| Date |
Text |
| 2007-12-24 09:28:49 | ** DENIED4TH REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OFF ADDRESSING. |
| | |
| | ** PLEASE SEE THERE ARE NOW CHANGES ONCE AGAIN TO THE |
| | RISER WHICH WAS NEW ON PREVIOUS REVIEW WHICH HAS NOW |
| | GENERATED NEW COMMENTS. |
| | |
| | 1) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS |
| | REVIEW. PLEASE SEE THERE ARE SEVERAL DEVICES/FIXTURES |
| | WITH NO CIRCUITING SHOWN. |
| | **PREVIOUS NOTE ** |
| | PLEASE COMPLETE CIRCUITING FOR ALL NEW |
| | DEVICES/CIRCUITS BEING INSTALLED. |
| | PLEASE CORRELATE WITH A PANEL SCHEDULE TO BE SUBMITTED. |
| | PLEASE INDICATE THE MINIMUM CONDUCTOR SIZES, OVER |
| | CURRENT PROTECTION FOR NEW CIRCUITS AND PANEL. PLEASE |
| | BE SURE TO SEE 700.12F FOR CIRCUITING OF EMERGENCY AND |
| | EXIT LIGHT FIXTURES. (MUST BE CIRCUITED TO THE LOCAL |
| | LIGHTING BRANCH CIRCUIT IN AREA OF FIXTURE) |
| | 240.4, 310.16, 408.4 |
| | FBC 106.3.5.1.2 |
| | |
| | 2) NOTE: PLEASE SEE RISER HAS NOW BEEN CHANGED ONCE |
| | AGAIN TO ADDRESS PREVIOUS COMMENTS HOWEVER NEW COMMENT |
| | AND EXISTING COMMENT NEEDS TO BE ADDRESSED. |
| | RISER SHOWS AN EXISTING 200AMP METER MAIN COMBO, ALONG |
| | WITH A NEW 200AMP MDP. (IS NOT THE METER/MAIN PANEL THE |
| | MDP?) |
| | THE MDP SCHEDULE SHOWS A 200AMP BREAKER TO THE EXISTING |
| | PANEL *A* YET THIS SAME MDP SHOWS FEED-THRU LUGS? |
| | PLEASE CLARIFY. |
| | PLEASE SEE THE NEW MDP SCHEDULE NOW HAS A NEW 60AMP |
| | BREAKER FEEDING NEW PANEL *B* HOWEVER THE LOAD ON PANEL |
| | *B* IS SHOWING EXCEEDING THE RATING OF THE OVER CURRENT |
| | PROTECTION DEVICE. PLEASE ALSO VERIFY THE CONDUCTORS |
| | WHICH ARE SHOWN AS #2 INTO A 60AMP BREAKER. |
| | PLEASE SEE 110.3, 90.7, 240.4, 310.16, ETC |
| | |
| | 3) NOTE: THIS COMMENT WAS FROM PREVIOUS REVIEW AND THE |
| | ONLY ITEM ADDED TO PLANS WAS A NOTE WHICH SAYS FOR |
| | LIGHTING TO MEET THE MAXIMUM LEVELS PER THE TABLE *C*. |
| | PLEASE KNOW THAT STATING THE CODE SECTION IN LIEU OF |
| | THE MINIMUM REQUIRED FOR CODE COMPLIANCE IN DESIGN MAY |
| | NOT BE USED. |
| | ** PREVIOUS NOTE** |
| | PLEASE KNOW AS PLANS APPEAR TO SHOW NEW LIGHTING BEING |
| | INSTALLED PLEASE PROVIDE LIGHTING POWER DENSITIES PER |
| | 13-415.2 |
| | ( ONLY FOR NEW). |
| | |
| | |
| | |
| | ** AS MENTIONED ON PREVIOUS REVIEW. PLEASE CALL TO GO |
| | OVER COMMENTS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2007-12-23 19:32:47 | 2007-12-23 19:32:47 |
| | IN ELEC FOR REVIEW. |