| 2007-03-12 14:12:49 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY |
| | OF WEST PALM BEACH AMENDMENTS; |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| | PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. PER FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION |
| | ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| | AS DETERMINED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 2. SHEET PG.2, SANITARY ISOMETRIC RISER DIAGRAM: PER |
| | FBC-2004 CHAPTER 1, SECTION 106.3.5.4 RESIDENTIAL (ONE |
| | AND TWO-FAMILY) PLEASE SUBMIT A PLUMBING SANITARY |
| | ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE, VENTS, |
| | TRAPS AND SIZES WITH CLEANOUT LOCATIONS. |
| | NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC, IS NOT |
| | CODE COMPLIANT, AND DOES NOT REFLECT THE FLOOR PLAN. |
| | PLEASE REFERENCE THE ATTACHED CORRECTED SANITARY |
| | ISOMETRIC RISER DIAGRAM TO THE PLUMBING COMMENTS FOR |
| | THE RESUBMITTAL. |
| | |
| | 3. SHEET PG. 2, SANITARY ISOMETRIC RISER DIAGRAM: PER |
| | FBC-2004 PLUMBING, SECTION 1002.1 A FIXTURE SHALL NOT |
| | BE DOUBLE TRAPPED. A WATER CLOSET HAS AN INTEGRAL TRAP |
| | AND A TRAP NEED NOT BE INDICATED. |
| | |
| | 4. SHEET PG. 2, SANITARY ISOMETRIC RISER DIAGRAM: PER |
| | FBC-2004 PLUMBING, SECTION 1002.1 EACH PLUMBING FIXTURE |
| | SHALL BE SEPERATELY TRAPPED BY A WATER SEAL TRAP. |
| | NOTE: TRAP REQUIRED FOR TUB. |
| | |
| | 5. SHEET PG.2, SANITARY ISOMETRIC RISER DIAGRAM: |
| | (A) 708.3.5 BUILDING DRAIN AND BUILDING |
| | SEWER JUNCTION. THERE SHALL BE A |
| | CLEANOUT NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN AND THE BUILDING SEWER. |
| | NOTE: PLEASE INDICATE THS CLEANOUT AS A TWO-WAY |
| | CLEANOUT. |
| | |
| | (B) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM). |
| | NOTE: FULL SIZE CLEANOUT (3") REQUIRED FOR WASHING |
| | MACHINE. |
| | |
| | (C) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | NOTE: CLEANOUT FOR WASHING MACHINE SHALL BE LOCATED |
| | FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.) |
| | |
| | 6. SHEET PG. 2, SANITARY ISOMETRIC RISER DIAGRAM: PER |
| | FBC-2004 PLUMBING, SECTION 406.3 STANDPIPE REQUIRED FOR |
| | WASHING MACHINE. PLEASE INDICATE ON THE RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |