| | 15. SHT A5.04 SHOW THE WATER CLOSET FLUSH CONTROLS AS |
| | REQUIRED IN SECTION 11-4.16.5, (WIDE SIDE). |
| | |
| | 16. ALL PLUMBING, MECHANICAL, AND ELECTRICAL SHEETS. |
| | THE SIGNATURE OF THE ENGINEER IS REQUIRED. INITIALS ARE |
| | SHOWN. FAC 61G15-23.002(2) AND FS 471.025 |
| | |
| | 17. SHT P0.00 KEY NOTE #4 INDICATES A PERFORATED CAP |
| | FOR THE SECONDARY DRAIN. PLEASE CLARIFY. SECTION |
| | 106.1.1. IF THE SECONDARY DRAIN IS FOR STORM, A FULL |
| | SIZE OPENING IS REQUIRED. |
| | |
| | 18. SHT P1.01 INDICATE ALL RISER NUMBERS AT THE BASE OF |
| | EACH STACK AND THROUGH THE BUILDING TO TRACK EACH |
| | RISER. (EXAMPLE S/1, S/2, RWL/1, RWL/2, ETC.). SECTION |
| | 106.1.2. |
| | |
| | 19. SHT P1.01 KEY NOTES #5 & #12 NOT FOUND. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 20. SHT P1.01 STAIR 1 FIRE DRAIN IS LABELED "SD". |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 21. SHT P1.01 ONE "SD" LINE IS INDICATED AS A 6" SANT. |
| | LINE (6). PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 22. SHT P1.01 IDENTIFY THE RISER BETWEEN THE DRINKING |
| | FOUNTAIN AND THE FOUNTAIN DRAIN. (NO KEY NOTE NUMBER). |
| | SECTION 106.1.1. |
| | |
| | 23. SHT P1.01 ONE CONDENSATE LINE TURNS INTO A STORM |
| | LINE. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 24. SHT P1.01 "SD" LINE DOES NOT REFLECT THE RISER IN |
| | THE AREA OF THE THE GAS LINE & BY STAIR 2. PLEASE |
| | CORRELATE. SECTION 106.1.1. |
| | |
| | 25. SHT P1.01 THE SANT. LINE BY SWITCHGEAR ROOM DOES |
| | NOT REFLECT THE RISER. PLEAE CORRELATE. SECTION |
| | 106.1.1. |
| | |
| | 26. SHT P1.02 IDENTYFY ALL RISERS FOR ALL SYSTEMS. |
| | SECTION 106.1.1. |
| | |
| | 27. SHT P1.02 KEY NOTES. THE FOLLOWING KEY NOTES WERE |
| | NOT FOUND. 4,11, & 15. NOTE 10 INDICATES IRRIGATION, |
| | COLD WATER AND "GAS PIPE".PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 28. SHT P1.03 TWO STORM LINES ARE NOT IDENTIFIED. |
| | SECTION 106.1.1. |
| | |
| | 29. SHT P1.03 RISERS D/3 & CD/3 ARE MISLABELED. SECTION |
| | 106.1.1. |
| | |
| | 30. SHT P1.03 ONE RISER IS LABELED AS BOTH KEY NOTES |
| | (17) & (18). PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 31. SHT P1.03W/1 DESIGNATIONAND KEY NOTE NUMBER |
| | NEAR A/C UNIT IN TENANT STORAGE ROOM ARE NOT LEGIBLE. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 32. SHT P1.03 KEY NOTE 19 SHOWN CONNECTING TO THE STORM |
| | RISER. CLARIFY. SECTION 106.1.1. |
| | |
| | 33. SHT P1.03 KEY NOTES 3,9,11,13,16 & 20 WERE NOT |
| | FOUND. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 34. SHT P1.03 RWL/4 DOES NOT LINE UP WITH THE RISERS ON |
| | THE NEXT LEVEL. SHOW OFFSET ON THE RISER DIAGRAM. |
| | SECTION 106.1.1. |
| | |
| | 35. SHT P1.04 SHOWS THE URINAL IN THE WOMEN'S TOILET |
| | ROOM. THIS IS REQUIRED IN THE MEN'S TOILET ROOM PER |
| | SECTION 424.1.6.1. |
| | |
| | 36. SHT P1.04 KEY NOTE (11) INDICATED ON THE FLOOR PLAN |
| | IS NOT SHOWN ON THE KEY NOTE SCHEDULE. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 37. SHT P1.04 THE PRL LINE FOR RISER S/64 IS NOT SHOWN |
| | ON THE FLOOR PLAN. THIS DOES NOT REFLECT THE RISER |
| | DIAGRAM. PLEASE CORRELATE. SECTION 106.1.1. |
| | |
| | 38. SHT P1.04 THE PIPING FOR S/16 DOES NOT REFLECT THE |
| | RISER DIAGRAM. CORRELATE RISER & FLOOR PLAN. SECTION |
| | 106.1.1. |
| | |
| | 39. SHT P1.04 S/7 DESIGNATION SHOWN BUT DOES NOT POINT |
| | TO ANY RISER. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 40. SHT P1.04 THE SINK INDICATED ON RISER S/10 IS NOT |
| | SHOWN ON THE FLOOR PLAN. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 41. SHT P1.04 MANY PLANTER DRAINS & DECK DRAIN AREAS |
| | SHOW WHAT APPEARS TO BE EXTRA DRAINS. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 42. SHT P1.04 THE OVERFLOW SCUPPERS SHALL BE LOCATED AS |
| | NEAR AS PRACTICAL TO THE REQUIRED VERTICAL LEADERS OR |
| | DOWNSPOUTS. SOME AREAS HAVE NOOVERFLOW SCUPPERS. |
| | SECTION 1503.4.3. OVERFLOW SCUPPERS SHALL BE SIZED PER |
| | SECTIONS 1101.7 & 1107.3 AS WELL AS TABLE 1106.7. |
| | |
| | 43. SHT P1.04 SOME AREAS HAVE NO SECONDARY DRAINS ON |
| | THE DECK. SOME AREAS APPEAR TO BE ABLE TO DRAIN INTO |
| | THE THE UNIT BEFORE DRAINING INTO THE SECONDARY DRAIN |
| | BECAUSE OF THE DISTANCE FROM THE MAIN DRAIN TO THE |
| | OVERFLOW DRAIN. PLEASE CLARIFY. SECTIONS 106.1.1 AND |
| | 1107.1. |
| | |
| | 44. SHT P1.04 SOME PLANTER DRAINS, DECK DRAINS SIZES |
| | AND SQUARE FOOTAGE ARE NOT LEGIBLE AS THEY ARE |
| | SUPERIMPOSED OVER OTHER PLAN INFORMATION. PLEASE MAKE |
| | ALL INFORMATION LEGIBLE. SECTION 106.1.1. |
| | |
| | 45. SHT P1.04 PIPING ON THE FLOOR PLAN DOES NOT REFLECT |
| | THE RISER AT THE BASE OF RISERS S/44, S/45, S/69 (W/M). |
| | PLEASE CORRELATE. SECTION 106.1.1. |
| | |
| | 46. SHT P1.04 RISER CD/4 DESIGNATION NOT SHOWN. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 47. SHT P1.05 PIPING ON THE FLOOR PLAN DOES NOT REFLECT |
| | THE RISER AT RISERS S/4 (SINK), S/7, S/10 (SINK), S/11 |
| | (W/M), S/23 (LAV), S/44, S/32. PLEASE CORRELATE |
| | INFORMATION. SECTION 106.1.1. |
| | |
| | 48. SHT P1.05 RISER S/56 DESIGNATION IN NOT LEGIBLE. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 49. SHT P1.05 RISER CD/4 DESIGNATION NOT INDICATED. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 50. SHT P1.05 RWL/10 NOT SHOWN. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 51. SHT P1.06 PIPING ON THE FLOOR PLAN DOES NOT REFLECT |
| | THE RISER DIAGRAMS FOR S/4, S/7, S/10, S/11 & S/50. |
| | CORRELATE. SECTION 106.1.1. |
| | |
| | 52. SHT P1.06 RISER S/56 DESIGNATION IS NOT LEGIBLE. |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 53. SHT P1.06 RISER CD/4 NOT SHOWN. SECTION 106.1.1. |
| | |
