2007-06-29 11:07:23BUILDING PLAN REVIEW
 PERMIT: 07020610
 ADD: 255 EVERNIA STREET
 CONT: DC CONSTRUCTION ASSO.
 TEL: (561)988-8505
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)OK, HOWEVER,THERE WERE SOME ELECTRICAL ISSUES.
  
 4)OK
  
 5)OK
  
 6)OK
  
 7)1009.11.5 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT. WHERE HANDRAILS ARE NOT
 CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL EXTEND
 HORIZONTALLY AT LEAST 12 INCHES (305 MM) BEYOND THE TOP
 RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD
 BEYOND THE BOTTOM RISER.
  
  
 8)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9)GUARDRAILS SHALL BE IN CONFORMANCE WITH FBC
 SEC.1607.7 AND FBC. SEC. 1012. INDICATE HOW THE
 GUARDRAIL WILL BE ATTATCHED,
  
 10) SUBMIT THE SHOP DRAWINGS FOR THE STAIRS FOR REVIEW
 AS NOTED ON THE DRAWINGS.
  
 11)PROVIDE A STRUCTURAL STEEL SCHEDULE FOR THE STEEL
 COLUMNS AND BEAMS INDICATING ALL DIMENTIONS. SEE SHEET
 S-2 IS MISSING THE DIMENTIONS OF THE STRUCTURAL COLUMNS
 AND BEAMS. ALSO INDICATE THE SIZE OF THE HOLES, THE
 TYPE OF BOLTS. SHOW THE DESIGN BEARING LOAD OF THE
 BEAMS AND COLUMNS.
  
 12)OK
  
 NEW*************
  
 13)1603.1.1 FLOOR LIVE LOAD . MEZZANINE
 THE UNIFORMLY DISTRIBUTED, CONCENTRATED AND IMPACT
 FLOOR LIVE LOAD USED IN THE DESIGN SHALL BE INDICATED
 FOR FLOOR AREAS. LIVE LOAD REDUCTION OF THE UNIFORMLY
 DISTRIBUTED FLOOR LIVE LOADS, IF USED IN THE DESIGN,
 SHALL BE INDICATED.
  
 14)1603.4
 CONSTRUCTION DOCUMENTS FOR OTHER THAN RESIDENTIAL
 BUILDINGS FILED WITH THE BUILDING OFFICIAL WITH
 APPLICATIONS FOR PERMITS SHALL SHOW ON EACH DRAWING THE
 LIVE LOADS PER SQUARE FOOT (M 2 ) OF AREA COVERED FOR
 WHICH THE BUILDING IS DESIGNED. OCCUPANCY PERMITS FOR
 BUILDINGS HEREAFTER ERECTED SHALL NOT BE ISSUED UNTIL
 THE FLOOR LOAD SIGNS, REQUIRED BY SECTION 1603.3 , HAVE
 BEEN INSTALLED. FOR STAIRS LOAD SEE FBC 1607.1
  
 15)NOTE: THE DOORS IN FRONT OF THE SINK SHALL BE
 REMOVED TO MEET THE REQUIREMENTS OF FBC.SEC.11-4.24
  
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER