Plan Review Notes
Plan Review Notes For Permit 07020735
Permit Number 07020735
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-22 19:47:312007-03-22 19:47:31
  
 ****** UNSAT ******
  
  
 *** DATURA & OLIVE ***
  
 ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT BEEN
 SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-20
 2002 NFPA-110
 ** SOME OP THESE CODES MAY BE PRESENT ON PLANS HOWEVER
 PLEASE SEE PLANS FOR ELECTRICAL AS THERE ARE SEVERAL
 CODE SECTIONS WHICH ARE REFLECTED ON PLANS FROM THE
 PREVIOUS CODES AND ANY NEW CODE SECTIONS SHOULD BE
 REFLECTED.
  
 2) NOTE: PLEASE SEE THE ARCHITECTURAL FIRM TITLE BLOCKS
 ARE MISSING INFORMATION AS REQUIRED PER FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004 AS REQUIRED UNDER
 FLORIDA STATUTES 481.219
  
 3) NOTE: PLEASE SEE LANDSCAPE PLANS WHICH CONTAIN A
 *RUBBER STAMP* FOR THE REQUIRED ORIGINAL SIGNATURE.
 THIS IN PROHIBITED UNDER FS 481.221 AND MUST BE AN
 ORIGINAL SIGNATURE AND DATE.
  
 4) NOTE: PLEASE SEE THE SHEETS WHICH ARE DONE BY STEVEN
 FELLER SHALL CONTAIN THE LEGAL SIGNATURE OF THE
 INDIVIDUAL AS RECOGNIZED, ON FILE, AND ON RECORD BY
 THIS OFFICE. PLEASE SEE FS 471.025 AND FAC 61G15-23.002
 WHICH REQUIRES ALL DOCUMENTS TO CONTAIN THE ORIGINAL
 SIGNATURE, DATE AND SEAL.
 PLEASE SEE OTHER DOCUMENTS SUBMITTED AS THESE ARE ALSO
 NOT SIGNED WITH SIGNATURE FROM THE ENGINEER OF RECORD
 KNOWN TO THIS OFFICE.
 PLEASE KNOW THAT THIS OFFICE HAS GIVEN NOTICE ON
 SEVERAL OCCASIONS FOR THIS SAME ISSUE AND PLANS MAY BE
 RETAINED BY THIS OFFICE FOR REVIEW FROM THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS.
  
 5) NOTE: PLEASE KNOW THAT ALL PLANS SHALL CONTAIN
 ORIGINAL SIGNATURES, DATES AND RAISED SEALS FROM ALL
 DESIGN PROFESSIONALS. PLEASE SEE THE ARCHITECTURAL
 SHEETS SEEMED TO BE *SIGNED* WITH INITIALS, AND ARE NOT
 DATED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 DESIGN PROFESSIONAL, PLEASE SUBMIT A SIGNED, DATED AND
 SEALED LETTER FOR SIGNATURE VERIFICATION. (FS 471.025,
 481.221) THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR
 FUTURE REFERENCE.
 PLEASE BE SURE LETTER IS PROPERLY NOTARIZED PER FS
 117.05 FOR NOTARIES.
  
 6) NOTE: PLEASE SEE FBC 2004 W/ 2006 FOR THE FLORIDA
 ENERGY CODE AND RELEVANT CODES FOR THIS BUILDING.
 PLEASE SEE THERE ARE AREAS WHICH DO NOT SHOW LIGHTING
 CONTROLS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE SEE THAT THE ENERGY CALCULATIONS DO NOT INDICATE
 AUTOMATED CONTROLS FOR LIGHTING. SHOWS MANUAL ON/OFF
 FOR CONTROL METHODS.
 PLEASE SEE 13-415.2 FOR PERFORMANCE OF INTERIOR
 LIGHTING.
 PLEASE PROVIDE INFORMATION IN DETAIL FOR THIS. PLEASE
 SEE THE LIGHTING SHOWN ON PLANS DOES NOT CORRELATE WITH
 THE ENERGY CALCULATIONS.
 PLEASE SEE ALL OF THE REVISED CHAPTER 13 ITEMS ALONG
 WITH THE EXISTING IN THE 2004.
  
 7) NOTE: PLEASE SEE THAT THE MAIN ELECTRICAL ROOM AND
 ELECTRICAL EQUIPMENT LOCATED IN THE GENERATOR ROOM
 SHALL BE GONE OVER WITH THE FIRE MARSHAL'S OFFICE.
 PLEASE SEE AT THIS TIME, DIRECT ACCESS TO THE MAIN
 ELECTRICAL ROOM THROUGH ANY RATED CORRIDOR, OR DIRECT
 DOOR ACCESS IS NOT SHOWN AT THIS TIME AND FURTHER
 REVIEW WILL BE NEEDED. PLEASE SEE THE LOCATION OF THE
 EDP WILL ALSO BE NOTED IN LATER NOTES FOR THE LOCATION
 OF CONTROL OF EM LOADS IN THE EVENT OF AN EMERGENCY.
 ACCESS AND LOCATION OF THIS EQUIPMENT SHOULD BE
 CONSIDERED AS DURING AN EVENT; ANY FIRE DEPARTMENT
 PERSONNEL MUST ACCESS ROOM AND CONTROL EQUIPMENT WHILE
 THE GENERATOR IS RUNNING AT CAPACITY. THE NOISE,
 LOCATION, HEAT, FUEL AND DISTRACTIONS COULD CREATE A
 HAZARD TO THESE PERSONS AND NOT BEING ABLE TO CONTROL
 ITEMS IN ORDER ETC. PLEASE CALL TO GO OVER THESE
 LOCATIONS ONCE ALL REVIEWS ARE DONE. THIS OFFICE WILL
 CONSULT WITH THE FM OFFICE AT A LATER DATE. NFPA-110
 7.2
  
 8) NOTE: PLEASE SUBMIT THE MANUFACTURE'S SPECS/CUT
 SHEETS FOR THE FOLLOWING.FIRE PUMP, FIRE PUMP
 CONTROLLER, GENERATOR, ATS, FUEL TANK(S).
 PLEASE KNOW ANY OTHER EQUIPMENT SPECS MAY BE REQUESTED
 FROM OTHER TRADES.
 110.3, 90.7.
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE THE FOLLOWING LOCATIONS SHALL
 CONTAIN EMERGENCY BATTERY BACK UP LIGHTS OF SOME KIND.
  
 GENERATOR ROOM (TO A LEVEL OF 30FT CANDLES), FIRE
 COMMAND ROOM, MAIN ELECTRICAL ROOM, METER CENTER ROOMS,
 ELEVATOR EQUIPMENT ROOM(S).
 PLEASE SEE NEXT NOTE WITH RESPECT TO STAIRS.NFPA-70
 110.26, 700.16, 700.12E, NFPA-110 7.3, NFPA-20 5.12.3,
 AND .4, NFPA-72 CHAPTER 2 FOR FCRM.
  
 10) NOTE: PLEASE SEE THE STAIRS AS ONE OF THE LIGHTING
 FIXTURES ON EACH LEVEL WILL BE REQUIRED TO CONTAIN A
 BATTERY BACK UP FIXTURE OF SOME TYPE. PLEASE ALSO
 PROVIDE THE MINIMUM PHOTO-METRICS FOR STAIRS UNDER
 NORMAL AND UNDER EMERGENCY CONDITIONS.
 PLEASE SEE NFPA-101, 7.8., 7.9
  
 11 NOTE: PLEASE PROVIDE NOTES FOR FAIL SAFE OPERATION
 OF GATES/DOORS WHICH MAY NOT INTERFERE WITH EGRESS IN
 THE EVENT OF POWER FAILURE.
 PLEASE SEE NFPA-101 CHAPTER 7, 7.1.9,7.2.1.5.
  
