Plan Review Notes
Plan Review Notes For Permit 07020666
Permit Number 07020666
Review Stop B
Sequence Number 2
Notes
Date Text
2007-10-19 16:35:12CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON, PERMIT NO 07020666 BUILDING
 PLAN EXAMINERII PROJECT ALTERATION
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS
 801 NORTH DIXIE HIGHWAY
  DATE OCTOBER 19, 2007
  
 BUILDINGPLANREVIEW
 ARCHITECT
 FLORIDA STATUE 481.219CERTIFICATION OF
 PARTNERSHIPS, LIMITED LIABILITY COMPANIES, AND
 CORPORATIONS.
 (1)THE PRACTICE OF OR THE OFFER TO PRACTICE
 ARCHITECTURE OR INTERIOR DESIGN BY LICENSEES THROUGH A
 CORPORATION, LIMITED LIABILITY COMPANY, OR PARTNERSHIP
 OFFERING ARCHITECTURAL OR INTERIOR DESIGN SERVICES TO
 THE PUBLIC, OR BY A CORPORATION, LIMITED LIABILITY
 COMPANY, OR PARTNERSHIP OFFERING ARCHITECTURAL OR
 INTERIOR DESIGN SERVICES TO THE PUBLIC THROUGH
 LICENSEES UNDER THIS PART AS AGENTS, EMPLOYEES,
 OFFICERS, OR PARTNERS, IS PERMITTED, SUBJECT TO THE
 PROVISIONS OF THIS SECTION.
 (2)FOR THE PURPOSES OF THIS SECTION, A CERTIFICATE OF
 AUTHORIZATION SHALL BE REQUIRED FOR A CORPORATION,
 LIMITED LIABILITY COMPANY, PARTNERSHIP, OR PERSON
 PRACTICING UNDER A FICTITIOUS NAME, OFFERING
 ARCHITECTURAL SERVICES TO THE PUBLIC JOINTLY OR
 SEPARATELY. HOWEVER, WHEN AN INDIVIDUAL IS PRACTICING
 ARCHITECTURE IN HER OR HIS OWN NAME, SHE OR HE SHALL
 NOT BE REQUIRED TO BE CERTIFIED UNDER THIS SECTION.
 CERTIFICATION UNDER THIS SUBSECTION TO OFFER
 ARCHITECTURAL SERVICES SHALL INCLUDE ALL THE RIGHTS AND
 PRIVILEGES OF CERTIFICATION UNDER SUBSECTION (3) TO
 OFFER INTERIOR DESIGN SERVICES.
 (10)EACH PARTNERSHIP, LIMITED LIABILITY COMPANY, AND
 CORPORATION CERTIFIED UNDER THIS SECTION SHALL NOTIFY
 THE DEPARTMENT WITHIN 30 DAYS OF ANY CHANGE IN THE
 INFORMATION CONTAINED IN THE APPLICATION UPON WHICH THE
 CERTIFICATION IS BASED. ANY REGISTERED ARCHITECT OR
 INTERIOR DESIGNER WHO QUALIFIES THE CORPORATION,
 LIMITED LIABILITY COMPANY, OR PARTNERSHIP AS PROVIDED
 IN SUBSECTION (7) SHALL BE RESPONSIBLE FOR ENSURING
 RESPONSIBLE SUPERVISING CONTROL OF PROJECTS OF THE
 ENTITY AND UPON TERMINATION OF HER OR HIS EMPLOYMENT
 WITH A PARTNERSHIP, LIMITED LIABILITY COMPANY, OR
 CORPORATION CERTIFIED UNDER THIS SECTION SHALL NOTIFY
 THE DEPARTMENT OF THE TERMINATION WITHIN 30 DAYS.
 COMMENT-THE CORPORATION SMITH AND MOORE ARCHITECTS,
 INC.MUST BE IN COMPLIANCE WITH THIS STATUE.
 A CERTIFICATE OF AUTHORIZATION IS REQUIRED. THE ADDRESS
 OF THE CORPORATION MUST BE LISTED WITH THIS
 CERTIFICATE.
  
  
  
  
 FLORIDA ADMINISTRATIVE CODE61G1-16.002DOCUMENTS
 SIGNED AND SEALED
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL
 AND BEING FILED FOR PUBLIC RECORD SHALL HAVE THE
 SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT WITH THE DATE.
 COMMENT-
 A. THE DESIGNER OF RECORD MUST SIGN AND SEAL THE
 STOREFRONT DRAWINGS PREPARED BY SMITH AND MOORE IN
 THEIR TITLE BLOCK.THE ACCEPTANCE REQUIREMENT WILL NOT
 BE NECESSARY AS THE DESIGNER AND PREPARER ARE THE
 SAME.
 B. THE FLORIDA PRODUCT APPROVAL FOR THE PANEL WALLS,
 STORE FRONT WAS SUBMITTED UNDER THE 2001 CODE. THE CODE
 BEING USED IS THE 2004.THE NOA MIAMI-DADE PRODUCT
 APPROVAL SUBMITTED WITH THIS PACKAGE HAS THE CORRECT
 CODE.I HAVE REPLACED THE 2001 FLORIDA PRODUCT
 APPROVALPANEL WALLS, STORE FRONTWITH THE 2004
 INFORMATION.
 PLEASE REVIEW THIS PRODUCT APPROVAL AND ACKNOWLEDGE
 ACCEPTANCE, IF APPLICABLE,ON BOTH COPIES.
  
  
 C PRODUCT APPROVALS REQUIRED
 FBC 1609.1.4 AND WPB ADMINISTRATIVE CODE 106.3
 REGULATED BY DCA RULE 9B-72FLORIDA PRODUCT APPROVALS
 SUBMIT TWO COPIES OF EACH APPROVAL ( 3 COPIES IF A
 THRESHOLD BUILDING ) WITH FLORIDA PRODUCT APPROVAL
 COVER SHEET THE ARCHITECT?S / ENGINEER?S SIGNATURE AS
 APPLICABLE, STATING ?TO THE BEST OF THEIR KNOWLEDGE THE
 PRODUCT APPROVAL COMPLIES WITH THE PLANS AND
 SPECIFICATIONS.SEE:WEB SITE
 WWW.FLORIDABUILDING.COM
  
 COMMENT-ARCHITECT MUST REVIEW THE PRODUCT APPROVALS
 SUBMITTED FOR COMPLIANCE WITH THE PROJECT
 AND PROVIDE THE STATEMENT ?TO THE BEST???..)
  
  
 D PROJECT INFORMATION
 FBC2004 FLORIDA BUILDING CODE BUILDING W/ 2005
 AND 6 REVISIONS
 FBC2004 ACCESSIBILITY CHAPTER11
 FBC2004 EXISTING BUILDING LEVEL OF ALTERATION II
 TYPE OF CONSTRUCTION V
 SPRINKLED / UN-SPRINKLED UN-SPRINKLED
 BASIC WIND SPEED ? MPH 140
 WIND EXPOSURE C
 WIND IMPORTANCE FACTOR I
 INTERNAL PRESSURE COEFFICIENT SEE 1609.6.2.1 TYPE OF
 OCCUPANCY A/B
 OCCUPANT LOAD-GROSS - NET 30
 COMMENT-NOTE THE FOLLOWING INFORMATION ON THE COVER
 SHEET
  
 D-1 SUBMIT A SURVEY OF THE EXISTING BUILDING WITH ALL
 PROPERTY LINES FOR REVIEW
  
  
 E FBC 713.1 GENERAL - FIRE RESISTANT JOINT SYSTEM
 JOINTS INSTALLED IN OR BETWEEN FIRE-RESISTANCE-RATED
 WALLS, FLOOR OR FLOOR/CEILING ASSEMBLIES AND ROOFS OR
 ROOF/CEILING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE-RESISTANT JOINT SYSTEM DESIGNED TO RESIST
 THE PASSAGE OF FIRE FOR A TIME PERIOD NOT LESS THAN THE
 REQUIRED FIRE-RESISTANCE RATING OF THE WALL, FLOOR OR
 ROOF IN OR BETWEEN WHICH IT IS INSTALLED.
 FIRE-RESISTANT JOINT SYSTEMS SHALL BE TESTED IN
 ACCORDANCE WITH SECTION 713.3 . THE VOID CREATED AT THE
 INTERSECTION OF A FLOOR/CEILING ASSEMBLY AND AN
 EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 713.4 .
 COMMENT-DETAIL1-A3PLEASE PROVIDE THE SYSTEM
 THAT IS TO BE APPLIED TO THE JOINT LOCATED AT THE WALL
 ASSEMBLY CONNECTEDTO THE UNDERSIDE OF THE ROOF
  
  
  
  
 ENGINEER COMMENTS
  
 F FBC 2001 104.3 EXAMINATION OF DOCUMENTS
 104.3.1 PLAN REVIEW. THE BUILDING OFFICIAL SHALL
 EXAMINE OR CAUSE TO BE EXAMINED EACH APPLICATION FOR A
 PERMIT AND THE ACCOMPANYING DOCUMENTS, CONSISTING OF
 DRAWINGS, SPECIFICATIONS, COMPUTATIONS AND ADDITIONAL
 DATA, AND SHALL ASCERTAIN BY SUCH EXAMINATIONS WHETHER
 THE CONSTRUCTION INDICATED AND DESCRIBED IS IN
 ACCORDANCE WITH THE REQUIREMENTS OF THE TECHNICAL CODES
 AND ALL OTHER PERTINENT LAWS OR ORDINANCES. COMMENT
 PLEASE SEE INFORMATION REQUESTEDSECTION 1604.8.2
  
  
 G FBC 1604.8.2 CONCRETE AND MASONRY WALLS. CONCRETE AND
 MASONRY WALLS SHALL BE ANCHORED TO FLOORS, ROOFS AND
 OTHER STRUCTURAL ELEMENTS THAT PROVIDE LATERAL SUPPORT
 FOR THE WALL. SUCH ANCHORAGE SHALL PROVIDE A POSITIVE
 DIRECT CONNECTION CAPABLE OF RESISTING THE HORIZONTAL
 FORCES SPECIFIED IN THIS CHAPTER BUT NOT LESS THAN A
 MINIMUM STRENGTH DESIGN HORIZONTAL FORCE OF 280 PLF
 (4.10 KN/M) OF WALL, UNLESS THE LATERAL FORCE HAS
 OTHERWISE BEEN CALCULATED BY THE ENGINEER OF RECORD.
 WALLS SHALL BE DESIGNED TO RESIST BENDING BETWEEN
 ANCHORS WHERE THE ANCHOR SPACING EXCEEDS 4 FEET (1219
 MM). REQUIRED ANCHORS IN MASONRY WALLS OF HOLLOW UNITS
 OR CAVITY WALLS SHALL BE EMBEDDED IN A REINFORCED
 GROUTED STRUCTURAL ELEMENT OF THE WALL. SEE SECTIONS
 1609.6.5 FOR WIND DESIGN REQUIREMENTS. COMMENTS-SEE
 ITEMS LISTED BELOW
  
 H SHEET S-2PLACE DETAIL NUMBER OR SYMBOL AT EACH
 WINDOW AND DOOR OPENING.IDENTIFY THE ?TYPICAL?
 OPENINGS DRAWN ON SHEET S-2 ALSO WITH A NUMERICAL
 NUMBER OR SYMBOL.THIS WILL PROVIDE THE EXACT
 STRUCTURAL COMPONENT TO BE USED IN THE FIELD AND FOR
 THIS PLAN REVIEW.
  
 I SHEET S-2 IDENTIFY COLUMNS AT DETAIL 5-S1
  
 C SHEET S-2 DETAIL 2-S1PROVIDE A SECTION AS TO THE
 2? X 6?BLOCKING OR BRIDGING,
 GRADE OF LUMBER,SIZE OF EXISTING MEMBERS FOR
 ATTACHMENT, TYPE OF ATTACHMENTS, PURPOSE OF
 INSTALLATION.
  
  
 J SHEET S-2 DETAIL 2 S-1 AND 1 S-1PROVIDE
 INFORMATION AS TO THE EXTERIOR BEAM AT THIS LOCATION .
  
  
 K SHEET S-1 IDENTIFY ALL COLUMNS AND BEAMS ON THE
 PARTIAL FOUNDATION PLAN
  
  
 L SHEET S-1 IDENTIFY THE HILTI 500 SYSTEM TO BE USED
 FROM THE HILTI CHART AND NOTE ON PLAN
  
 M SHEET S-2STRUCTURAL NOTESPROVIDE THE CONCRETE
 DESIGN STRENGTH TO BE USED FOR THE FOUNDATION, BEAMS,
 COLUMNS.
 PROVIDE THE GRADE FOR THE REINFORCING STEEL
  
  
 N FBC1609.1.4 SUBMIT PRODUCT APPROVAL FOR THE
 TRUSS ANCHORS SIMPSON HG A-10
 COMMENTPLEASE FIND THE SIMPSON PRODUCT APPROVAL I
 RETRIEVED ON LINE.
 PLEASE REVIEW AND ACKNOWLEDGE ACCEPTANCE
  
  
  
 PLAN REVIEWER?S PREVIOUS COMMENTS ON 3/29/07NOT
 ADDRESSED
  
 4) DESIGN INFORMATION NOT COMPLETE
 COMMENTS-SEE THIS PLAN REVIEWER?S COMMENTD
  
 8) NEGATIVE AND POSITIVE DESIGN PRESSURES ARE TO BE PUT
 ON SHEET A-2ELEVATIONS
  
 9) WHERE IS THE PROPERTY LINES?
 COMMENTS-SEE THIS PLAN REVIEWER?S COMMENTD-1
  
 10) FLEXIBLE JOINT AT THE ROOF LINE OF THE TENANT
 SEPARATION WALL
 COMMENTS-SEE THIS PLAN REVIEWER?S COMMENTE