| 2007-04-11 17:45:09 | BUILDING REVIEW CHECKLIST: |
| | 1- NEW ROOF: PROVIDE ROOF FRAMING PLAN SHOWING |
| | CALCULATED UPLIFT LOADS AND TRUSS ANCHOR SCHEDULE. |
| | SEC. 106.1.2 CITY AMENDMENTSTO FBC 2004. |
| | |
| | 2- EXTERIOR ELEVATIONS DON'T MATCH ROOF TRUSS LAYOUT |
| | PLAN PROVIDED.REVISE AS REQUIRED. |
| | |
| | 3- PROVIDE CLEAR FLOOR PLANSSHOWING WALLS TO BE |
| | REMOVED, NEW WALLS, ETC.SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | 4- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDASTATUTE. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| | FOR: |
| | A) SIMPSON CONNECTORS SPECIFIED ON PLANS. |
| | B) WINDOW MULLIONS. |
| | C) FRENCH DOORS AND ALL NEW EXTERIOR DOORS. |
| | D) STORM PANELS.NEED TO PROVIDE 2004 CODE VERSION |
| | PRODUCT APPROVAL. ONE SUBMITTED IS 2001 CODE VERSION. |
| | ***NOTE: ALSO,CLEARLY IDENTIFY SPECIFIC ANCHOR TYPE |
| | AND SPACING TO BE USED. |
| | ***ALSO, CLEARLY IDENTIFY OPENINGS TO HAVE STORM |
| | SHUTTERS. |
| | |
| | 6- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND |
| | APPROVED IN WRITING (NOT SIGNING AND SEALING) BY THE |
| | DESIGNER OF RECORD AS REQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 7- ENERGY CALCULATIONS: PROVIDE CURRENT FORM 600A-2004 |
| | R AND OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| | |
| | 8- SPECIFY SIZE AND TYPE OF EGRESS WINDOW AT BEDROOM |
| | #3, WHICH WAS CHANGED FROM DOOR TO WINDOWTO VERIFY |
| | COMPLIANCE WITH SEC. R310 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 9- SPECIFY CALCULATED DESIGN PRESSURES FOR WINDOWS AND |
| | DOORS TO VERIFY COMPLIANCE WITH SEC. R301 OF 2004 |
| | FLORIDA RESIDENTIAL CODE AND COMPLIANCE WITH PRODUCT |
| | APPROVAL SUBMITTED. |
| | |
| | 10-NEW ROOF: SPECIFY ROOF PITCH TO VERIFY IF DOUBLE |
| | LAYER OF UNDERLAYMENT IS REQUIRED OR NOT. |
| | |
| | 11- SPECIFY ROOF SHEATHING NAILING SIZE AND SPACING AS |
| | REQUIRED BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 12- TYPICAL WALL SECTION IS INCOMPLETE. SPECIFY DRYWALL |
| | AT WALLS AND CEILING. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | 13- DESIGNER OF RECORD TO SIGN AND DATE ALL DRAWINGS AS |
| | REQUIREDBY SEC. 106.3.4.3 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 14- DESIGNER OF RECORD TO SPECIFY ALL DESIGN CRITERIA |
| | INCLUDING CODE USED, ALL WIND LOADS, ALL DEAD LOADS, |
| | ALL LIVE LOADS AS REQUIRED BY SEC. R301 AND TABLE |
| | R301.5OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 15- SPECIFY ATTIC ACCESS FOR NEW PITCHED ROOF AT REAR |
| | OF HOUSE AS REQUIRED BY SEC. R807 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |