| 2007-06-25 14:33:47 | |
| | |
| | *** UNSAT 2ND REVIEW *** |
| | |
| | ** PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS |
| | REVIEW WHICH ARE IN NEED OF ADDRESSING ALONG WITH NEW |
| | COMMENTS BASED ON REVISIONS AND CHANGES TO THE PLANS. |
| | PLEASE SEE NEW COMMENTS ALSO BASED ON INFORMATION NOW |
| | SHOWN WHICH WAS NOT ON PREVIOUS PLANS. |
| | |
| | |
| | |
| | 1) NOTE:PLEASE SEE THE ARCHITECTURAL COVER SHEET |
| | WHICH CONTAINS A 2005 NFPA-72, WHICH SHOULD BE 2002. |
| | THIS COULD BE REDLINED HOWEVER AS THIS SHEET WILL |
| | REQUIRE REVISIONS FOR OTHER COMMENTS THIS SHOULD BE |
| | ADJUSTED AT THIS TIME. |
| | |
| | 2) NOTE: PLEASE SEE THIS NOTE REMAINS THE SAME FROM |
| | PREVIOUS REVIEW. |
| | PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE |
| | WITH THE PLANS. |
| | PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT FOR |
| | THE TYPE OF LUMINARIES, THE NUMBER OF LUMINARIES, AND |
| | THE WATTAGE AS SHOWN ON LUMINARIES. |
| | PLEASE SEE THESE DO NOT CORRELATE AT THIS TIME. PLEASE |
| | SEE THE FIXTURE SCHEDULE NEEDS TO BE COMPLETED WITH |
| | FIXTURE INFORMATION. THESE CAN ALWAYS BE REVISED AT A |
| | LATER DATE. |
| | PLEASE SEE THE SIGNATURE, DATE AND RAISED SEAL IS |
| | REQUIRED ON CERTIFICATION SHEETS. 13-103.1.1.1 PLEASE |
| | SEE ONLY THE SIGNATURE AND DATE ARE PRESENT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE |
| | WITH THE PLANS. PLEASE SEE THE LIGHTING, WATTAGE, |
| | NUMBER OF FIXTURES ETC. |
| | PLEASE BE SURE THE FIXTURE LEGEND STATES THE TYPE OF |
| | FIXTURE SPECIFIED AND COORDINATE THIS WITH THE ENERGY |
| | CALCULATIONS. |
| | THESE DO NOT CORRELATE AT ALL AT THIS TIME. |
| | PLEASE SEE MAXIMUM LIGHTING POWER DENSITIES WHICH HAS |
| | NOT BEEN STATED ON PLANS, OR CORRELATE IN ENERGY |
| | CALCULATIONS. |
| | PLEASE BE SURE THESES CONTAIN A RAISED SEAL, DATE AND |
| | SIGNATURE OF THE DESIGNER OF RECORD ON SHEET(S) WHICH |
| | CONTAIN THE TITLE BLOCKS FOR THE DESIGNER OF RECORD. |
| | THE SHEET CONTAINS THE LOCATION OF THE PRINTED NAME FOR |
| | THE DESIGNER HOWEVER THIS SHEET WAS NOT SIGNED, DATED |
| | OR SEALED. |
| | PLEASE BE SURE ONCE THE METHOD OF CONTROLS IS FIGURED |
| | FOR THE PLANS TO BE SURE TO CORRELATE CONTROL METHODS |
| | ON THE ENERGY CALCULATIONS. |
| | PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1, |
| | 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1, |
| | 13-415.2, 13-415.2.ABC.1.2 (3) FOR TRACK LIGHTING. |
| | |
| | 3) NOTE: PLEASE SEE THE LOCATION OF THE ELECTRICAL |
| | PANEL IS NOT PERMITTED IN CLOSET.110.26, 408.7, 240.24 |
| | ETC |
| | PLEASE SEE COMMENTS WITH RESPECT TO THE NEW RISER AS |
| | OTHER ELECTRICAL EQUIPMENT IS NOT SHOWN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE ELECTRICAL PLANS DO NOT INDICATE A |
| | SCALE IN WHICH PLANS ARE UNDER, HOWEVER IT IS BEING |
| | ASSUMED THAT THE SCALE IS THAT OF THE ARCHITECTURAL |
| | PLANS AT 3/16THS. |
| | PLEASE SEE THE LOCATION AND MINIMUM CLEARANCES FOR THE |
| | ELECTRICAL PANEL *A* DO NOT SEEM TO MEET 110.26. PLEASE |
| | ALSO SEE 408.7 AND 240.24 FOR LOCATION OF EASILY |
| | IGNITABLE MATERIALS AND CLOSE PROXIMITY OF COMBUSTIBLES |
| | WITH OVER CURRENT PROTECTION DEVICES. |
| | PLEASE ADJUST PLANS. |
| | |
| | 4) NOTE:PLEASE KNOW THE SUITE/UNIT # MAY BE ADJUSTED |
| | BY THE ADDRESSING REVIEWER. ON SHEETS WHICH DO NOT |
| | REQUIRE REVISIONS THE ADDRESS FOR SUITE/UNIT NUMBER MAY |
| | BE CHANGED BY HAND. |
| | THIS COMMENT WILL REMAIN AS THE INFORMATION FOR THIS |
| | HAS BEEN FORWARDED TO ADDRESSING. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE THE ADDRESS ON THE PLANS FOR THE |
| | LOCATION OF THE SCOPE OF WORK. PLEASE ALSO KNOW THIS |
| | WILL BE SENT TO ADDRESSING FOR THE NEW SUITE NUMBER |
| | WHICH WILL BE ASSIGNED. |
| | |
| | 5) NOTE: PLEASE SEE THE PHOTO-METRICS ON SHEET A-1 DOES |
| | NOT INDICATE THE COMPLIANCE AS PREVIOUSLY NOTED. PLEASE |
| | SHOW LEVELS UNDER NORMAL AND UNDER EMERGENCY. AS THE |
| | LIGHTING PLANS DO NOT INDICATE THE EMERGENCY LIGHT |
| | FIXTURES NEEDED FOR THIS EGRESS PATH IT DOES NOT SEEM |
| | THE MINIMUM LEVELS CAN BE MET BASED ON THE PLANS |
| | SUBMITTED. |
| | PLEASE SUBMIT THE COMPLETED INFORMATION FOR REVIEW. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE PROVIDE THE PHOTO-METRIC LEVELS FOR STAIRS PER |
| | NFPA-101 2003 7.8.1.3, 7.9.2.2. |
| | |
| | 6) NOTE: PLEASE SEE THE PLANS NOW INCLUDE A NEW |
| | ELECTRICAL RISER WHICH CONTAINS THE FOLLOWING |
| | COMMENTS. |
| | A) PLEASE SEE THE OCP FOR THE TRANSFORMER IS SET TOO |
| | HIGH PER 450.3. |
| | B) PLEASE SEE THE CONDUCTOR SIZES ARE NOT SUFFICIENT |
| | SIZE FOR THE 100AMP OCP AS SHOWN ON MAIN DISCONNECT. |
| | PLEASE SEE 6A ABOVE AS THE OCP WILL BE |
| | CHANGING.240.4,310.16,ETC. |
| | C) PLEASE SEE INDICATE THE GROUNDING ATTACHMENT FOR |
| | TRANSFORMER. 250.50,250.20,250.30 ETC. |
| | D) PLEASE SEE THE NEW LOAD CALCULATIONS NEED TO BE |
| | ADJUSTED TO COORDINATE WITH ALL ELECTRICAL AND |
| | DEDICATED LOADS ON PANEL SCHEDULE. THERE ARE SEVERAL |
| | DEDICATE CIRCUIT LOADS ON PANEL WHICH ARE NOT SHOWN IN |
| | LOAD CALCULATIONS. THESE MAY NOT BE PART OF THE GENERAL |
| | LIGHTING/RECEPTACLE LOADS. |
| | PLEASE SEE WATER HEATERS UNDER 422.13 WHICH IS REQUIRED |
| | AT 125% (NEW CODE CHANGE FOR 05). PLEASE SEE OTHER |
| | SECTIONS IN THE 2005 NEC 220. |
| | |
| | 7) NOTE: PLEASE SHOW LOCATION OF ALL SERVICE EQUIPMENT |
| | INCLUDING THE NEW TRANSFORMER NOT SHOWN. PLEASE SEE |
| | 110.26,408.7,240.24,450.9,450.13 ETC. |
| | |
| | 8) NOTE:PLEASE SEE PLANS INDICATE THE DEVICES AS |
| | PREVIOUSLY REQUESTED AND IT IS KNOWN THAT THE FA |
| | DEVICES WILL BE UNDER A SEPARATE PERMIT HOWEVER THE |
| | MINIMUM LEVELS FOR ADA COMPLIANCE NEEDS TO BE STATED ON |
| | PLANS. THIS CAN BE ON THE SYMBOL LEGEND. |
| | PLEASE SEE THE LEVELS AS REQUIRED IN CODE STATED IN |
| | PREVIOUS NOTES. QUOTING THE CODE IN LIEU OF SPECIFIC |
| | INFORMATION IS NOT PERMITTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW AS THIS BUILDING ISFULLY SPRINKLED AND |
| | CONTAINS A FIRE ALARM SYSTEM, PLEASE KNOW THE BASE |
| | PLANS SHALL INDICATE THE BASE PROTECTION EVEN THOUGH |
| | ANY FIRE SPRINKLER AND FIRE ALARM WORK WILL BE UNDER A |
| | SEPARATE PERMIT. FBC ADMIN SECTION 106.3.5.1.2 PLEASE |
| | PROVIDE THE MINIMUM LEVELS FOR ALL HORN AND STROBE |
| | DEVICES PER FBC 11-4.28.1, .2 AND .3(4). THIS IS |
| | REQUIRED ON THE PLANS AT THIS TIME. |
| | |
| | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |