2007-04-05 15:14:06 
  
 PROVISO
  
 THIS PERMIT IS BEING ISSUED TO
 FACILITATE THE REPAIR OF THIS BUILDING
 THE PLANS HOWEVER ARE INCOMPLETE. PLEASE
 RESUBMIT A REVISION SHOWING ACTUAL
 CONDITIONS PRIOR TO CALLING ROUGH
 ELECTRICAL INSPECTION.
 THE REVIEWED PLAN MUST BE ON THE JOB
 SITE AT TIME OF INSPECTION. ALLOW AT
 LEAST ONE WEEK (PER TRADE) FOR PLAN
 REVIEW.
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1}INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD"SWITCHES ARE
 SHOWN ON THE PLAN. THE SUBMITTALS WERE RECEIVED IN THE
 RESUB PACKAGE, BUT THE SENSORS NEED TO BE LOCATED ON
 THE PLAN.SHOW COMPLIANCE ON THE DRAWING.
  
 2} THE DISCONNECT LOCATIONS FOR THE CONDENSING UNITS DO
 NOT COMPLY WITH THE 3' CLEARANCE REQUIREMENTS OF
 110.26, NEC.
  
 3} THE UTILITY RECEPTACLE CIRCUIT (#PA-20) FOR THE
 CONDENSING UNITS WAS OMITTED FROM THE PANEL SCHEDULE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718