| Date |
Text |
| 2007-05-01 10:57:19 | 1. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A |
| | MINIMUM OF AT LEAST 6" HIGH AND AT LEAST 1" WIDE |
| | NUMBERS ARE REQUIRED. |
| | |
| | 2. DEMOLITION ACTIVITIES TO COMPLY WITH NFPA 241. |
| | |
| | 3. EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION. |
| | |
| | 4. DEBRIS SHAHLL BE REMOVED FROM THE SITE DAILY. |
| | |
| | 5. A TEMPORARY STANDPIPE SYSTEM IS REQUIRED WHEN THE |
| | BUILDING REACHES THREE STORIES OR THIRTY FEET IN |
| | HEIGHT. |
| | |
| | 6. ALL CUTTING AND WELDING OPERATIONS TO COMPLY WITH |
| | NFPA 51B. |
| | |
| | 7. THE BUILDING WILL BE REQUIRED TO BE COMPLETELY FIRE |
| | SPRINKLER PROTECTED. |
| | |
| | 8. THE BUILDING WILL BE CONSIDERED A HIGH-RISE BUILDING |
| | AND SHALL COMPLY WITH THE FLORIDA BUILDING CODE AND THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | 9. SITE PLAN, PAGE A.100 DOES NOT ILLUSTRATE ANY FIRE |
| | HYDRANT LOCATIONS. |
| | |
| | 10. THE BUILDING WILL BE CONSIDERED A MULTIPLE |
| | OCCUPANCY BUILDING SINCE STORAGE, MERCANTILE, AND |
| | REDIENTIAL OCCUPANCIES WILL EXIST. |
| | |
| | 11. PLEASE EXPLAIN EXIT DISCHARGE RATIONALE FROM EXIT |
| | DOORS. |
| | |
| | 12. PLEASE ILLUSTRATE DIMENSIONS FROM THE PROPOSED |
| | BUILDING TO THE EXISTING TWO STORY BUILDING. |
| | |
| | 13. A TWO HOUR FIRE SEPARATION IS REQUIRED BETWEEN THE |
| | PARKING GARAGE AND ALL OTHER AREAS OF THE BUILDING. |
| | PROPERLY RATED OPENING PROTECTIVES WILL BE REQUIRED. |
| | |
| | 14. GROUND LEVEL SITE PLAN DOES NOT ILLUSTRATE THE |
| | LOCATION OF THE FIRE COMMAND ROOM. |
| | |
| | 15. PROPER TENANT SEPARATIONS WILL BE REQUIRED BETWEEN |
| | EACH RETAIL TENANT SPACE. |
| | |
| | 16. ON PAGE A.200 PORTIONS OF THE BUILDING APPEAR TO |
| | EXTEND BEYONG THE PROPERTY. PLEASE PROVIDE MORE |
| | DETAILS. |
| | |
| | 17. ON PAGE A2.01 IT IS NOTED THAT THE INTERIOR |
| | BUILD-OUTS WILL BE UNDER SEPARATE PERMIT. PLEASE BE |
| | ADVISED THAT ALL REQUIRED FIRE AND LIFE SAFETY DEVICES |
| | FOR THE BUILDING SHALL BE INSTALLED PRIOR TO REQUESTING |
| | A CERTIFICATE OF OCCUPANCY. |
| | |
| | 18. EXIT SIGNS NOT DISPLAYED ON LIFE SAFETY SHEETS. |
| | |
| | 19. ON PAGE LS.1 EXIT DISCHARGE IDENTIFIED IN SOME |
| | LOCALES ARE POSITIONED BETWEEN OBJECTS. PLEASE |
| | EXPLAIN. |
| | |
| | 20. MISSING RATED DOOR SYMBOL NEAR PAGE LS.3. |
| | |
| | 21. DOOR SWING APPEARS IMPROPER ON PAGE LS.3 LEAVING |
| | THE POOL DECK AREA. |
| | |
| | 22. ELEVATOR WARNING SIGNS REQUIRED. |
| | |
| | 23. WHY IS THE FIRE PUMP ROOM DISPLAYED ON THE |