| | 54. SHT P1.07INDICATE THE STACK NUMBER FOR EACH VTR |
| | TO VERIFY ALL VENTS THRU THE ROOF. SECTION 106.1.1. |
| | |
| | 55. SHT P1.07 INDICATE THE RWL NUMBER FOR EACH ROOF |
| | DRAIN. SECTION 106.1.1. |
| | |
| | 56. SHT P1.07 MANY VTR'S, RD'S, SF AREAS, ETC ARE |
| | PRINTED OVER OTHER INFORMATION AND ARE NOT LEGIBLE. |
| | PLEASE CLEAR UP ALL INFORMATION. SECTION 106.1.1. |
| | |
| | 57. SHT P1.07 1 4" VTR IS SHOWN UNDER DUCT WORK FOR THE |
| | A/C SYSTEM. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 58. SHT P1.07 SOME AREAS FOR THE ROOF DRAINS DO NOT |
| | SHOW ALL THE AREAS THAT CONTRIBUTE TO THE TOTAL SF. |
| | SOME UPPER ROOFS (SUCH AS STAIR ROOFS, MAINT. ROOM |
| | ROOF, CIRCULAR ROOF), VERTICAL WALLS (SUCH AS STAIRS OR |
| | MAINTENANCE ROOM), DO NOT SHOW ANY CONTRIBUTION. PLEASE |
| | RECHECK ALL AREAS TO VERIFY TOTAL AREA FOR EACH DRAIN. |
| | TABLE 1106.3 AND SECTION 106.1.1. |
| | |
| | 59. SHT P1.07 KEY NOTES SEEM TO BE FOR MECHANICAL. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 60. SHT P2.01 THE 3" BRANCH LINE DOWNSTREAM OF RISER |
| | S/72 DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. |
| | SECTION 106.1.1. |
| | |
| | 61. SHT P2.01 PIPING LAYOUT ON THE FLOOR PLAN TO RISERS |
| | S/45 & S/46 DOES NOT REFLECT THE RISER DIAGRAM. PLEASE |
| | CORRELATE. SECTION 106.1.1. |
| | |
| | 62. SHT P2.01 INDICATE WHERE RISER S/41 CONNECTS TO THE |
| | BUILDING DRAIN/BRANCH LINE. SECTION 106.1.1. |
| | |
| | 63. SHT P2.01 THE COLLECTION RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN DOWNSTREAM OF 6" HD. (SHOWS AN |
| | EXTRA FLOOR DRAIN). CORRELATE. SECTION 106.1.1. |
| | |
| | 64. SHT P2.01 HUB DRAIN INDICATES A 10"X72" HUB PIPE |
| | SEALED AT THE TOP. THE FIRE LINE DRAIN SHALL DRAIN TO |
| | AN INDIRECT WASTE RECEPTOR, AND BY SEALING THE TOP, IT |
| | WILL BE A DIRECTION CONNECTION. PLEASE CLARIFY. SECTION |
| | 802.1.5. |
| | |
| | 65. SHT P2.01 A SECOND RISER S/31 IS INDICATED AS RISER |
| | S/28 ON THE FLOOR PLAN. PLEASE CORRELATE & CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 66. SHT P2.01 PLEASE GIVE A DESIGNATION TO EACH |
| | BUILDING DRAIN INTO THE BUILDING IN ORDER TO TRACK THE |
| | PIPING AND EXPEDITE THE REVIEW PROCESS. SECTION |
| | 106.1.1. |
| | |
| | 67. SHT P2.02 RISERS S/62, S/67 & S/17 WERE NOT FOUND. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 68. SHT P2.02 SECTION (A) INDICATES THE REVENT |
| | CONNECTING TO RISER S/6. RISER S/6 DOES NOT SHOW VENT |
| | CONNECTION TO RISER. PLEASE CLARIFY. SECTION 106.1.1 & |
| | TABLE 916.1. |
| | |
| | 69. SHT P2.02 RISER S/58 SHOWS DFU AS 70, BUT THE |
| | COLLECTION RISER INDICATES DFU AS 86. PLEASE CLARIFY. |
| | SECTION 106.1.1. & TABLES 710.1(1) & 710.1(2). |
| | |
| | 70. SHT P2.02 THE SANITARY COLLECTION RISER DOES NOT |
| | REFLECT THE FLOOR PLAN BY THE SECOND RISER (S/74). |
| | PLEASE CORRELATE. SECTION 106.1.1. |
| | |
| | 71. SHT P2.02 RISER S/18 IS SHOWN AS 84 DFUON THE |
| | COLLECTION RISER, BUT ONLY 14 DFU ON THE RISER DIAGRAM. |
| | PLEASE CLARIFY & CORRELATE. SECTION 106.1.1. |
| | |
| | 72. SHT P2.02 THE SANITARY COLLECTION SHOWS THE VENT |
| | FROM THE SHOWER CONNECTING TO RISER S/74. RISER S/74 |
| | DOES NOT SHOW THE VENT CONNECTING TO THE RISER. PLEASE |
| | CLARIFY AND CORRELATE. SECTION 106.1.1. |
| | |
| | 73. SHT P2.02 RISER S/20 ON THE COLLECTION RISER IS |
| | SHOWN AS 88 DFU, BUT THE RISER DIAGRAM SHOWS IT AS 86 |
| | DFU. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 74. SHT P2.06 2 RISERS FOR S/2 AND S/59 ARE SHOWN. ONE |
| | IS A SOVENT SYSTEM AND THE OTHER IS A CONVENTIONAL |
| | SYSTEM.THE FLOOR PLAN INDICATES A SOVENT SYSTEM. |
| | PLEASE CORRELATE AND DELETE THE SYSTEM NOT USED. |
| | SECTION 106.1.1. |
| | |
| | 75. SHT P2.06 2 RISERS ARE SUBMITTED FOR S/42. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 76. SHT P2.06 RISERS S/34, S/71, S/73, & S/41 ALL SHOW |
| | SHOWERS, BUT THE FLOOR PLAN SHOWS TUBS. PLEASE |
| | CORRELATE. SECTION 106.1.1. |
| | |
| | 77. SHT P2.09 KEY NOTE #1 & RISER DIAGRAM INDICATE AIR |
| | CHAMBERS. AIR CHAMBERS ARE NOT APPROVED. DELETE FROM |
| | THE RISER AND THE NOTES. SECTION 604.9 & PDI-WH 201. |
| | |
| | 78. SHT P2.09 RISERS W/4, W/5, W/6, W/8, W/9, W/11, |
| | W/13, W/17 & W/18 SHOW 1" SUPPLY TO EACH UNIT, BUT ONLY |
| | ARE BEING FED BY 3/4" ON THE RISER AT THE 8TH FLOOR. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 79. SHT P2.09 RISER W/7 SHOWS 3/4" TO THE 8TH FLOOR & |
| | 3/4"SUPPLY TO THE UNIT, BUT THE UNIT RISER SHOWS 1" |
| | SUPPLY TO THE UNIT. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 80. SHT P2.09 RISER W/14 INDICATES A UNIT 14, BUT NO |
| | UNIT 14 HAS BEEN FOUND. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 81. SHT P2.10 RISER W/15 SHOWS 1-1/4" AT THE BASE OF |
| | THE RISER, BUT 1-1/2" IS SHOWN ON THE RISER ON SHT |
| | P2.09. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 82. SHT P2.11 RWL/16 RISER SHOWS 750SF, BUT THE ROOF |
| | PLAN SHOWS 930SF. PLEASE CORRELATE. SECTION 106.1.1 & |
| | TABLE 1106.3. |
| | |
| | 83. SHT P2.11 RWL/15 RISER SHOWS 930SF, BUT THE ROOF |
| | PLAN SHOWS 1440SF. PLEASE CORRLEATE. SECTION 106.1.1. & |
| | TABLE 1106.3. |
| | |
| | 84. THE CONNECTION OF RWL/16 TO RWL/15 ON THE RISER |
| | DOES NOT REFLECT THE ISOMETRIC. ONE SHOWS THE |
| | CONNECTION ON THE HORIZONTAL AND THE OTHER SHOWS THE |
| | CONNECTION ON THE VERTICAL. CORRELATE. SECTION 106.1.1 |
| | & TABLE 1106.3. |
| | |
| | 85. THE SECTION OF HORIZONTAL PIPE BETWEEN RISERS RWL/8 |
| | & RWL/11 SHALL BE A MINIMUM 5" PER TABLE 1106.3. |
| | |
| | 86. SHT P2.12 THE RISER DOES NOT REFLECT THE FLOOR PLAN |
| | PIPING IN 3 AREAS ON THE GROUND FLOOR. PLEASE |
