| 2007-09-17 12:03:44 | BUILDING PLAN REVIEW |
| | PERMIT: 07020610 |
| | ADD: 255 EVERNIA STREET |
| | CONT: DC CONSTRUCTION ASSO. |
| | TEL: (561)988-8505 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 3RD |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGE AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)FL.S.S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT.NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE |
| | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: |
| | 713.13(6) THE POSTING OF THE NOTICE OF COMMENCEMENT AT |
| | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)OK, |
| | 4)OK |
| | 5)OK |
| | 6)OK |
| | 7)OK, HOWEVER, OPENING GUARDS SHALL HAVE BALUSTERS OR |
| | ORNAMENTAL PATTERNS SUCH THAT A 4 INCH DIAMETER SPHERE |
| | CANNOT PASS THROUGH. FBC 1012.3 |
| | |
| | **NO RESPONSE** |
| | 8)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 9)GUARDRAILS SHALL BE IN CONFORMANCE WITH FBC |
| | SEC.1607.7 AND FBC. SEC. 1012. INDICATE HOW THE |
| | GUARDRAIL WILL BE ATTATCHED, |
| | **NO RESPONSE** |
| | |
| | 10) SUBMIT THE SHOP DRAWINGS FOR THE STAIRS FOR REVIEW |
| | AS NOTED ON THE DRAWINGS. |
| | **NOTED** HOWEVER, THE SHOP DRAWINGS SHALL HAVE AN |
| | APPROVAL STAMP BY THE ENGINEER OR ARCHITECT OR RECORD. |
| | SEE SHEET S-3 SUBMITTAL NOTE #1. |
| | |
| | 11)PROVIDE A STRUCTURAL STEEL SCHEDULE FOR THE STEEL |
| | COLUMNS AND BEAMS INDICATING ALL DIMENTIONS. SEE SHEET |
| | S-2 IS MISSING THE DIMENTIONS OF THE STRUCTURAL COLUMNS |
| | AND BEAMS. ALSO INDICATE THE SIZE OF THE HOLES, THE |
| | TYPE OF BOLTS. SHOW THE DESIGN BEARING LOAD OF THE |
| | BEAMS AND COLUMNS. |
| | |
| | 12)OK |
| | |
| | NEW************* |
| | |
| | 13)OK |
| | |
| | 14)OK |
| | |
| | 15)OK |
| | |
| | 16)NOTE:WALL WITHIN 2FEET OF URINALS AND WATER |
| | CLOSETS SHALL HAVE A SMOOTH, HARD, NONABOORBENT SURFACE |
| | TO A HEIGHT OF 4 FEET ABOVE THE FLOOR. EPOXY PAINT ON |
| | DRYWALL IS NOT CONSIDERED A HARD SURFACE. FBC 1210.2 |
| | |
| | 17)INDICATE WHICH TABLE WAS USED TO CALCULATE THE |
| | OCCUPANT LOAD OF THE BUILDING. SEE TABLE 1004.1.2. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |