| 2007-03-05 13:45:41 | |
| | DENIED/INCOMPLETE INFORMATION |
| | |
| | THIS REVIEWING IS BASED ON THE OPINION THAT ALL THE |
| | ELECTRICAL SYSTEMS AND EQUIPMENT ON THE PLAN IS NEW AS |
| | THERE IS NOTHING IN THE DESCRIPTION ON THE APPLICATION, |
| | OR NOTES ON THE PLAN INDICATING OTHERWISE. |
| | |
| | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | THE PANELS ARE MARKED "MLO", INDICATE THE LOCATION OF |
| | THE DISCONNECTING MEANS. SEE 408.36. |
| | |
| | 2}PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT |
| | SIZE AND TYPE, GROUNDING DETAILS PER 215.5.. THE "ONE |
| | LINE "DIAGRAM SUBMITTED DOES NOT HAVE ENOUGH |
| | INFORMATION. |
| | |
| | 3} GIVE AMPERE RATING FOR THE PANELS. 215.5 |
| | |
| | 4} THE PANEL SCHEDULES ARE LABELED "PA AND "PC", THE |
| | PANELS AND CIRCUITS ARE LABELED "PA" AND "PB". PLEASE |
| | CORRELATE. |
| | |
| | 5} THE LIGHTING CIRCUIT IN SUITE 1, OFFICE 105, IS |
| | MISMARKED "PB-18" |
| | |
| | 6} THE WATER COOLERS SHOWN IN BOTH SUITES ON SHEET E1, |
| | ARE NOT LISTED ON THE PANEL SCHEDULES. SEE 210.23(A)(2) |
| | FOR REQUIREMENTS. |
| | |
| | 7} PLEASE COMPLETE NOTE #7 , OR USE AS A CONTINUATION |
| | OF NOTE #6. |
| | |
| | 8} CONDENSER #1, CIRCUIT 5,7 AND #2, CIRCUIT 8,10, |
| | PANEL "PA" INDICATE A 10 AMP LOAD (2500 WATTS) |
| | PROTECTED BY A 60 AMP BREAKER. THIS EXCEEDS THE |
| | PARAMETERS OF 440.22 FOR OCP. |
| | |
| | 9} THE AHU CIRCUITS IN PANEL "PA" ARE IN VIOLATION OF |
| | 424.3(B). SEE ALSO 240.4, REFERENCED IN SAME. THE |
| | WATTAGE OF THESE UNITS DOES NOT CORRESPOND TO THE |
| | SPECIFICATIONS ON SHEET M1. PLEASE CORRELATE |
| | |
| | 10} SHOW THE LOCATION REQUIRED DISCONNECTS PER 440.14, |
| | ANDRECEPTACLE PER 210.63 FOR THE CONDENSING UNT, |
| | SHEET E1. |
| | |
| | 11}THE PANEL LABELED "PC", CIRCUIT PB 4,6 AT THE |
| | RECEPTACLE, INDICATES A 60 AMP OCP FOR A 3300 WATT A/C |
| | LOAD IN VIOLATION OF 240.4. |
| | |
| | 12}INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR |
| | SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE |
| | SHOWN ON THE PLAN.SHOW COMPLIANCE ON THE DRAWING. |
| | |
| | 13} INDICATE COMPLIANCE WITH 13-415.2ABC.1, PERFORMANCE |
| | CALCULATION PROCEDURES. SUBMIT FORMS WITH 13-415.2B OR |
| | 13-415.2.C.1 DENSITIES. |
| | |
| | NOTE: IF THERE ARE ANY QUESTIONS REGARDING THE |
| | REQUIREMENT TO COMPLY, PLEASE SEE 13.400.0.C.4, SECOND |
| | PARAGRAPH. |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |
| | |