| | CORRELATE. SECTION 106.1.1. |
| | |
| | 87. SHT P2.13 RECHECK SQUARE FOOTAGE OF EACH AREA. SF |
| | OF ONE DECK DRAIN SHOWS 80SF, BUT BY SCALING THE AREA |
| | IT IS MORE. PLEASE CLARIFY. SECTION 106.1.1 & TABLE |
| | 1106.3. |
| | |
| | 88. SHT P2.13 ONE LINE SHOWS 4" @1700SF. A MINIMUM OF |
| | 5" IS REQUIRED UNLESS THE SLOPE IS GREATER THAN |
| | 1/8"/FT. PLEASE CLARIFY. TABLE 1106.3. |
| | |
| | 89. SHT P2.13 THE RISER DOES NOT REFLECT THE FLOOR PLAN |
| | PIPING IN 3 AREAS. PLEASE CORRELATE. SECTION 106.1.1. |
| | |
| | 90. SHT P2.13 THE SIZE OF THE DECK DRAINAGE PIPING |
| | SHALL NOT BE REDUCED IN THE DIRECTION OF FLOW. (6" TO |
| | 4"). SECTION 704.2. |
| | |
| | 91. SHT P2.13 THE TOTAL DRAINAGE AREA IS APPROX. |
| | 20,140SF. THE SECONDARY DRAINS ADD UP TO 6,880SF. |
| | PLEASE CLARIFY. THE SECONDARY DRAINS SHALL DRAIN THE |
| | SAME AMOUNT OF SQUARE FOOTAGE AS THE PRIMARY DRAINS. |
| | SECTION 1107.3. SCUPPERS SHALL BE SIZED TO PREVENT THE |
| | DEPTH OF PONDING WATER FROM EXCEEDING THAT FOR WHICH |
| | THE ROOF WAS DESIGNED AS DETERMINED BY SECTION 1101.7. |
| | PLEASE KEEP IN MIND THE DEPTH OF THE WATER BEFORE THE |
| | SECONDARY DRAINAGE STARTS TO REMOVE THE STORM WATER AND |
| | THE HEIGHT OF THE SLIDING DOORS TO THE UNITS OFF THE |
| | TERACES. |
| | |
| | 92. SHT P2.14 INDICATES GAS PIPE SIZES BASED ON THE |
| | NFPA CHART. PIPING SHALL BE SIZED PER THE FBC-2004 FUEL |
| | GAS CODE. PLEASE CHANGE REFERENCE. |
| | |
| | 93. SHT P2.14 THE LONGEST RUN IS INDICATED AS 58'0", |
| | BUT ADDITION INDICATES 62' WITHOUT COUNTING THE LENGTH |
| | OF PIPES FROM THE METER TO THE FIRST RISER. PLEASE |
| | RECHECK THE ADDITION AND ADD THE PIPE LENGTH FROM THE |
| | METER TO THE FIRST RISER. FBC-2004 FUEL GAS CODE |
| | APPENDIX A - USE OF CAPACITY TABLES A.3.1(4). |
| | |
| | 94. SHT P2.14 INDICATE THE LENGTH OF PIPES FROM THE |
| | REGULATOR TO THE POOL HEATER. |
| | |
| | 95. SHT P2.14 SUBMIT THE MANUF. SPECIFICATION SHEETS |
| | FOR THE POOL HEATER, AND THE REGULATOR. INDICATE THE |
| | MODEL FOR EACH AND SHOW THE LISTING. STANDARDS NFPA 54, |
| | NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | 96. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | 97. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | 98. SHT P2.14 KEY NOTE #13 NOT APPROVED. SECTION |
| | 504.7.2. SHOW TERMINATION FOR PAN DRAIN. |
| | |
| | 99. SHT P3.02 INSTALLTION NOTES. SE SOVENT (SESCO)& |
| | TITE-RUFF SYSTEMS, DESIGN MANUAL 101/0 & TABLES. SUBMIT |
| | MANUF. SPECIFICATION FOR ALL . SHOW TESTING AND |
| | APPROVAL FOR ALL. |
| | |
| | 100. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION |
| | 607.3.2. PLEASE INDICATE METHOD. |
| | |
| | 101. PLEASE RESUBMIT THE SET OF PLUMBING PLANS WITH THE |
| | RED LINE MARK-UPS TO HELP EXPEDITE FOLLOWING PLAN |
| | REVIEWS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |