Plan Review Notes
Plan Review Notes For Permit 07020704
Permit Number 07020704
Review Stop B
Sequence Number 2
Notes
Date Text
2007-04-18 16:34:09****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)ADDRESSED.
  
 2.)"CUSTOMER" IS SPECIFIED FOR CONNECTOR A ON THE
 CONNECTOR SCHEDULE.PLEASE SPECIFY A CONNECTOR.
 CALCULATIONS MAY BE REQUIRED.
  
 2ND REVIEW, CONNECTOR A IS STILL "CUSTOMER", CONNECTOR
 B IS A SIMPSON CONNECTOR.ENGINEER IS TO SPECIFY A
 CONNECTOR; NOT SURE WHAT "CUSTOMER" MEANS.
  
 3.)COMMENT FROM FIRST REVIEW -PLEASE SEE
 FAC61G15-23.002. DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS AND TO HAVE ALL INFORMATION REQUIRED BY
 FAC61G15-23.002 ON EACH SHEET.
  
 SOME SHEETS OUT OF THE SET ARE SEALED, NONE HAVE ALL
 INFORMATION REQUIRED.PLEASE VISIT THE FBPE.ORG
 WEBSITE TO REVIEW RULE FAC61G15-23.002 AND REVISE THE
 PLANS TO INCLUDE ALL REQUIRED INFORMATION.
  