| Plan Review Notes For Permit 07020689 |
| Permit Number |
07020689 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-08 11:39:42 | ******DENIED***** | | | | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.COMBUSTIBLE WASTE MATERIALS SHALL BE REMOVED FROM | | | THE SITE AT THE END OF EACH SHIFT OR MORE FREQUENTLY AS | | | NECESSARY FOR SAFE OPERATION. | | | | | | 3.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE | | | OR HINDER WITH EMERGENCY RESPONSE ACCESSTO THE | | | STRUCTURE OR THE VICINITY THEREOF (INCLUDING FIRE | | | LANES). | | | | | | 4.IT IS STATED ON SHEET A2 THAT THE MEANS OF EGRESS | | | FACTORS IS/ARE BASED ON NFPA 101 - 2006, HOWEVER , NFPA | | | 101- 2003 EDITION SHALL BE REFERENCED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEM | | | 561-805-6722 |
|