| 2009-07-23 13:37:06 | | | | ** PROVISO ** | | | | | | ** BEFORE INSPECTIONS. ANY INSTALLATION OF NEW FIXTURES | | | ON PLANS IS AT THE RISK OF CONTRACTOR TO INSTALL IF | | | FIXTURES ARE OVER ALLOWANCES. | | | | | | 1) NOTE: AS REVISIONS HAVE BEEN SUBMITTED REVISING | | | LIGHTING FIXTURES, PLEASE KNOW THAT THE PREVIOUS | | | ATTACHED LIGHTING PERFORMANCE CALCULATIONS WOULD BE | | | REQUIRED TO BE UPDATED. | | | AN EXAMPLE IS: THE PLANS SIMPLY STATE * RECESSED | | | LIGHTS*, HOWEVER RECESSED LIGHTING FIXTURES COULD BE | | | 25W RATED, 50W RATED OR AS MUCH AS 1500W RATED. THE | | | CALCULATIONS MY NOT USE A BULB WATTAGE OR RATING IT | | | MUST BE BASED ON THE RATED FIXTURE. PLEASE SEE | | | 13-415.2.ABC.1.1, .1.2 UNDER THE 2004 FBC W/2006 | | | REVISIONS. | | | PLEASE CALL TO GO OVER. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|