2007-05-01 10:57:191. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A
 MINIMUM OF AT LEAST 6" HIGH AND AT LEAST 1" WIDE
 NUMBERS ARE REQUIRED.
  
 2. DEMOLITION ACTIVITIES TO COMPLY WITH NFPA 241.
  
 3. EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION.
  
 4. DEBRIS SHAHLL BE REMOVED FROM THE SITE DAILY.
  
 5. A TEMPORARY STANDPIPE SYSTEM IS REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT.
  
 6. ALL CUTTING AND WELDING OPERATIONS TO COMPLY WITH
 NFPA 51B.
  
 7. THE BUILDING WILL BE REQUIRED TO BE COMPLETELY FIRE
 SPRINKLER PROTECTED.
  
 8. THE BUILDING WILL BE CONSIDERED A HIGH-RISE BUILDING
 AND SHALL COMPLY WITH THE FLORIDA BUILDING CODE AND THE
 FLORIDA FIRE PREVENTION CODE.
  
 9. SITE PLAN, PAGE A.100 DOES NOT ILLUSTRATE ANY FIRE
 HYDRANT LOCATIONS.
  
 10. THE BUILDING WILL BE CONSIDERED A MULTIPLE
 OCCUPANCY BUILDING SINCE STORAGE, MERCANTILE, AND
 REDIENTIAL OCCUPANCIES WILL EXIST.
  
 11. PLEASE EXPLAIN EXIT DISCHARGE RATIONALE FROM EXIT
 DOORS.
  
 12. PLEASE ILLUSTRATE DIMENSIONS FROM THE PROPOSED
 BUILDING TO THE EXISTING TWO STORY BUILDING.
  
 13. A TWO HOUR FIRE SEPARATION IS REQUIRED BETWEEN THE
 PARKING GARAGE AND ALL OTHER AREAS OF THE BUILDING.
 PROPERLY RATED OPENING PROTECTIVES WILL BE REQUIRED.
  
 14. GROUND LEVEL SITE PLAN DOES NOT ILLUSTRATE THE
 LOCATION OF THE FIRE COMMAND ROOM.
  
 15. PROPER TENANT SEPARATIONS WILL BE REQUIRED BETWEEN
 EACH RETAIL TENANT SPACE.
  
 16. ON PAGE A.200 PORTIONS OF THE BUILDING APPEAR TO
 EXTEND BEYONG THE PROPERTY. PLEASE PROVIDE MORE
 DETAILS.
  
 17. ON PAGE A2.01 IT IS NOTED THAT THE INTERIOR
 BUILD-OUTS WILL BE UNDER SEPARATE PERMIT. PLEASE BE
 ADVISED THAT ALL REQUIRED FIRE AND LIFE SAFETY DEVICES
 FOR THE BUILDING SHALL BE INSTALLED PRIOR TO REQUESTING
 A CERTIFICATE OF OCCUPANCY.
  
 18. EXIT SIGNS NOT DISPLAYED ON LIFE SAFETY SHEETS.
  
 19. ON PAGE LS.1 EXIT DISCHARGE IDENTIFIED IN SOME
 LOCALES ARE POSITIONED BETWEEN OBJECTS. PLEASE
 EXPLAIN.
  
 20. MISSING RATED DOOR SYMBOL NEAR PAGE LS.3.
  
 21. DOOR SWING APPEARS IMPROPER ON PAGE LS.3 LEAVING
 THE POOL DECK AREA.
  
 22. ELEVATOR WARNING SIGNS REQUIRED.
  
 23. WHY IS THE FIRE PUMP ROOM DISPLAYED ON THE
 MEZZANINE LEVEL ON PAGE A2.02.
  
 24. PLEASE EXPLAIN WHAT CHEMICALS ARE PLANNED TO BE
 STORED IN THE POOL EQUIPMENT ROOM ON PAGE A2.02.
  
 25. PLEASE EXPLAIN WHAT CHEMICALS IF ANY WILL BE STORED
 IN THE POOL STORAGE ROOM ON PAGE A2.03.
  
 26. PLEASE INDICATE ON PLANS THE SLIP PROTECTION
 METHODS PLANNED FOR EXIT ACCESS AND EXIT STAIR
 ARRANGEMENTS LOCATED ON THE EXTERIOR.
  
 27. PLEASE PROVIDE FLAME SPREAD DETAILS ON ALL FABRIC
 CANOPIES PLANNED FOR USE.
  
 28. MORE DETAILS REQUIRED ON THE VEHICLE LIFTS
 ILLUSTRATED ON THE PLANS.
  
 29. PLEASE PROVIDE A DETAIL ILLUSTRATING WINDOW
 OPENINGS PRESENT ON THE ADJACENT BUILDING IN RELATION
 TO STAIR # 3.
  
 30. ELECTRIC POWERED SMOKE DETECTORS REQUIRED ON EVERY
 LEVEL OF THE RESIDENTIAL UNITS.
  
 31. SMOKE DETECTORS SHALL BE PLACED A MINIMUM OF AT
 LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS.
  
 32. SOME OF THE LIFE SAFETY SHEETS ILLUSTRATE TWENTY
 MINUTE FIRE DOORS BUT DOOR SCHEDULE SHEETS DO NOT
 INDICATE ANY TWENTY MINUTE FIRE DOORS.
  
 33. PLEASE PROVIDE DETAILS ON EPS FOAM MOLDING
 DISPLAYED ONELEVATION DRAWINGS.
  
 34. PLEASE INDICATE USES OF ALUMINUM LOUVERS SHOWN ON
 THE ELEVATION DRAWINGS.
  
 35. POOL HOUSE REFELECTED CEILING PLAN ON PAGE A4.01
 DISPLAYS AN EMERGENCY LIGHT BUT NO EXIT NO EXIT
 MARKINGS.
  
 36. PLEASE PROVIDE FLAME SPREAD DETAILS ON HIGH DENSITY
 FOAM PRODUCTS ILLUSTRATED ON THE DRAWINGS.
  
 37. EXIT SIGN PLACEMENT SHALL NOT EXTEND ONE HUNDRED
 FEET APART.
  
 38. EXIT SIGN PLACEMENT ON PAGE E1.04 DIFFERS FROM PAGE
 E1.05 CORRIDOR AREAS. PLEASE EXPLAIN.
  
 39. ONLY ONE EXIT SIGN PRESENT ON PAGE E1.06.
  
 40. SMOKE DETECTORS APPEAR TO BE MISSING OUTSIDE OF THE
 SLEEPING ROOMS ON UNIT 11 ON PAGE E2.04.
  
 41. MORE DETAILS REQUIRED ON DAY TANK ILLUSTRATED ON
 PAGE E3.01. SIZE, LISTINGS, MARKINGS, ETC.
  
 42. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM. FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL
 LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION
 SERVICE.
  
 43. WHY IS THERE NO MANUAL PULL STATION NEAR FOYER ON
 PAGE FA1.03 FROM POOL DECK.
  
 44. SMOKE DETECTOR INSTALLATION PLACEMENT SHALL NOT
 EXCEED MANUFACTURER OR CODE REQUIREMENTS.
  
 45. PLEASE INDICATE WHAT MESSAGE IS PLANNED FOR THE
 FIRE ALARM VOICE FEATURE OF THE FIRE ALARM SYSTEM.
  
 46. THE SMOKE CONTROL PANEL INDICATED ON PAGE FA1.07
 SHALL PROVIDE A GRAPHIC REPRESENTATION OF THE BUILDING
 IN ADDITION TO THE FIVE POSITION SWITCHES.
  
 47. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 COMPLETE AUTOMATIC FIRE SPRINKLER SYSTEM.
  
 48. BACKFLOW DEVICE DISPLAYED ON FP 1.01 SHALL ALSO BE
 EQUIPPED WITH A CHAIN AND LOCK.
  
 49. STANDPIPE HOSE VALVES THROUGHOUT THE BUILDING SHALL
 BE EQUIPPED WITH 1 1/2 REDUCERS. PLEASE ENSURE THAT ALL
 FP SHEETS ARE PROVIDED WITH THIS NOTE.
  
 50. NOTE 30 ON PAGE FP3.01 IS INCORRECT. A TEMPORARY
 STANDPIPE IS NEEDED WHEN THE BUILDING REACHES THREE
 STORIES OR THIRTY FEET IN HEIGHT.
  
 51. SMOKE CONTROL NOTE ON PAGE M0.00 INDICATES WINDOWS
 AND PANELS WILL BE USED FOR THE RETAIL AND LIVING
 AREAS. PLEASE IDENTIFY THESE LOCATIONS.
  
 52. ALLL REQUIRED FIRE AND SMOKE DAMPERS ARE TO BE DROP
 TESTED TO ENSURE PROPER FUNCTION AFTER INSTALLATION.
  
 53. ARCHITECTURAL FEATURES SUCH AS SOFFITS SHALL NOT
 INTERFERE WITH ANY FIRE SPRINKLER HEAD OPERATIONS.
  
 54. TCTILE SIGNAGE REQUIRED AT ALL EXITS.
  
 55. STAIRWELL IDENTIFICATION SIGNS REQUIRED. THESE
 SIGNS SHALL IDENTIFY STAIR NUMBER, FLOOR LEVEL,
 TERMINUS TOP AND BOTTOM.
  
 56. STAIRWELL PRESSURIZATION AND OTHER MECHANICAL SMOKE
 MANAGEMENT SYSTEMS SHALL CONSIDER STACK EFFECT. THE
 TERM "STACK EFFECT" SHALL APPEAR ON THE PLANS.
  
 57. THE FIRE PUMP APPEAR ON SOME PLANS ON THE LEFT SIDE
 AND OTHER DRAWINGS THEY APPEAR ON THE RIGHT SIDE. THE
 SAME OREINTATION SHOULD APPEAR.
  
 58. THE LOCATION OF THE FDC SHOULD FACE DATURA STREET
 SO THE HOSE WILL NOT KINK.
  
 59. ELECTRONIC SWITCHES, CHAIN AND LOCK WILL BE
 REQUIRED ON THE FIRE LINE BACKFLOW DEVICE NOTED ON PAGE
 C-13.
  
 60. ALL ELECTRICAL INSTALLATIONS TO COMPLY WITH NFPA
 70, THE NATIONAL ELECTRICAL CODE.
  
 61. ALL UNDERGROUND LINES SHALL BE LOCATED PRIOR TO ANY
 EXCAVATION ACTIVITIES.
  
 62. COULD NOT LOCATE ANY FIRE EXTINGUISHERS ON THE
 PLANS.
  
 63. WHAT USES ARE PLANNED FOR THE MEZZANINES IN THE
 RETAIL AREA.
  
 MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION
 804-4709 PHONE