| | MEZZANINE LEVEL ON PAGE A2.02. |
| | |
| | 24. PLEASE EXPLAIN WHAT CHEMICALS ARE PLANNED TO BE |
| | STORED IN THE POOL EQUIPMENT ROOM ON PAGE A2.02. |
| | |
| | 25. PLEASE EXPLAIN WHAT CHEMICALS IF ANY WILL BE STORED |
| | IN THE POOL STORAGE ROOM ON PAGE A2.03. |
| | |
| | 26. PLEASE INDICATE ON PLANS THE SLIP PROTECTION |
| | METHODS PLANNED FOR EXIT ACCESS AND EXIT STAIR |
| | ARRANGEMENTS LOCATED ON THE EXTERIOR. |
| | |
| | 27. PLEASE PROVIDE FLAME SPREAD DETAILS ON ALL FABRIC |
| | CANOPIES PLANNED FOR USE. |
| | |
| | 28. MORE DETAILS REQUIRED ON THE VEHICLE LIFTS |
| | ILLUSTRATED ON THE PLANS. |
| | |
| | 29. PLEASE PROVIDE A DETAIL ILLUSTRATING WINDOW |
| | OPENINGS PRESENT ON THE ADJACENT BUILDING IN RELATION |
| | TO STAIR # 3. |
| | |
| | 30. ELECTRIC POWERED SMOKE DETECTORS REQUIRED ON EVERY |
| | LEVEL OF THE RESIDENTIAL UNITS. |
| | |
| | 31. SMOKE DETECTORS SHALL BE PLACED A MINIMUM OF AT |
| | LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS. |
| | |
| | 32. SOME OF THE LIFE SAFETY SHEETS ILLUSTRATE TWENTY |
| | MINUTE FIRE DOORS BUT DOOR SCHEDULE SHEETS DO NOT |
| | INDICATE ANY TWENTY MINUTE FIRE DOORS. |
| | |
| | 33. PLEASE PROVIDE DETAILS ON EPS FOAM MOLDING |
| | DISPLAYED ONELEVATION DRAWINGS. |
| | |
| | 34. PLEASE INDICATE USES OF ALUMINUM LOUVERS SHOWN ON |
| | THE ELEVATION DRAWINGS. |
| | |
| | 35. POOL HOUSE REFELECTED CEILING PLAN ON PAGE A4.01 |
| | DISPLAYS AN EMERGENCY LIGHT BUT NO EXIT NO EXIT |
| | MARKINGS. |
| | |
| | 36. PLEASE PROVIDE FLAME SPREAD DETAILS ON HIGH DENSITY |
| | FOAM PRODUCTS ILLUSTRATED ON THE DRAWINGS. |
| | |
| | 37. EXIT SIGN PLACEMENT SHALL NOT EXTEND ONE HUNDRED |
| | FEET APART. |
| | |
| | 38. EXIT SIGN PLACEMENT ON PAGE E1.04 DIFFERS FROM PAGE |
| | E1.05 CORRIDOR AREAS. PLEASE EXPLAIN. |
| | |
| | 39. ONLY ONE EXIT SIGN PRESENT ON PAGE E1.06. |
| | |
| | 40. SMOKE DETECTORS APPEAR TO BE MISSING OUTSIDE OF THE |
| | SLEEPING ROOMS ON UNIT 11 ON PAGE E2.04. |
| | |
| | 41. MORE DETAILS REQUIRED ON DAY TANK ILLUSTRATED ON |
| | PAGE E3.01. SIZE, LISTINGS, MARKINGS, ETC. |
| | |
| | 42. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM |
| | SYSTEM. FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL |
| | LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION |
| | SERVICE. |
| | |
| | 43. WHY IS THERE NO MANUAL PULL STATION NEAR FOYER ON |
| | PAGE FA1.03 FROM POOL DECK. |
| | |
| | 44. SMOKE DETECTOR INSTALLATION PLACEMENT SHALL NOT |
| | EXCEED MANUFACTURER OR CODE REQUIREMENTS. |
| | |
| | 45. PLEASE INDICATE WHAT MESSAGE IS PLANNED FOR THE |
| | FIRE ALARM VOICE FEATURE OF THE FIRE ALARM SYSTEM. |
| | |
| | 46. THE SMOKE CONTROL PANEL INDICATED ON PAGE FA1.07 |
| | SHALL PROVIDE A GRAPHIC REPRESENTATION OF THE BUILDING |
| | IN ADDITION TO THE FIVE POSITION SWITCHES. |
| | |
| | 47. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | COMPLETE AUTOMATIC FIRE SPRINKLER SYSTEM. |
| | |
| | 48. BACKFLOW DEVICE DISPLAYED ON FP 1.01 SHALL ALSO BE |
| | EQUIPPED WITH A CHAIN AND LOCK. |
| | |
| | 49. STANDPIPE HOSE VALVES THROUGHOUT THE BUILDING SHALL |
| | BE EQUIPPED WITH 1 1/2 REDUCERS. PLEASE ENSURE THAT ALL |
| | FP SHEETS ARE PROVIDED WITH THIS NOTE. |
| | |
| | 50. NOTE 30 ON PAGE FP3.01 IS INCORRECT. A TEMPORARY |
| | STANDPIPE IS NEEDED WHEN THE BUILDING REACHES THREE |
| | STORIES OR THIRTY FEET IN HEIGHT. |
| | |
| | 51. SMOKE CONTROL NOTE ON PAGE M0.00 INDICATES WINDOWS |
| | AND PANELS WILL BE USED FOR THE RETAIL AND LIVING |
| | AREAS. PLEASE IDENTIFY THESE LOCATIONS. |
| | |
| | 52. ALLL REQUIRED FIRE AND SMOKE DAMPERS ARE TO BE DROP |
| | TESTED TO ENSURE PROPER FUNCTION AFTER INSTALLATION. |
| | |
| | 53. ARCHITECTURAL FEATURES SUCH AS SOFFITS SHALL NOT |
| | INTERFERE WITH ANY FIRE SPRINKLER HEAD OPERATIONS. |
| | |
| | 54. TCTILE SIGNAGE REQUIRED AT ALL EXITS. |
| | |
| | 55. STAIRWELL IDENTIFICATION SIGNS REQUIRED. THESE |
| | SIGNS SHALL IDENTIFY STAIR NUMBER, FLOOR LEVEL, |
| | TERMINUS TOP AND BOTTOM. |
| | |
| | 56. STAIRWELL PRESSURIZATION AND OTHER MECHANICAL SMOKE |
| | MANAGEMENT SYSTEMS SHALL CONSIDER STACK EFFECT. THE |
| | TERM "STACK EFFECT" SHALL APPEAR ON THE PLANS. |
| | |
| | 57. THE FIRE PUMP APPEAR ON SOME PLANS ON THE LEFT SIDE |
| | AND OTHER DRAWINGS THEY APPEAR ON THE RIGHT SIDE. THE |
| | SAME OREINTATION SHOULD APPEAR. |
| | |
| | 58. THE LOCATION OF THE FDC SHOULD FACE DATURA STREET |
| | SO THE HOSE WILL NOT KINK. |
| | |
| | 59. ELECTRONIC SWITCHES, CHAIN AND LOCK WILL BE |
| | REQUIRED ON THE FIRE LINE BACKFLOW DEVICE NOTED ON PAGE |
| | C-13. |
| | |
| | 60. ALL ELECTRICAL INSTALLATIONS TO COMPLY WITH NFPA |
| | 70, THE NATIONAL ELECTRICAL CODE. |
| | |
| | 61. ALL UNDERGROUND LINES SHALL BE LOCATED PRIOR TO ANY |
| | EXCAVATION ACTIVITIES. |
| | |
| | 62. COULD NOT LOCATE ANY FIRE EXTINGUISHERS ON THE |
| | PLANS. |
| | |
| | 63. WHAT USES ARE PLANNED FOR THE MEZZANINES IN THE |
| | RETAIL AREA. |
| | |
| | MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION |
| | 804-4709 PHONE |
| | 804-4774 FAX |