2007-08-11 16:05:16DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 FROM PLUMBING REVIEW:
  
 92. SHT P2.14 INDICATES GAS PIPE SIZES BASED ON THE
 NFPA CHART. PIPING SHALL BE SIZED PER THE FBC-2004 FUEL
 GAS CODE. PLEASE CHANGE REFERENCE.
  
 93. SHT P2.14 THE LONGEST RUN IS INDICATED AS 58'0",
 BUT ADDITION INDICATES 62' WITHOUT COUNTING THE LENGTH
 OF PIPES FROM THE METER TO THE FIRST RISER. PLEASE
 RECHECK THE ADDITION AND ADD THE PIPE LENGTH FROM THE
 METER TO THE FIRST RISER. FBC-2004 FUEL GAS CODE
 APPENDIX A - USE OF CAPACITY TABLES A.3.1(4).
  
 94. SHT P2.14 INDICATE THE LENGTH OF PIPES FROM THE
 REGULATOR TO THE POOL HEATER.
  
 95. SHT P2.14 SUBMIT THE MANUF. SPECIFICATION SHEETS
 FOR THE POOL HEATER, AND THE REGULATOR. INDICATE THE
 MODEL FOR EACH AND SHOW THE LISTING. STANDARDS NFPA 54,
 NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2.
  
 96. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  