| Plan Review Notes For Permit 07020647 |
| Permit Number |
07020647 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-05 17:04:39 | *****DENIED***** | | | | | | | | | | | | | | | 1.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK IS | | | BEING CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. | | | | | | 2.THE NUMERICAL ADDRESS IS REQUIRED. ON LOCATION | | | SECTION OF HYDRAULIC DESIGN INFORMATION SHEET. | | | | | | 3.THE SPECIFICATION SHEET FOR THE STYLE 009 FIRELOCK | | | EZ RIGID COUPLING HAS THE STAMPING OF THE TOWN OF | | | JUPITER.ALL SUCH PAPERWORK WILL BE STAMPED BY THE | | | (AHJ) CITY OF WEST PALM BEACH. | | | | | | 4.PLEASE PROVIDE SAFETY MARGIN CALCULATION FOR THIS | | | SYSTEM.AS PER WEST PALM BEACH FIRE PREVENTION, A | | | SAFETY MARGIN OF NO LESS THAN 5.0 PSI IS REQUIRED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS , INCLUDE A | | | RESPONSE LETTER INDICATING HOW/WHERE EACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | |
|