| 2007-06-29 11:07:23 | BUILDING PLAN REVIEW |
| | PERMIT: 07020610 |
| | ADD: 255 EVERNIA STREET |
| | CONT: DC CONSTRUCTION ASSO. |
| | TEL: (561)988-8505 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 2ND |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. |
| | NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE |
| | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: |
| | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT |
| | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)OK, HOWEVER,THERE WERE SOME ELECTRICAL ISSUES. |
| | |
| | 4)OK |
| | |
| | 5)OK |
| | |
| | 6)OK |
| | |
| | 7)1009.11.5 HANDRAIL EXTENSIONS. |
| | HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING |
| | SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN |
| | ADJACENT STAIR FLIGHT. WHERE HANDRAILS ARE NOT |
| | CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL EXTEND |
| | HORIZONTALLY AT LEAST 12 INCHES (305 MM) BEYOND THE TOP |
| | RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD |
| | BEYOND THE BOTTOM RISER. |
| | |
| | |
| | 8)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 9)GUARDRAILS SHALL BE IN CONFORMANCE WITH FBC |
| | SEC.1607.7 AND FBC. SEC. 1012. INDICATE HOW THE |
| | GUARDRAIL WILL BE ATTATCHED, |
| | |
| | 10) SUBMIT THE SHOP DRAWINGS FOR THE STAIRS FOR REVIEW |
| | AS NOTED ON THE DRAWINGS. |
| | |
| | 11)PROVIDE A STRUCTURAL STEEL SCHEDULE FOR THE STEEL |
| | COLUMNS AND BEAMS INDICATING ALL DIMENTIONS. SEE SHEET |
| | S-2 IS MISSING THE DIMENTIONS OF THE STRUCTURAL COLUMNS |
| | AND BEAMS. ALSO INDICATE THE SIZE OF THE HOLES, THE |
| | TYPE OF BOLTS. SHOW THE DESIGN BEARING LOAD OF THE |
| | BEAMS AND COLUMNS. |
| | |
| | 12)OK |
| | |
| | NEW************* |
| | |
| | 13)1603.1.1 FLOOR LIVE LOAD . MEZZANINE |
| | THE UNIFORMLY DISTRIBUTED, CONCENTRATED AND IMPACT |
| | FLOOR LIVE LOAD USED IN THE DESIGN SHALL BE INDICATED |
| | FOR FLOOR AREAS. LIVE LOAD REDUCTION OF THE UNIFORMLY |
| | DISTRIBUTED FLOOR LIVE LOADS, IF USED IN THE DESIGN, |
| | SHALL BE INDICATED. |
| | |
| | 14)1603.4 |
| | CONSTRUCTION DOCUMENTS FOR OTHER THAN RESIDENTIAL |
| | BUILDINGS FILED WITH THE BUILDING OFFICIAL WITH |
| | APPLICATIONS FOR PERMITS SHALL SHOW ON EACH DRAWING THE |
| | LIVE LOADS PER SQUARE FOOT (M 2 ) OF AREA COVERED FOR |
| | WHICH THE BUILDING IS DESIGNED. OCCUPANCY PERMITS FOR |
| | BUILDINGS HEREAFTER ERECTED SHALL NOT BE ISSUED UNTIL |
| | THE FLOOR LOAD SIGNS, REQUIRED BY SECTION 1603.3 , HAVE |
| | BEEN INSTALLED. FOR STAIRS LOAD SEE FBC 1607.1 |
| | |
| | 15)NOTE: THE DOORS IN FRONT OF THE SINK SHALL BE |
| | REMOVED TO MEET THE REQUIREMENTS OF FBC.SEC.11-4.24 |
| | |
| | |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |