Plan Review Notes
Plan Review Notes For Permit 07020689
Permit Number 07020689
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-05 13:45:41 
 DENIED/INCOMPLETE INFORMATION
  
 THIS REVIEWING IS BASED ON THE OPINION THAT ALL THE
 ELECTRICAL SYSTEMS AND EQUIPMENT ON THE PLAN IS NEW AS
 THERE IS NOTHING IN THE DESCRIPTION ON THE APPLICATION,
 OR NOTES ON THE PLAN INDICATING OTHERWISE.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 THE PANELS ARE MARKED "MLO", INDICATE THE LOCATION OF
 THE DISCONNECTING MEANS. SEE 408.36.
  
 2}PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS PER 215.5.. THE "ONE
 LINE "DIAGRAM SUBMITTED DOES NOT HAVE ENOUGH
 INFORMATION.
  
 3} GIVE AMPERE RATING FOR THE PANELS. 215.5
  
 4} THE PANEL SCHEDULES ARE LABELED "PA AND "PC", THE
 PANELS AND CIRCUITS ARE LABELED "PA" AND "PB". PLEASE
 CORRELATE.
  
 5} THE LIGHTING CIRCUIT IN SUITE 1, OFFICE 105, IS
 MISMARKED "PB-18"
  
 6} THE WATER COOLERS SHOWN IN BOTH SUITES ON SHEET E1,
 ARE NOT LISTED ON THE PANEL SCHEDULES. SEE 210.23(A)(2)
 FOR REQUIREMENTS.
  
 7} PLEASE COMPLETE NOTE #7 , OR USE AS A CONTINUATION
 OF NOTE #6.
  
 8} CONDENSER #1, CIRCUIT 5,7 AND #2, CIRCUIT 8,10,
 PANEL "PA" INDICATE A 10 AMP LOAD (2500 WATTS)
 PROTECTED BY A 60 AMP BREAKER. THIS EXCEEDS THE
 PARAMETERS OF 440.22 FOR OCP.
  
 9} THE AHU CIRCUITS IN PANEL "PA" ARE IN VIOLATION OF
 424.3(B). SEE ALSO 240.4, REFERENCED IN SAME. THE
 WATTAGE OF THESE UNITS DOES NOT CORRESPOND TO THE
 SPECIFICATIONS ON SHEET M1. PLEASE CORRELATE
  
 10} SHOW THE LOCATION REQUIRED DISCONNECTS PER 440.14,
 ANDRECEPTACLE PER 210.63 FOR THE CONDENSING UNT,
 SHEET E1.
  
 11}THE PANEL LABELED "PC", CIRCUIT PB 4,6 AT THE
 RECEPTACLE, INDICATES A 60 AMP OCP FOR A 3300 WATT A/C
 LOAD IN VIOLATION OF 240.4.
  
 12}INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.SHOW COMPLIANCE ON THE DRAWING.
  
 13} INDICATE COMPLIANCE WITH 13-415.2ABC.1, PERFORMANCE
 CALCULATION PROCEDURES. SUBMIT FORMS WITH 13-415.2B OR
 13-415.2.C.1 DENSITIES.
  
 NOTE: IF THERE ARE ANY QUESTIONS REGARDING THE
 REQUIREMENT TO COMPLY, PLEASE SEE 13.400.0.C.4, SECOND
 PARAGRAPH.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  