 12) NOTE: PLEASE SEE DOORS ON WEST WALL WHICH SEEM TO
 SWING IN PATH OF EGRESS. PLEASE ALSO VERIFY THE MAKE UP
 AIR, AND/OR EXHAUST ALONG THIS SAME AREA OF EGRESS.
 PLEASE SEE THAT THIS MAY ALSO BE IN THE COMMENTS FROM
 OTHER TRADES.
 PLEASE VERIFY WITH ALL TRADES AND REVIEWER(S).
 FBC 106.1.2
  
 13) NOTE: PLEASE PLACE A SCHEDULE/ LIST FOR ALL
 COMPONENTS IN THE FIRE COMMAND ROOM AS REQUIRED PER
 NFPA-101 11.8.5
  
 14) NOTE: PLEASE PROVIDE INFORMATION ON CAR LIFTS AND
 BE SURE EQUIPMENT INDICATES LISTING ON EQUIPMENT FROM A
 NRTL.
 110.3, 90.7
  
 15) NOTE: PLEASE BE SURE ALL DEVICE AND LEVELS FOR
 HORNS AND STROBES MEET FBC ADA 11-4.28, .1, .2 AND
 .3(4).
  
 16) NOTE: PLEASE PROVIDE ELEVATIONS FOR THE EPSS SYSTEM
 WHICH MUST MEET THE ELEVATIONS AS SET-FORTH ON THE
 100YEAR STORM SURGE CHARTS OR *SLOSH* CHARTS PER
 CHAPTER 7, 7.3.1 NFPA-110.
  
 17) NOTE: PLEASE PROVIDE INFORMATION ON FUEL
 CONSUMPTION ON GENERATOR FOR 100% LOAD OF THE FIRE PUMP
 AND ALL EMERGENCY SYSTEMS PER 700 AND 701.
 PLEASE SEE NFPA-110, NFPA-20 9.6.2.2
  
 18) NOTE: PLEASE SEE THE NEW FLORIDA STATE STATUTES
 WITH RESPECT TO THE NEW HOUSE BILL 7121 WHICH WAS
 SIGNED INTO LAW JULY OF 07.
 PLEASE SEE THERE ARE SEVERAL STATUTES WHICH WERE
 AFFECTED. PLEASE SEE THAT A INDUSTRY BULLETIN IS BEING
 PLACED IN WITH THE REVIEW NOTES AS ADDITIONAL
 INFORMATION.
 *ONCE THIS INFORMATION IS READ AND STATUTES REVIEWED,
 PLEASE PROVIDE ALL INFORMATION AS REQUIRED ON PLANS AND
 DOCUMENTATION FOR REVIEW.
 PLEASE KNOW THAT SOME OF THIS INFORMATION WILL ALSO BE
 NEEDED BY THE FIRE MARSHAL, STATE BOARD FOR ELEVATORS
 ETC.
  
 19) NOTE: PLEASE BE SURE THE FOLLOWING STATEMENT IS
 PLACED ON PLANS AS REQUIRED PER FBC 109.3.6.4.4 PLEASE
 SEE A STATEMENT OF SIMILAR WORDING IS ALREADY ON THE
 LIFE SAFETY PLANS.
 " TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633, FLORIDA STATUTES"
  
 20) NOTE: PLEASE SEE PART OF FIRE PUMP FEEDS FROM FPL
 APPEARS TO BE ROUTED THROUGH ONE OF THE CORRIDORS ON
 SHEET E1.01. PLEASE CLARIFY THIS AS THE RISER DOES NOT
 SHOW DETAIL FOR THIS.
 PLEASE SEE 695.6A.
  
 21) NOTE: PLEASE PROVIDE THE NORMAL AND EMERGENCY
 PHOTO-METRICS FOR ALL EGRESS PATHS. PLEASE KNOW THIS
 WOULD ALSO INCLUDE POOL DECK AREAS. ETC
 LS 101 7.8, 7.9
 FBC 106.1.2
  
 22) NOTE: PLEASE PROVIDE NOTE FOR POOL AREA LIGHTS:
 LIGHTING SHALL BE INSTALLED A MINIMUM OF 5FT FROM
 WATERS EDGE FOR 120V W/GFI PROTECTION AND A MINIMUM OF
 10FTFOR LOW VOLTAGE TYPE FIXTURES. (WORDS TO THIS
 AFFECT)
 680.22, 411.4B
  
 23) NOTE: PLEASE PROVIDE NOTE FOR POOL AREA AND THE
 EQUAL-POTENTIAL BONDING GRID WHICH IS REQUIRED PER
 680.26. PLEASE KNOW THE POOL PERMIT WILL BE UNDER A
 SEPARATE PERMIT, HOWEVER AS THE STRUCTURAL ELEMENTS
 MOST LIKELY WILL BE IN PLACE BEFORE PERMITTING OF POOL,
 PLEASE INCLUDE NOTE AT THIS TIME.
  
 24) NOTE: PLEASE INCLUDE NOTE FOR ANY LIGHTNING
 PROTECTION SYSTEMS SHALL MEET NFPA-780. (EVEN WHEN
 PERMITTED SEPARATELY OR IF A SYSTEM IS NOT GOING TO BE
 INSTALLED AT THIS TIME).
  
 25) NOTE: PLEASE PROVIDE WIND LOADS AND INFORMATION FOR
 SITE/ROOF TOP POLES WHICH ARE REQUIRED TO MEET FBC
 140MPH.
 THIS WILL BE REVIEWED ONCE SUBMITTED BY THE STRUCTURAL
 REVIEWER. PLEASE KNOW THE EFFECTIVE PROJECTED AREA
 (EFA) OF FIXTURE.
 FBC 106.1.2
  
 26) NOTE: PLEASE PROVIDE NOTE FOR NO NIGHT-TIME OR DUSK
 TO DAWN SWIMMING PERMITTED UNLESS THE INTENT IS THAT
 NIGHT-TIME SWIMMING WILL BE ALLOWED. IF THIS IS THE
 CASE PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR POOL AREA
 WHICH WILL BE REQUIRED TO BE STAMPED BY THE PALM BEACH
 COUNTY HEALTH DEPARTMENT.
 FBC 106.1.2
  
 27) NOTE: PLEASE BE SURE TO PROVIDE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS. PLEASE KNOW SOME AREA
 DESIGNATIONS ARE NEEDED TO DETERMINE ARE USE AND REVIEW
 FOR CIRCUITING CODE COMPLIANCE AND USE.
 FBC 106.1.2
  
 28) NOTE: PLEASE PROVIDE MORE INFORMATION FOR ELEVATOR
 ROOMSAND THE DEDICATE CIRCUITS REQUIRED PER 620.22,
 23 AND 24. SOME OF THESE ARE SHOWN ON PLANS, HOWEVER
 NOT ALL.
 PLEASE SEE COMMENT #9 ABOVE WITH RESPECT TO LIGHTING
 REQUIRED. PLEASE ALSO SEE THAT THE ROOF TOP APPEARS TO
 SHOW ANOTHER AREA WHICH CONTAINS MAINS FOR EACH OF THE
 ELEVATORS, YET THE PLANS DO NOT APPEAR TO SHOW ANY ROOM
 FOR EQUIPMENT?? PLEASE CLARIFY THIS AREA AS REDLINED ON
 PLANS. IF THERE IS A SECOND ROOM, PLEASE PROVIDE
 INFORMATION AND ELECTRICAL AS REQUIRED FOR ROOM. FBC
 106.1.2
  
 29) NOTE: PLEASE PROVIDE COMPLETE DE-RATING
 CALCULATIONS FOR CONDUITS AND FEEDERS BEING RUN ACROSS
 ROOF-TOP AREA. PLEASE KNOW THE TYPE OF ROOF ALONG WITH
 OTHER FACTORS WILL HAVE AN AFFECT ON THE TEMPERATURE.
 PLEASE SEE NEC 310.16, TABLES FOR DE-RATING AND THE
 NUMBER OF CURRENT CARRYING CONDUCTORS.
 THE FEEDERS AS SHOWN ON RISER AND PANELS FEEDING THESE
 OTHER PANELS ARE NOT OF SUFFICIENT SIZE AS SHOWN ON
 PLANS.
 PLEASE ADJUST.
 FBC 106.3.5.1.2, 106.1.2
 NEC 215.5, 215.3 ETC
  
 30) NOTE: PLEASE PROVIDE VOLTAGE DROP FOR THE SAME
 FEEDERS AS NOTED IN NOTE #29.
 PLEASE SEE FBC 13-413.ABC.1
 PLEASE ALSO PROVIDE WORST CASE VOLTAGE DROP FOR BRANCH
 CIRCUITS AND FEEDERS AS ON PLANS FOR LONGEST RUNS.
  
 31) NOTE: PLEASE SEE NFPA-72, FBC FOR THE DEFINITIONS
 OF SMOKE DEVICES. PLEASE DETERMINE IF THESE ARE INDEED
 DEVICES WHICH ONLY DETECT AND DO NOT SOUND.
 IF DEVICES DETECT AND ONLY PROVIDE SIGNALING TO
 HORN/SIREN DEVICES THEN THESE WOULD BE SD/ SMOKE
 DETECTORS.
 IF DEVICES ARE 120V BATTERY BACK AS SHOWN ON PLANS
 WHICH DETECT AND SOUND, THEN THESE DEVICES WOULD BE
 CONSIDERED SA/ SMOKE ALARMS.
 PLEASE ADJUST PLANS.
 NFPA-72 11.5.1.1, 11.8.3
  
 32) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING GFI
 RECEPTACLES ON SOME PENINSULAS IN KITCHENS PER
 210.52C1-5. PLEASE SEE LOCATION OF SOME DO NOT SEEM TO
 MEET THE DISTANCE PERMITTED.
 PLEASE SEE UNIT #4, #5 WHICH SHOW MORE THAN 6INCH
 OVERHANG.
 PLEASE SEE THAT THERE ARE OTHER UNITS WHICH ARE ALSO
 MISSING SOME COVERAGE PER ABOVE. PLEASE GO OVER PLANS
 AND SEE REDLINED PLANS FOR SOME OF THESE WHICH MAY BE
 MARKED ON REVIEWED SET.
  
 33) NOTE: PLEASE SEE SOME UNITS WHICH DO NOT APPEAR TO
 SHOW ANY LIGHTING FIXTURE IN BEDROOMS. PLEASE SEE
 210.70, LS 7.8 WHICH WILL REQUIRE A LIGHT FIXTURE IF
 SOME SORT INSTALLED FOR FINAL.
  
 34) NOTE: PLEASE SEE UNIT #5, AS THE CLOSET IN
 DEN/BEDROOM #3 SEEMS TO SHOW A GFI IN CLOSET? PLEASE
 CLARIFY.
 FBC 106.1.2
  
 35) NOTE: PLEASE INCLUDE NOTE ON PLANS FOR PLACEMENT OF
 SA/SD DEVICES PER NFPA-72 2002 11.5.1.1, 11.8.3
  
 36) NOTE: PLEASE SEE UNIT #6 WHICH APPEARS TO SHOW A
 FLOOR BOX IN THE DOORWAY WHICH IS A TRIPPING HAZARD.
 PLEASE SEE 210.52 FOR LOCATIONS WHICH ARE PROHIBITED.
  
 37) NOTE: PLEASE SEE 210.52D AS THE GFI RECEPTACLE IN
 BATHROOMS ARE REQUIRED TO CONTAIN THE DEVICE WITHIN 3FT
 OF THE SINK EDGE. PLEASE KNOW THAT THE CROSSING OVER
 ONE SINK TO REACH THE DEVICE ON THE OTHER SIDE IS NOT
 PERMITTED. PLEASE EITHER ADD A DEVICE OR RELOCATE.
 PLEASE SEE UNIT #7 FOR EXAMPLE. THIS IS NOT AN ISSUE IN
 ALL UNITS.
  
 38) NOTE: PLEASE SEE THAT ARC FAULT IS REQUIRED FOR ALL
 OUTLETS INCLUDINGRECETPS, LTS, FANS AND SMOKE
 ALARMS.
 PLEASE SEE 210.12.
  
 39) NOTE: PLEASE SEE UNIT H FOR 10FT OF HALLWAY PER
 210.52H
  
 40) NOTE: PLEASE SEE SOME WALLS/UNITS MISSING
 RECEPTACLES FOR WALL SPACES.UNITS L-9, 9,PLEASE SEE
 210.52. EXAMPLE FOR SOME ARE REDLINED ON PLANS.
  
