| 2007-06-19 18:38:35 | *** UNSAT 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW STILL |
| | NEED TO BE CLARIFIED. |
| | SOME COMMENTS ARE NEW DUE TO INFORMATION ONLY NOW BEING |
| | SUBMITTED OR SHOWN ON PLANS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE PLANS NOW MENTIONS NEW LIGHTING |
| | CONTROLS BEING INSTALLED HOWEVER THE RESPONSE LETTER |
| | MENTIONS TO SEE KEY NOTE ON PLANS. THE KEY NOT ON PLANS |
| | ONLY STATES THE NEW DEVICES ARE TO COMPLY WITH THE FBC |
| | CHAPTER 13. PLEASE KNOW THAT QUOTING THE CODE ON PLANS |
| | IN LIEU OF SHOWING CODE COMPLIANCE DETAIL(S) IS NOT |
| | ACCEPTABLE. |
| | PLEASE SHOW LOCATIONS OF THESE DEVICES AS THE CODE DOES |
| | REQUIRE THEM TO BE LOCATED IN SPECIFIC LOCATIONS. |
| | PLEASE INDICATE THE TYPE OF DEVICE WHICH IS TO BE |
| | INSTALLED SO THAT MINIMUM COVERAGE AND CONTROL AND CAN |
| | BE VERIFIED FOR THE ENERGY CODE AND LIFE SAFETY CODE. |
| | PLEASE INDICATE THE MAXIMUM AMOUNT OF TIME ON DEVICES: |
| | THIS WILL DEPEND ON THE TYPE OF DEVICE CHOSEN. (4HRS |
| | MAX FOR TIMER TYPE AND 30MINS MAXIMUM FOR OS TYPE |
| | DEVICES) |
| | 13-415.1.ABC.1.1, .1.2 |
| | PLEASE SEE THE NUMBER OF LIGHTING FIXTURES LISTED ON |
| | PERFORMANCE CALCULATIONS DO NOT COORDINATE WITH PLANS. |
| | PLEASE GO THROUGH ALL FIXTURES AND PLEASE SEE RECESSED |
| | LIGHTS WHICH BULBS ARE BEING CHANGED OUT SHOULD |
| | INDICATE THE NEW WATTAGE. |
| | PLEASE CALL TO GO OVER ITEMS IN THE CODE WHICH GIVES |
| | YOU ADDITIONAL WATTAGE PER SQ FT IF NEEDED. |
| | |
| | 2) NOTE: PLEASE SEE THE LIGHTING FIXTURES FOR EMERGENCY |
| | LIGHTING ON PLANS AND FIXTURE LEGEND IS VERY FAINT. |
| | PLEASE SEE SEVERAL OF THESE ARE REDLINED WITH CIRCLES |
| | ON PLANS AND FIXTURE LEGEND. PLEASE ADJUST PRINTING O |
| | THIS FOR LS 101 7.8, 7.9 |
| | ALREADY CORRECTED CIRCUITING. |
| | |
| | 3) NOTE: PLEASE SEE PLANS MENTIONS THE TRANSFORMER IS |
| | TO BE RELOCATED HOWEVER PLANS DO NOT INDICATE THE NEW |
| | LOCATION? PLEASE SEE 450.13, 110.26 AS THE LOCATION IS |
| | NOT PERMITTED ABOVE CEILINGS FOR THE SIZE UNIT ETC AND |
| | MINIMUM CLEARANCES ON FLOOR IS ALSO REQUIRED. |
| | PLEASE COMPLETE. |
| | |
| | 4) NOTE: PLEASE SEE RISER HAS NOW BEEN REVISED TO |
| | INCLUDE A NEW DISCONNECT ON THE LOAD SIDE OF THE |
| | TRANSFORMER HOWEVER THE PLANS DO NOT SHOW THIS |
| | DISCONNECT. REVIEW FOR LOCATION FOR 240.21,110.26 AND |
| | 240.24 ETC CAN NOT BE VERIFIED AT THIS TIME. |
| | PLEASE SHOW LOCATION OF THIS NEW DISCONNECT ON PLANS. |
| | |
| | 5) NOTE: PLEASE SEE MY PREVIOUS COMMENT WITH RESPECT TO |
| | GFI PROTECTION OF RECEPTACLES IN KITCHEN (210.8B2) AND |
| | THE RESPONSE MENTIONED TO SEE REVISED ELECTRICAL NOTE. |
| | THE ELECTRICAL NOTE HAD NO REFERENCE TO GFI PROTECTION |
| | AND ONLY MENTION *MOISTURE PROOF*? |
| | |
| | 6) NOTE: PLEASE SEE THE PREVIOUS PLANS INDICATE CLEAR |
| | DEFINITIONS OF WALLS ETC FROM DINING AREA TO KITCHEN |
| | AND BAR AREA HOWEVER THE NEW SHEETS HAVE THESE |
| | REMOVED? |
| | PLEASE SEE PREVIOUS PLANS ATTACHED. |
| | FBC 106.1.2 |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |