| 2007-03-22 19:47:31 | 2007-03-22 19:47:31 |
| | |
| | ****** UNSAT ****** |
| | |
| | |
| | *** DATURA & OLIVE *** |
| | |
| | ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT BEEN |
| | SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE NEXT REVIEW. |
| | |
| | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | 2003 NFPA-20 |
| | 2002 NFPA-110 |
| | ** SOME OP THESE CODES MAY BE PRESENT ON PLANS HOWEVER |
| | PLEASE SEE PLANS FOR ELECTRICAL AS THERE ARE SEVERAL |
| | CODE SECTIONS WHICH ARE REFLECTED ON PLANS FROM THE |
| | PREVIOUS CODES AND ANY NEW CODE SECTIONS SHOULD BE |
| | REFLECTED. |
| | |
| | 2) NOTE: PLEASE SEE THE ARCHITECTURAL FIRM TITLE BLOCKS |
| | ARE MISSING INFORMATION AS REQUIRED PER FLORIDA |
| | ADMINISTRATIVE CODE 61G1-16.004 AS REQUIRED UNDER |
| | FLORIDA STATUTES 481.219 |
| | |
| | 3) NOTE: PLEASE SEE LANDSCAPE PLANS WHICH CONTAIN A |
| | *RUBBER STAMP* FOR THE REQUIRED ORIGINAL SIGNATURE. |
| | THIS IN PROHIBITED UNDER FS 481.221 AND MUST BE AN |
| | ORIGINAL SIGNATURE AND DATE. |
| | |
| | 4) NOTE: PLEASE SEE THE SHEETS WHICH ARE DONE BY STEVEN |
| | FELLER SHALL CONTAIN THE LEGAL SIGNATURE OF THE |
| | INDIVIDUAL AS RECOGNIZED, ON FILE, AND ON RECORD BY |
| | THIS OFFICE. PLEASE SEE FS 471.025 AND FAC 61G15-23.002 |
| | WHICH REQUIRES ALL DOCUMENTS TO CONTAIN THE ORIGINAL |
| | SIGNATURE, DATE AND SEAL. |
| | PLEASE SEE OTHER DOCUMENTS SUBMITTED AS THESE ARE ALSO |
| | NOT SIGNED WITH SIGNATURE FROM THE ENGINEER OF RECORD |
| | KNOWN TO THIS OFFICE. |
| | PLEASE KNOW THAT THIS OFFICE HAS GIVEN NOTICE ON |
| | SEVERAL OCCASIONS FOR THIS SAME ISSUE AND PLANS MAY BE |
| | RETAINED BY THIS OFFICE FOR REVIEW FROM THE FLORIDA |
| | BOARD OF PROFESSIONAL ENGINEERS. |
| | |
| | 5) NOTE: PLEASE KNOW THAT ALL PLANS SHALL CONTAIN |
| | ORIGINAL SIGNATURES, DATES AND RAISED SEALS FROM ALL |
| | DESIGN PROFESSIONALS. PLEASE SEE THE ARCHITECTURAL |
| | SHEETS SEEMED TO BE *SIGNED* WITH INITIALS, AND ARE NOT |
| | DATED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE |
| | DESIGN PROFESSIONAL, PLEASE SUBMIT A SIGNED, DATED AND |
| | SEALED LETTER FOR SIGNATURE VERIFICATION. (FS 471.025, |
| | 481.221) THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR |
| | FUTURE REFERENCE. |
| | PLEASE BE SURE LETTER IS PROPERLY NOTARIZED PER FS |
| | 117.05 FOR NOTARIES. |
| | |
| | 6) NOTE: PLEASE SEE FBC 2004 W/ 2006 FOR THE FLORIDA |
| | ENERGY CODE AND RELEVANT CODES FOR THIS BUILDING. |
| | PLEASE SEE THERE ARE AREAS WHICH DO NOT SHOW LIGHTING |
| | CONTROLS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2 AND |
| | .1.3. |
| | PLEASE SEE THAT THE ENERGY CALCULATIONS DO NOT INDICATE |
| | AUTOMATED CONTROLS FOR LIGHTING. SHOWS MANUAL ON/OFF |
| | FOR CONTROL METHODS. |
| | PLEASE SEE 13-415.2 FOR PERFORMANCE OF INTERIOR |
| | LIGHTING. |
| | PLEASE PROVIDE INFORMATION IN DETAIL FOR THIS. PLEASE |
| | SEE THE LIGHTING SHOWN ON PLANS DOES NOT CORRELATE WITH |
| | THE ENERGY CALCULATIONS. |
| | PLEASE SEE ALL OF THE REVISED CHAPTER 13 ITEMS ALONG |
| | WITH THE EXISTING IN THE 2004. |
| | |
| | 7) NOTE: PLEASE SEE THAT THE MAIN ELECTRICAL ROOM AND |
| | ELECTRICAL EQUIPMENT LOCATED IN THE GENERATOR ROOM |
| | SHALL BE GONE OVER WITH THE FIRE MARSHAL'S OFFICE. |
| | PLEASE SEE AT THIS TIME, DIRECT ACCESS TO THE MAIN |
| | ELECTRICAL ROOM THROUGH ANY RATED CORRIDOR, OR DIRECT |
| | DOOR ACCESS IS NOT SHOWN AT THIS TIME AND FURTHER |
| | REVIEW WILL BE NEEDED. PLEASE SEE THE LOCATION OF THE |
| | EDP WILL ALSO BE NOTED IN LATER NOTES FOR THE LOCATION |
| | OF CONTROL OF EM LOADS IN THE EVENT OF AN EMERGENCY. |
| | ACCESS AND LOCATION OF THIS EQUIPMENT SHOULD BE |
| | CONSIDERED AS DURING AN EVENT; ANY FIRE DEPARTMENT |
| | PERSONNEL MUST ACCESS ROOM AND CONTROL EQUIPMENT WHILE |
| | THE GENERATOR IS RUNNING AT CAPACITY. THE NOISE, |
| | LOCATION, HEAT, FUEL AND DISTRACTIONS COULD CREATE A |
| | HAZARD TO THESE PERSONS AND NOT BEING ABLE TO CONTROL |
| | ITEMS IN ORDER ETC. PLEASE CALL TO GO OVER THESE |
| | LOCATIONS ONCE ALL REVIEWS ARE DONE. THIS OFFICE WILL |
| | CONSULT WITH THE FM OFFICE AT A LATER DATE. NFPA-110 |
| | 7.2 |
| | |
| | 8) NOTE: PLEASE SUBMIT THE MANUFACTURE'S SPECS/CUT |
| | SHEETS FOR THE FOLLOWING.FIRE PUMP, FIRE PUMP |
| | CONTROLLER, GENERATOR, ATS, FUEL TANK(S). |
| | PLEASE KNOW ANY OTHER EQUIPMENT SPECS MAY BE REQUESTED |
| | FROM OTHER TRADES. |
| | 110.3, 90.7. |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE SEE THE FOLLOWING LOCATIONS SHALL |
| | CONTAIN EMERGENCY BATTERY BACK UP LIGHTS OF SOME KIND. |
| | |
| | GENERATOR ROOM (TO A LEVEL OF 30FT CANDLES), FIRE |
| | COMMAND ROOM, MAIN ELECTRICAL ROOM, METER CENTER ROOMS, |
| | ELEVATOR EQUIPMENT ROOM(S). |
| | PLEASE SEE NEXT NOTE WITH RESPECT TO STAIRS.NFPA-70 |
| | 110.26, 700.16, 700.12E, NFPA-110 7.3, NFPA-20 5.12.3, |
| | AND .4, NFPA-72 CHAPTER 2 FOR FCRM. |
| | |
| | 10) NOTE: PLEASE SEE THE STAIRS AS ONE OF THE LIGHTING |
| | FIXTURES ON EACH LEVEL WILL BE REQUIRED TO CONTAIN A |
| | BATTERY BACK UP FIXTURE OF SOME TYPE. PLEASE ALSO |
| | PROVIDE THE MINIMUM PHOTO-METRICS FOR STAIRS UNDER |
| | NORMAL AND UNDER EMERGENCY CONDITIONS. |
| | PLEASE SEE NFPA-101, 7.8., 7.9 |
| | |
| | 11 NOTE: PLEASE PROVIDE NOTES FOR FAIL SAFE OPERATION |
| | OF GATES/DOORS WHICH MAY NOT INTERFERE WITH EGRESS IN |
| | THE EVENT OF POWER FAILURE. |
| | PLEASE SEE NFPA-101 CHAPTER 7, 7.1.9,7.2.1.5. |
| | |
| | 12) NOTE: PLEASE SEE DOORS ON WEST WALL WHICH SEEM TO |
| | SWING IN PATH OF EGRESS. PLEASE ALSO VERIFY THE MAKE UP |
| | AIR, AND/OR EXHAUST ALONG THIS SAME AREA OF EGRESS. |
| | PLEASE SEE THAT THIS MAY ALSO BE IN THE COMMENTS FROM |
| | OTHER TRADES. |
| | PLEASE VERIFY WITH ALL TRADES AND REVIEWER(S). |
| | FBC 106.1.2 |
| | |
| | 13) NOTE: PLEASE PLACE A SCHEDULE/ LIST FOR ALL |
| | COMPONENTS IN THE FIRE COMMAND ROOM AS REQUIRED PER |
| | NFPA-101 11.8.5 |
| | |
| | 14) NOTE: PLEASE PROVIDE INFORMATION ON CAR LIFTS AND |
| | BE SURE EQUIPMENT INDICATES LISTING ON EQUIPMENT FROM A |
| | NRTL. |
| | 110.3, 90.7 |
| | |
| | 15) NOTE: PLEASE BE SURE ALL DEVICE AND LEVELS FOR |
| | HORNS AND STROBES MEET FBC ADA 11-4.28, .1, .2 AND |
| | .3(4). |
| | |
| | 16) NOTE: PLEASE PROVIDE ELEVATIONS FOR THE EPSS SYSTEM |
| | WHICH MUST MEET THE ELEVATIONS AS SET-FORTH ON THE |
| | 100YEAR STORM SURGE CHARTS OR *SLOSH* CHARTS PER |
| | CHAPTER 7, 7.3.1 NFPA-110. |
| | |
| | 17) NOTE: PLEASE PROVIDE INFORMATION ON FUEL |
| | CONSUMPTION ON GENERATOR FOR 100% LOAD OF THE FIRE PUMP |
| | AND ALL EMERGENCY SYSTEMS PER 700 AND 701. |
| | PLEASE SEE NFPA-110, NFPA-20 9.6.2.2 |
| | |
| | 18) NOTE: PLEASE SEE THE NEW FLORIDA STATE STATUTES |
| | WITH RESPECT TO THE NEW HOUSE BILL 7121 WHICH WAS |
| | SIGNED INTO LAW JULY OF 07. |
| | PLEASE SEE THERE ARE SEVERAL STATUTES WHICH WERE |
| | AFFECTED. PLEASE SEE THAT A INDUSTRY BULLETIN IS BEING |
| | PLACED IN WITH THE REVIEW NOTES AS ADDITIONAL |
| | INFORMATION. |
| | *ONCE THIS INFORMATION IS READ AND STATUTES REVIEWED, |
| | PLEASE PROVIDE ALL INFORMATION AS REQUIRED ON PLANS AND |
| | DOCUMENTATION FOR REVIEW. |
| | PLEASE KNOW THAT SOME OF THIS INFORMATION WILL ALSO BE |
| | NEEDED BY THE FIRE MARSHAL, STATE BOARD FOR ELEVATORS |
| | ETC. |
| | |
| | 19) NOTE: PLEASE BE SURE THE FOLLOWING STATEMENT IS |
| | PLACED ON PLANS AS REQUIRED PER FBC 109.3.6.4.4 PLEASE |
| | SEE A STATEMENT OF SIMILAR WORDING IS ALREADY ON THE |
| | LIFE SAFETY PLANS. |
| | " TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE BUILDING CODES AND THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER |
| | 633, FLORIDA STATUTES" |
| | |
| | 20) NOTE: PLEASE SEE PART OF FIRE PUMP FEEDS FROM FPL |
| | APPEARS TO BE ROUTED THROUGH ONE OF THE CORRIDORS ON |
| | SHEET E1.01. PLEASE CLARIFY THIS AS THE RISER DOES NOT |
| | SHOW DETAIL FOR THIS. |
| | PLEASE SEE 695.6A. |
| | |
| | 21) NOTE: PLEASE PROVIDE THE NORMAL AND EMERGENCY |
| | PHOTO-METRICS FOR ALL EGRESS PATHS. PLEASE KNOW THIS |
| | WOULD ALSO INCLUDE POOL DECK AREAS. ETC |
| | LS 101 7.8, 7.9 |
| | FBC 106.1.2 |
| | |
| | 22) NOTE: PLEASE PROVIDE NOTE FOR POOL AREA LIGHTS: |
| | LIGHTING SHALL BE INSTALLED A MINIMUM OF 5FT FROM |
| | WATERS EDGE FOR 120V W/GFI PROTECTION AND A MINIMUM OF |
| | 10FTFOR LOW VOLTAGE TYPE FIXTURES. (WORDS TO THIS |
| | AFFECT) |
| | 680.22, 411.4B |
| | |
| | 23) NOTE: PLEASE PROVIDE NOTE FOR POOL AREA AND THE |
| | EQUAL-POTENTIAL BONDING GRID WHICH IS REQUIRED PER |
| | 680.26. PLEASE KNOW THE POOL PERMIT WILL BE UNDER A |
| | SEPARATE PERMIT, HOWEVER AS THE STRUCTURAL ELEMENTS |
| | MOST LIKELY WILL BE IN PLACE BEFORE PERMITTING OF POOL, |
| | PLEASE INCLUDE NOTE AT THIS TIME. |
| | |
| | 24) NOTE: PLEASE INCLUDE NOTE FOR ANY LIGHTNING |
| | PROTECTION SYSTEMS SHALL MEET NFPA-780. (EVEN WHEN |
| | PERMITTED SEPARATELY OR IF A SYSTEM IS NOT GOING TO BE |
| | INSTALLED AT THIS TIME). |
| | |
| | 25) NOTE: PLEASE PROVIDE WIND LOADS AND INFORMATION FOR |
| | SITE/ROOF TOP POLES WHICH ARE REQUIRED TO MEET FBC |
| | 140MPH. |
| | THIS WILL BE REVIEWED ONCE SUBMITTED BY THE STRUCTURAL |
| | REVIEWER. PLEASE KNOW THE EFFECTIVE PROJECTED AREA |
| | (EFA) OF FIXTURE. |
| | FBC 106.1.2 |
| | |
| | 26) NOTE: PLEASE PROVIDE NOTE FOR NO NIGHT-TIME OR DUSK |
| | TO DAWN SWIMMING PERMITTED UNLESS THE INTENT IS THAT |
| | NIGHT-TIME SWIMMING WILL BE ALLOWED. IF THIS IS THE |
| | CASE PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR POOL AREA |
| | WHICH WILL BE REQUIRED TO BE STAMPED BY THE PALM BEACH |
| | COUNTY HEALTH DEPARTMENT. |
| | FBC 106.1.2 |
| | |
| | 27) NOTE: PLEASE BE SURE TO PROVIDE ALL ROOM AND AREA |
| | DESIGNATIONS ON PLANS. PLEASE KNOW SOME AREA |
| | DESIGNATIONS ARE NEEDED TO DETERMINE ARE USE AND REVIEW |
| | FOR CIRCUITING CODE COMPLIANCE AND USE. |
| | FBC 106.1.2 |
| | |
| | 28) NOTE: PLEASE PROVIDE MORE INFORMATION FOR ELEVATOR |
| | ROOMSAND THE DEDICATE CIRCUITS REQUIRED PER 620.22, |
| | 23 AND 24. SOME OF THESE ARE SHOWN ON PLANS, HOWEVER |
| | NOT ALL. |
| | PLEASE SEE COMMENT #9 ABOVE WITH RESPECT TO LIGHTING |
| | REQUIRED. PLEASE ALSO SEE THAT THE ROOF TOP APPEARS TO |
| | SHOW ANOTHER AREA WHICH CONTAINS MAINS FOR EACH OF THE |
| | ELEVATORS, YET THE PLANS DO NOT APPEAR TO SHOW ANY ROOM |
| | FOR EQUIPMENT?? PLEASE CLARIFY THIS AREA AS REDLINED ON |
| | PLANS. IF THERE IS A SECOND ROOM, PLEASE PROVIDE |
| | INFORMATION AND ELECTRICAL AS REQUIRED FOR ROOM. FBC |
| | 106.1.2 |
| | |
| | 29) NOTE: PLEASE PROVIDE COMPLETE DE-RATING |
| | CALCULATIONS FOR CONDUITS AND FEEDERS BEING RUN ACROSS |
| | ROOF-TOP AREA. PLEASE KNOW THE TYPE OF ROOF ALONG WITH |
| | OTHER FACTORS WILL HAVE AN AFFECT ON THE TEMPERATURE. |
| | PLEASE SEE NEC 310.16, TABLES FOR DE-RATING AND THE |
| | NUMBER OF CURRENT CARRYING CONDUCTORS. |
| | THE FEEDERS AS SHOWN ON RISER AND PANELS FEEDING THESE |
| | OTHER PANELS ARE NOT OF SUFFICIENT SIZE AS SHOWN ON |
| | PLANS. |
| | PLEASE ADJUST. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | NEC 215.5, 215.3 ETC |
| | |
| | 30) NOTE: PLEASE PROVIDE VOLTAGE DROP FOR THE SAME |
| | FEEDERS AS NOTED IN NOTE #29. |
| | PLEASE SEE FBC 13-413.ABC.1 |
| | PLEASE ALSO PROVIDE WORST CASE VOLTAGE DROP FOR BRANCH |
| | CIRCUITS AND FEEDERS AS ON PLANS FOR LONGEST RUNS. |
| | |
| | 31) NOTE: PLEASE SEE NFPA-72, FBC FOR THE DEFINITIONS |
| | OF SMOKE DEVICES. PLEASE DETERMINE IF THESE ARE INDEED |
| | DEVICES WHICH ONLY DETECT AND DO NOT SOUND. |
| | IF DEVICES DETECT AND ONLY PROVIDE SIGNALING TO |
| | HORN/SIREN DEVICES THEN THESE WOULD BE SD/ SMOKE |
| | DETECTORS. |
| | IF DEVICES ARE 120V BATTERY BACK AS SHOWN ON PLANS |
| | WHICH DETECT AND SOUND, THEN THESE DEVICES WOULD BE |
| | CONSIDERED SA/ SMOKE ALARMS. |
| | PLEASE ADJUST PLANS. |
| | NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | 32) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING GFI |
| | RECEPTACLES ON SOME PENINSULAS IN KITCHENS PER |
| | 210.52C1-5. PLEASE SEE LOCATION OF SOME DO NOT SEEM TO |
| | MEET THE DISTANCE PERMITTED. |
| | PLEASE SEE UNIT #4, #5 WHICH SHOW MORE THAN 6INCH |
| | OVERHANG. |
| | PLEASE SEE THAT THERE ARE OTHER UNITS WHICH ARE ALSO |
| | MISSING SOME COVERAGE PER ABOVE. PLEASE GO OVER PLANS |
| | AND SEE REDLINED PLANS FOR SOME OF THESE WHICH MAY BE |
| | MARKED ON REVIEWED SET. |
| | |
| | 33) NOTE: PLEASE SEE SOME UNITS WHICH DO NOT APPEAR TO |
| | SHOW ANY LIGHTING FIXTURE IN BEDROOMS. PLEASE SEE |
| | 210.70, LS 7.8 WHICH WILL REQUIRE A LIGHT FIXTURE IF |
| | SOME SORT INSTALLED FOR FINAL. |
| | |
| | 34) NOTE: PLEASE SEE UNIT #5, AS THE CLOSET IN |
| | DEN/BEDROOM #3 SEEMS TO SHOW A GFI IN CLOSET? PLEASE |
| | CLARIFY. |
| | FBC 106.1.2 |
| | |
| | 35) NOTE: PLEASE INCLUDE NOTE ON PLANS FOR PLACEMENT OF |
| | SA/SD DEVICES PER NFPA-72 2002 11.5.1.1, 11.8.3 |
| | |
| | 36) NOTE: PLEASE SEE UNIT #6 WHICH APPEARS TO SHOW A |
| | FLOOR BOX IN THE DOORWAY WHICH IS A TRIPPING HAZARD. |
| | PLEASE SEE 210.52 FOR LOCATIONS WHICH ARE PROHIBITED. |
| | |
| | 37) NOTE: PLEASE SEE 210.52D AS THE GFI RECEPTACLE IN |
| | BATHROOMS ARE REQUIRED TO CONTAIN THE DEVICE WITHIN 3FT |
| | OF THE SINK EDGE. PLEASE KNOW THAT THE CROSSING OVER |
| | ONE SINK TO REACH THE DEVICE ON THE OTHER SIDE IS NOT |
| | PERMITTED. PLEASE EITHER ADD A DEVICE OR RELOCATE. |
| | PLEASE SEE UNIT #7 FOR EXAMPLE. THIS IS NOT AN ISSUE IN |
| | ALL UNITS. |
| | |
| | 38) NOTE: PLEASE SEE THAT ARC FAULT IS REQUIRED FOR ALL |
| | OUTLETS INCLUDINGRECETPS, LTS, FANS AND SMOKE |
| | ALARMS. |
| | PLEASE SEE 210.12. |
| | |
| | 39) NOTE: PLEASE SEE UNIT H FOR 10FT OF HALLWAY PER |
| | 210.52H |
| | |
| | 40) NOTE: PLEASE SEE SOME WALLS/UNITS MISSING |
| | RECEPTACLES FOR WALL SPACES.UNITS L-9, 9,PLEASE SEE |
| | 210.52. EXAMPLE FOR SOME ARE REDLINED ON PLANS. |
| | |
| | 41) NOTE: PLEASE SEE UNIT L-8 WHICH PANEL SCHEDULE |
| | CALLS CIRCUIT #23 AS A BEDROOM. THIS IS NOT CLEAR AS |
| | THE ROOM IS APPROXIMATELY 6FT BY 10FT AND IS RIGHT OFF |
| | THE DINING/ KITCHEN AREA WITH NO DOOR? |
| | PLEASE CLARIFY THIS. |
| | |
| | 42) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE PANEL SCHEDULES AND OTHER CIRCUITS |
| | ON PLANS. |
| | PLEASE SEE THAT MOST OF THE CIRCUITS ARE SHOWN HOWEVER |
| | SEE REDLINED PLANS AND SEE 9, L8, L9 FOR SOME |
| | EXAMPLES. |
| | 408.4, 310.16, 240.4. |
| | FBC 106.1.2 |
| | |
| | 43) NOTE: PLEASE PROVIDE NOTES ON ELECTRICAL ROOMS/FIRE |
| | COMMAND ROOMS SHEETS ALONG WITH THE RISER SHEETS FOR |
| | REQUIREMENTS FOR SIGNAGE FOR ALL SERVICES, MAINS, |
| | LOCATIONS. |
| | 230.2E, 700.8, 701.9 ETC |
| | |
| | 44) NOTE: PLEASE BE SURE TO CORRELATE LABELING OF ALL |
| | UNITS ON RISER WITH PANELS. PLEASE PROVIDE THE OCP FOR |
| | EACH UNIT ON METER SCHEDULE OR SCHEDULE OF SOME KIND |
| | FOR EACH. |
| | NEED FOR REVIEW OF CODE COMPLIANCE FOR EACH UNIT |
| | FEEDERS ETC |
| | 215.5, 240.4, |
| | FBC 106.3.5.1.2 |
| | |
| | 45) NOTE: PLEASE SEE THAT THE EDP WILL REQUIRE A MCB AS |
| | THE POWER BEING SHUT OFF FROM THE GENERATOR CAN NOT BE |
| | VERIFIED. PLEASE KNOW THAT THE DISCONNECTING MEANS |
| | SHALL BE READILY ACCESSIBLE WITHOUT EXPOSING ANY |
| | PERSONS TO LIVE PARTS. 110.27. |
| | 230.70, 701, 700 ETC. |
| | ADDITIONAL INFORMATION IS NEEDED, AND PLEASE KNOW ONE |
| | CONSULTATION IS DONE BY THIS OFFICE WITH THE FIRE |
| | MARSHAL FOR LOCATION OF SAID EQUIPMENT SHUT DOWN/EDP |
| | THEN THIS CAN BE GONE OVER WITH THE ENGINEERS/DESIGNERS |
| | OF PROJECT. |
| | |
| | 46) NOTE: PLEASE PROVIDE ALL GENERATOR, ATS, FIRE PUMP, |
| | FIRE PUMP CONTROLLER ON PLANS. |
| | FBC 106.3.5.1.2 |
| | |
| | 47) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS |
| | FOR THE FIRE PUMP ARE SHOWN RATED FOR 205AMPS, YET THE |
| | LOAD IS SHOWN HIGHER AT 221 AMPS. PLEASE SEE 430.50, |
| | AND SIZING OF THE CONDUCTORS WHICH ARE REQUIRED TO BE |
| | @125%. |
| | 430.22, 230.208, 240.4, 310.16 ETC. |
| | PLEASE SEE THE CONDUCTORS FROM THE GENERATOR ARE SIZE |
| | FOR MORE THAN ONE RUN OF THE SAME SIZE CONDUCTORS. |
| | |
| | 48) NOTE: PLEASE SEE JUST BELOW THE LOAD SUMMARY ON |
| | SHEET 4.01 WHICH CONTAINS AN *AND MAG ONLY CB. PLEASE |
| | SEE THE LOAD SUMMARY DOES NOT INDICATE ANY * ON ANY OF |
| | THE ITEMS ABOVE THIS NOTE. |
| | PLEASE CLARIFY THIS NOTE. |
| | FBC 106.1.2 |
| | |
| | 49) NOTE: PLEASE SEE THE MAIN #5 FOR ONE 100AMP RETAIL |
| | SERVICE IS NOT BEING PERMITTED AT THIS TIME UNDER THE |
| | EXCEPTIONS OF 230.2. |
| | PLEASE KNOW THAT THIS SINGLE TENANT FEED WILL BE |
| | REQUIRED TO COME FROM WHAT IS MAIN #6 AT THIS TIME |
| | WHICH WILL BE REQUIRED TO BECOME MAIN #5 FOR RETAIL. |
| | PLEASE SEE THE FOLLOWING COMMENT WITH RESPECT TO WHAT |
| | IS BEING SHOWN NOW FOR MAIN 6. |
| | |
| | 50) NOTE: PLEASE SEE RISER WHICH CURRENTLY SHOWS MAIN |
| | #6 AS BEING FUTURE HOWEVER THE RISER SHOWS CONDUITS AND |
| | SERVICE ENTRANCE CONDUCTORS BEING INSTALLED AT THIS |
| | TIME? PLEASE KNOW THAT ALL EQUIPMENT MUST BE INSTALLED |
| | IN ITS COMPLETENESS IN ORDER FOR THE CONDUCTORS TO BE |
| | TERMINATED IN REQUIRED FASHION. |
| | PLEASE SEE RISER WHICH ACTUALLY SHOWS THE GUTTER BEING |
| | INSTALLED AT THIS TIME? HOW IS THIS POSSIBLE? PLEASE |
| | SEE THAT THE MAIN WHICH IS SHOWN IN THE MAIN ELECTRICAL |
| | ROOM NEXT TO THE EMERGENCY MAIN WILL NOT BE PERMITTED. |
| | THIS MAIN #6 WHICH WILL BECOME MAIN #5 WILL BE REQUIRED |
| | TO BE MOVED/RELOCATED. |
| | PLEASE ALSO SEE THE SCHEDULE FOR THIS RDP SHOWS THIS A |
| | BEING A MLO PANEL?? |
| | PLEASE SEE ELECTRICAL PLANS INDICATE A MAIN? PLEASE |
| | ALSO KNOW A MAIN WILL BE REQUIRED TO GRANT THE |
| | ADDITIONAL SERVICE AS SHOWN. |
| | PLEASE SEE 230.70, 230.71, 230.72, 230.2. |
| | PLEASE KNOW IF THIS SERVICE IS GOING TO BE INSTALLED |
| | AND DEPENDING TO WHAT POINT THE EQUIPMENT WILL BE |
| | INSTALLED AT THIS TIME WILL DETERMINE WHAT WILL BE |
| | REQUIRED TO BE SHOWN. PLEASE KNOW IT APPEARS THE MAIN, |
| | AND GUTTER AT A MINIMUM WILL BE REQUIRED AT THIS TIME. |
| | PLEASE KNOW IF THIS IS THE CASE, PLEASE INCLUDE THE |
| | CONDUCTORS FROM THIS MAIN TO GUTTER. 310.16, 240.4, |
| | 250.110, 250.122, 250.24B ETC. |
| | ** PLEASE KNOW THAT THERE ARE MANY ITEMS WHICH MAY NOT |
| | BE KNOWN AT THIS TIME DUE TO CHANGES IN SERVICE(S) FROM |
| | NOTES #49 AND #50. |
| | |
| | 51) NOTE: PLEASE PROVIDE MORE INFORMATION ON WHICH |
| | CONDUCTORS ARE GOING TO BE COPPER. PLEASE SEE NOTE ON |
| | PANEL PLANS MENTIONS ALL CONDUCTORS ARE GOING TO BE |
| | ALUMINUM UNLESS OTHER WISE NOTED, YET THE FOLLOWING |
| | NOTE MENTIONS ALL GROUNDS TO BE COPPER? PLEASE CLARIFY |
| | WHAT CONDUCTORS ARE GOING TO BE COPPER AND ALUM. PLEASE |
| | KNOW AT THAT NO GROUNDING ELECTRODE SYSTEMS OR |
| | CONDUCTORS TO THIS SYSTEM WILL BE PERMITTED TO BE |
| | ALUM. |
| | PLEASE SEE 110.3, 90.4 |
| | |
| | 52) NOTE: PLEASE SEE THAT THE RISER SHEET CONTAIN A |
| | NOTE #1 AT THE GENERATOR WHICH POINTS TO THE BASE OF |
| | THE UNIT, HOWEVER THE NOTE #1 IS FOR VERTICAL SUPPORT |
| | OF CONDUCTORS? |
| | PLEASE COORDINATE. |
| | FBC106.1.2 |
| | |
| | 53) NOTE: PLEASE INDICATE AMPERAGE ON METER CENTERS AND |
| | FOR OVER CURRENT PROTECTION TO UNITS. |
| | 240.4, 310.16, 230.94 ETC. |
| | FBC 106.1.2 |
| | |
| | 54) NOTE: PLEASE SEE LOAD CALCULATIONS AND THE SECTION |
| | OF THE CODES IN DIFFERENT PLACES WHICH ARE FROM THE |
| | PREVIOUS CODE. PLEASE SEE THE 2005 NEC AND UPDATE CODE |
| | SECTIONS. |
| | FBC 106.1.2 |
| | |
| | 55) NOTE: PLEASE SEE THE CONDUCTORS WHICH ARE SHOWN |
| | GOING TO WHAT IS NOW BEING SHOWN AS MAIN #6 IS ONLY |
| | RATED FOR 1000 AMPS, YET THIS EQUIPMENT WILL HAVE A |
| | MAIN OF 1200AMPS OR MORE. |
| | PLEASE SEE 240.4C FOR DEVICES RATED OVER 800AMPS. |
| | |
| | 56) NOTE: PLEASE KNOW AS NOTICE FOR FUTURE RETAIL |
| | TENANT METERS, AS THESE WILL BE REQUIRED TO CONTAIN |
| | *FLOATING NEUTRAL KITS* AS THE BONDING WILL BE DONE AT |
| | THE FIRST MEANS OF DISCONNECT PER 250.24B AND THE |
| | EQUIPMENT GROUNDING WILL BE FOLLOW. |
| | PLEASE KNOW THAT THE NEUTRALS AND EQUIPMENT GROUNDING |
| | WILL BE REQUIRED TO BE SEPARATED TO AVOID OBJECTIONABLE |
| | CURRENTS. |
| | 250.6 |
| | |
| | 57) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AND |
| | LARGEST MOTOR LOADS AT 125% ON EACH PANEL AND THEN FOR |
| | THE SERVICE LOADS. |
| | 230.42, 215.3 ETC. |
| | PLEASE SHOW IN LOAD CALCULATIONS. |
| | |
| | 58) NOTE: PLEASE SEE THE FEEDERS TO PANEL *HA* ARE ONLY |
| | RATED FOR 100AMPS, AND THESE ARE ON A 150AMP BREAKER |
| | FOR OVER CURRENT PROTECTION. |
| | PLEASE SEE 240.4 AND 310.16 (SHOWN AS ALUM). |
| | |
| | 59) NOTE: PLEASE SEE THE FEEDERS TO PANEL *P* AS THESE |
| | ARE SHOWN AS 100AMP RATED FEEDERS ON OVER CURRENT |
| | PROTECTION WHICH IS HIGHER AT 150AMPS. |
| | PLEASE CORRELATE AND ADJUST PER 240.4, 310.16. (SHOWN |
| | AS ALUM, EVEN AS COPPER AND #1, THESE WOULD NOT BE OF |
| | SUFFICIENT SIZE). |
| | |
| | 60) NOTE: PLEASE KNOW THAT MANY LOCATIONS MAY HAVE BEEN |
| | REDLINED ON ONE SET OF THE PLANS, HOWEVER PLEASE DO NOT |
| | RELY ON THESE MARK UPS FOR ALL LOCATIONS OR |
| | CORRECTIONS. |
| | PLEASE BE SURE TO GO OVER PLANS IN DETAIL AS THERE MAY |
| | BE ITEMS NOT YET IDENTIFIED. |
| | |
| | NOTE ADDED 3/29 |
| | |
| | 61) NOTE: PLEASE SEE 422.13 AS THE LOADS FOR STORAGE |
| | TYPE WATER HEATERS SHALL BE SHOWN AND FIGURED AT 125%. |
| | PLEASE SEE THIS CHANGE IN THE 2005 NEC. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-03-21 19:57:53 | 2007-03-21 19:57:53 |
| | REVIEW TO CONTINUE AND BE COMPLETE ON 3/22/07 NOTES TO |
| | FOLLOW AS PLANS WILL BE GOING TO A *F* STATUS. |
| 2007-03-12 07:47:34 | REVIEW CONTINUED |
| 2007-03-11 13:21:55 | ONE ROLL AND SUBMITTALS IN ELEC FOR REVIEW. |