 41) NOTE: PLEASE SEE UNIT L-8 WHICH PANEL SCHEDULE
 CALLS CIRCUIT #23 AS A BEDROOM. THIS IS NOT CLEAR AS
 THE ROOM IS APPROXIMATELY 6FT BY 10FT AND IS RIGHT OFF
 THE DINING/ KITCHEN AREA WITH NO DOOR?
 PLEASE CLARIFY THIS.
  
 42) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES AND OTHER CIRCUITS
 ON PLANS.
 PLEASE SEE THAT MOST OF THE CIRCUITS ARE SHOWN HOWEVER
 SEE REDLINED PLANS AND SEE 9, L8, L9 FOR SOME
 EXAMPLES.
 408.4, 310.16, 240.4.
 FBC 106.1.2
  
 43) NOTE: PLEASE PROVIDE NOTES ON ELECTRICAL ROOMS/FIRE
 COMMAND ROOMS SHEETS ALONG WITH THE RISER SHEETS FOR
 REQUIREMENTS FOR SIGNAGE FOR ALL SERVICES, MAINS,
 LOCATIONS.
 230.2E, 700.8, 701.9 ETC
  
 44) NOTE: PLEASE BE SURE TO CORRELATE LABELING OF ALL
 UNITS ON RISER WITH PANELS. PLEASE PROVIDE THE OCP FOR
 EACH UNIT ON METER SCHEDULE OR SCHEDULE OF SOME KIND
 FOR EACH.
 NEED FOR REVIEW OF CODE COMPLIANCE FOR EACH UNIT
 FEEDERS ETC
 215.5, 240.4,
 FBC 106.3.5.1.2
  
 45) NOTE: PLEASE SEE THAT THE EDP WILL REQUIRE A MCB AS
 THE POWER BEING SHUT OFF FROM THE GENERATOR CAN NOT BE
 VERIFIED. PLEASE KNOW THAT THE DISCONNECTING MEANS
 SHALL BE READILY ACCESSIBLE WITHOUT EXPOSING ANY
 PERSONS TO LIVE PARTS. 110.27.
 230.70, 701, 700 ETC.
 ADDITIONAL INFORMATION IS NEEDED, AND PLEASE KNOW ONE
 CONSULTATION IS DONE BY THIS OFFICE WITH THE FIRE
 MARSHAL FOR LOCATION OF SAID EQUIPMENT SHUT DOWN/EDP
 THEN THIS CAN BE GONE OVER WITH THE ENGINEERS/DESIGNERS
 OF PROJECT.
  
 46) NOTE: PLEASE PROVIDE ALL GENERATOR, ATS, FIRE PUMP,
 FIRE PUMP CONTROLLER ON PLANS.
 FBC 106.3.5.1.2
  
 47) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS
 FOR THE FIRE PUMP ARE SHOWN RATED FOR 205AMPS, YET THE
 LOAD IS SHOWN HIGHER AT 221 AMPS. PLEASE SEE 430.50,
 AND SIZING OF THE CONDUCTORS WHICH ARE REQUIRED TO BE
 @125%.
 430.22, 230.208, 240.4, 310.16 ETC.
 PLEASE SEE THE CONDUCTORS FROM THE GENERATOR ARE SIZE
 FOR MORE THAN ONE RUN OF THE SAME SIZE CONDUCTORS.
  
 48) NOTE: PLEASE SEE JUST BELOW THE LOAD SUMMARY ON
 SHEET 4.01 WHICH CONTAINS AN *AND MAG ONLY CB. PLEASE
 SEE THE LOAD SUMMARY DOES NOT INDICATE ANY * ON ANY OF
 THE ITEMS ABOVE THIS NOTE.
 PLEASE CLARIFY THIS NOTE.
 FBC 106.1.2
  
 49) NOTE: PLEASE SEE THE MAIN #5 FOR ONE 100AMP RETAIL
 SERVICE IS NOT BEING PERMITTED AT THIS TIME UNDER THE
 EXCEPTIONS OF 230.2.
 PLEASE KNOW THAT THIS SINGLE TENANT FEED WILL BE
 REQUIRED TO COME FROM WHAT IS MAIN #6 AT THIS TIME
 WHICH WILL BE REQUIRED TO BECOME MAIN #5 FOR RETAIL.
 PLEASE SEE THE FOLLOWING COMMENT WITH RESPECT TO WHAT
 IS BEING SHOWN NOW FOR MAIN 6.
  
 50) NOTE: PLEASE SEE RISER WHICH CURRENTLY SHOWS MAIN
 #6 AS BEING FUTURE HOWEVER THE RISER SHOWS CONDUITS AND
 SERVICE ENTRANCE CONDUCTORS BEING INSTALLED AT THIS
 TIME? PLEASE KNOW THAT ALL EQUIPMENT MUST BE INSTALLED
 IN ITS COMPLETENESS IN ORDER FOR THE CONDUCTORS TO BE
 TERMINATED IN REQUIRED FASHION.
 PLEASE SEE RISER WHICH ACTUALLY SHOWS THE GUTTER BEING
 INSTALLED AT THIS TIME? HOW IS THIS POSSIBLE? PLEASE
 SEE THAT THE MAIN WHICH IS SHOWN IN THE MAIN ELECTRICAL
 ROOM NEXT TO THE EMERGENCY MAIN WILL NOT BE PERMITTED.
 THIS MAIN #6 WHICH WILL BECOME MAIN #5 WILL BE REQUIRED
 TO BE MOVED/RELOCATED.
 PLEASE ALSO SEE THE SCHEDULE FOR THIS RDP SHOWS THIS A
 BEING A MLO PANEL??
 PLEASE SEE ELECTRICAL PLANS INDICATE A MAIN? PLEASE
 ALSO KNOW A MAIN WILL BE REQUIRED TO GRANT THE
 ADDITIONAL SERVICE AS SHOWN.
 PLEASE SEE 230.70, 230.71, 230.72, 230.2.
 PLEASE KNOW IF THIS SERVICE IS GOING TO BE INSTALLED
 AND DEPENDING TO WHAT POINT THE EQUIPMENT WILL BE
 INSTALLED AT THIS TIME WILL DETERMINE WHAT WILL BE
 REQUIRED TO BE SHOWN. PLEASE KNOW IT APPEARS THE MAIN,
 AND GUTTER AT A MINIMUM WILL BE REQUIRED AT THIS TIME.
 PLEASE KNOW IF THIS IS THE CASE, PLEASE INCLUDE THE
 CONDUCTORS FROM THIS MAIN TO GUTTER. 310.16, 240.4,
 250.110, 250.122, 250.24B ETC.
 ** PLEASE KNOW THAT THERE ARE MANY ITEMS WHICH MAY NOT
 BE KNOWN AT THIS TIME DUE TO CHANGES IN SERVICE(S) FROM
 NOTES #49 AND #50.
  
 51) NOTE: PLEASE PROVIDE MORE INFORMATION ON WHICH
 CONDUCTORS ARE GOING TO BE COPPER. PLEASE SEE NOTE ON
 PANEL PLANS MENTIONS ALL CONDUCTORS ARE GOING TO BE
 ALUMINUM UNLESS OTHER WISE NOTED, YET THE FOLLOWING
 NOTE MENTIONS ALL GROUNDS TO BE COPPER? PLEASE CLARIFY
 WHAT CONDUCTORS ARE GOING TO BE COPPER AND ALUM. PLEASE
 KNOW AT THAT NO GROUNDING ELECTRODE SYSTEMS OR
 CONDUCTORS TO THIS SYSTEM WILL BE PERMITTED TO BE
 ALUM.
 PLEASE SEE 110.3, 90.4
  
 52) NOTE: PLEASE SEE THAT THE RISER SHEET CONTAIN A
 NOTE #1 AT THE GENERATOR WHICH POINTS TO THE BASE OF
 THE UNIT, HOWEVER THE NOTE #1 IS FOR VERTICAL SUPPORT
 OF CONDUCTORS?
 PLEASE COORDINATE.
 FBC106.1.2
  
