2007-02-28 11:56:37 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER108.3 FBC AS
 AMENDED. EVEN IF YOU PROVIDE LABOR AS AN OWNER/BUILDER,
 THE VALUE OF THE APPLICATION MUST BE AT THE SAME RATE A
 CONTRACTOR WOULD CHARGE. THIS IS FOR REPORT PURPOSES.
  
 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS. 215.5.
  
 3} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 4} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC
 AS AMENDED. ALSO SEE 408.4 NEC. ALL PANELS BEING
 ADDED.
  
 5} REGARDING THE RANGE AND DRYER WIRING, AN EQUIPMENT
 GROUND IS REQUIRED PER 250.134-138. 2 WIRE AND 3 WIRE
 ROMEX IS LISTED ON THE PLAN.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.