Plan Review Notes
Plan Review Notes For Permit 07020666
Permit Number 07020666
Review Stop E
Sequence Number 6
Notes
Date Text
2009-07-23 13:37:06 
 ** PROVISO **
  
 ** BEFORE INSPECTIONS. ANY INSTALLATION OF NEW FIXTURES
 ON PLANS IS AT THE RISK OF CONTRACTOR TO INSTALL IF
 FIXTURES ARE OVER ALLOWANCES.
  
 1) NOTE: AS REVISIONS HAVE BEEN SUBMITTED REVISING
 LIGHTING FIXTURES, PLEASE KNOW THAT THE PREVIOUS
 ATTACHED LIGHTING PERFORMANCE CALCULATIONS WOULD BE
 REQUIRED TO BE UPDATED.
 AN EXAMPLE IS: THE PLANS SIMPLY STATE * RECESSED
 LIGHTS*, HOWEVER RECESSED LIGHTING FIXTURES COULD BE
 25W RATED, 50W RATED OR AS MUCH AS 1500W RATED. THE
 CALCULATIONS MY NOT USE A BULB WATTAGE OR RATING IT
 MUST BE BASED ON THE RATED FIXTURE. PLEASE SEE
 13-415.2.ABC.1.1, .1.2 UNDER THE 2004 FBC W/2006
 REVISIONS.
 PLEASE CALL TO GO OVER.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717