 53) NOTE: PLEASE INDICATE AMPERAGE ON METER CENTERS AND
 FOR OVER CURRENT PROTECTION TO UNITS.
 240.4, 310.16, 230.94 ETC.
 FBC 106.1.2
  
 54) NOTE: PLEASE SEE LOAD CALCULATIONS AND THE SECTION
 OF THE CODES IN DIFFERENT PLACES WHICH ARE FROM THE
 PREVIOUS CODE. PLEASE SEE THE 2005 NEC AND UPDATE CODE
 SECTIONS.
 FBC 106.1.2
  
 55) NOTE: PLEASE SEE THE CONDUCTORS WHICH ARE SHOWN
 GOING TO WHAT IS NOW BEING SHOWN AS MAIN #6 IS ONLY
 RATED FOR 1000 AMPS, YET THIS EQUIPMENT WILL HAVE A
 MAIN OF 1200AMPS OR MORE.
 PLEASE SEE 240.4C FOR DEVICES RATED OVER 800AMPS.
  
 56) NOTE: PLEASE KNOW AS NOTICE FOR FUTURE RETAIL
 TENANT METERS, AS THESE WILL BE REQUIRED TO CONTAIN
 *FLOATING NEUTRAL KITS* AS THE BONDING WILL BE DONE AT
 THE FIRST MEANS OF DISCONNECT PER 250.24B AND THE
 EQUIPMENT GROUNDING WILL BE FOLLOW.
 PLEASE KNOW THAT THE NEUTRALS AND EQUIPMENT GROUNDING
 WILL BE REQUIRED TO BE SEPARATED TO AVOID OBJECTIONABLE
 CURRENTS.
 250.6
  
 57) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AND
 LARGEST MOTOR LOADS AT 125% ON EACH PANEL AND THEN FOR
 THE SERVICE LOADS.
 230.42, 215.3 ETC.
 PLEASE SHOW IN LOAD CALCULATIONS.
  
 58) NOTE: PLEASE SEE THE FEEDERS TO PANEL *HA* ARE ONLY
 RATED FOR 100AMPS, AND THESE ARE ON A 150AMP BREAKER
 FOR OVER CURRENT PROTECTION.
 PLEASE SEE 240.4 AND 310.16 (SHOWN AS ALUM).
  
 59) NOTE: PLEASE SEE THE FEEDERS TO PANEL *P* AS THESE
 ARE SHOWN AS 100AMP RATED FEEDERS ON OVER CURRENT
 PROTECTION WHICH IS HIGHER AT 150AMPS.
 PLEASE CORRELATE AND ADJUST PER 240.4, 310.16. (SHOWN
 AS ALUM, EVEN AS COPPER AND #1, THESE WOULD NOT BE OF
 SUFFICIENT SIZE).
  
 60) NOTE: PLEASE KNOW THAT MANY LOCATIONS MAY HAVE BEEN
 REDLINED ON ONE SET OF THE PLANS, HOWEVER PLEASE DO NOT
 RELY ON THESE MARK UPS FOR ALL LOCATIONS OR
 CORRECTIONS.
 PLEASE BE SURE TO GO OVER PLANS IN DETAIL AS THERE MAY
 BE ITEMS NOT YET IDENTIFIED.
  
 NOTE ADDED 3/29
  
 61) NOTE: PLEASE SEE 422.13 AS THE LOADS FOR STORAGE
 TYPE WATER HEATERS SHALL BE SHOWN AND FIGURED AT 125%.
 PLEASE SEE THIS CHANGE IN THE 2005 NEC.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-21 19:57:532007-03-21 19:57:53
 REVIEW TO CONTINUE AND BE COMPLETE ON 3/22/07 NOTES TO
 FOLLOW AS PLANS WILL BE GOING TO A *F* STATUS.
2007-03-12 07:47:34REVIEW CONTINUED
2007-03-11 13:21:55ONE ROLL AND SUBMITTALS IN ELEC FOR REVIEW.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved