| 2007-03-01 14:32:37 | ****************PROVISO**************** | | | A} PER FBC-2004 FUEL GAS, SECTION 404.7 ABOVE-GROUND | | | PIPING: ALL PIPING INSTALLED OUTDOORS SHALL BE ELEVATED | | | NOT LESS THAN 3-1/2" ABOVE-GROUND. | | | B} PER FBC-2004 FUEL GAS, SECTION 408.4 SEDIMENT TRAP: | | | A SEDIMENT TRAP SHALL BE INSTALLED DOWNSTREAM OF THE | | | EQUIPMENT SHUOFF VALVE AS CLOSE TO THE INLET OF THE | | | EQUIPMENT AS PRACTICAL. | | | C}PER FBC-2004 FUEL GAS, SECTION 409.5 EQUIPMENT | | | SHUTOFF VALVE: EACH APPLIANCE SHALL BE PROVIDED WITH A | | | SHUTOFF VALVE SEPERATE FROM THE APPLIANCE, NOT FURTHER | | | THAN 6' FROM THE APPLIANCE, AND SHALL BE INSTALLED | | | UPSTREAM FROM THE UNION. SHUTOFF VALVES SHALL BE | | | PROVIDED WITH ACCESS. | | | D} PER FBC-2004 FUEL GAS, SECTION 415: PIPING SHALL BE | | | SUPPORTED PER TABLE 415.1. NOTE, 1-1/4" STEEL PIPE | | | HORIZONTAL SPACING OF SUPPORTS MINIMUM OF 10'. |
|