Plan Review Notes
Plan Review Notes For Permit 07020610
Permit Number 07020610
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-04 08:41:06*** UNSAT ***
  
 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN
 SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGE SIN THE FBC WHICH WILL
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE ALSO SEE ELECTRICAL CHANGES UNDER THE 2005
 INCLUDING ANY SECTIONS OF CODES WHICH ARE REFLECTED ON
 PLANS FROM THE PREVIOUS 2002 NEC.
 PLEASE LIST THE FOLLOWING FOR THIS REVIEWER AT A
 MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS DO NOT
 CORRELATE WITH THE PLANS. PLEASE SEE THE LIGHTING,
 WATTAGE, NUMBER OF FIXTURES ETC.
 PLEASE BE SURE THE FIXTURE LEGEND STATES THE TYPE OF
 FIXTURE SPECIFIED AND COORDINATE THIS WITH THE ENERGY
 CALCULATIONS.
 THESE DO NOT CORRELATE AT ALL AT THIS TIME.
 PLEASE SEE MAXIMUM LIGHTING POWER DENSITIES WHICH HAS
 NOT BEEN STATED ON PLANS, OR CORRELATE IN ENERGY
 CALCULATIONS.
 PLEASE BE SURE THESES CONTAIN A RAISED SEAL, DATE AND
 SIGNATURE OF THE DESIGNER OF RECORD ON SHEET(S) WHICH
 CONTAIN THE TITLE BLOCKS FOR THE DESIGNER OF RECORD.
 THE SHEET CONTAINS THE LOCATION OF THE PRINTED NAME FOR
 THE DESIGNER HOWEVER THIS SHEET WAS NOT SIGNED, DATED
 OR SEALED.
 PLEASE BE SURE ONCE THE METHOD OF CONTROLS IS FIGURED
 FOR THE PLANS TO BE SURE TO CORRELATE CONTROL METHODS
 ON THE ENERGY CALCULATIONS.
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1,
 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1,
 13-415.2, 13-415.2.ABC.1.2 (3) FOR TRACK LIGHTING.
  
 3) NOTE: PLEASE SEE THAT PLANS DO NOT INDICATE ANY
 METHODS FOR THE REQUIRED AUTOMATED CONTROLS PER FBC
 2004 W/2006 REVISIONS.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 4) NOTE: PLEASE SEE THE ELECTRICAL PLANS DO NOT
 INDICATE A SCALE IN WHICH PLANS ARE UNDER, HOWEVER IT
 IS BEING ASSUMED THAT THE SCALE IS THAT OF THE
 ARCHITECTURAL PLANS AT 3/16THS.
 PLEASE SEE THE LOCATION AND MINIMUM CLEARANCES FOR THE
 ELECTRICAL PANEL *A* DO NOT SEEM TO MEET 110.26. PLEASE
 ALSO SEE 408.7 AND 240.24 FOR LOCATION OF EASILY
 IGNITABLE MATERIALS AND CLOSE PROXIMITY OF COMBUSTIBLES
 WITH OVER CURRENT PROTECTION DEVICES.
 PLEASE ADJUST PLANS.
  
 5) NOTE: PLEASE PROVIDE THE ADDRESS ON THE PLANS FOR
 THE LOCATION OF THE SCOPE OF WORK. PLEASE ALSO KNOW
 THIS WILL BE SENT TO ADDRESSING FOR THE NEW SUITE
 NUMBER WHICH WILL BE ASSIGNED.
  
 6) NOTE: PLEASE PROVIDE THE PHOTO-METRIC LEVELS FOR
 STAIRS PER NFPA-101 2003 7.8.1.3, 7.9.2.2.
  
 7) NOTE: PLEASE SEE THAT NO INFORMATION IS BEING
 PROVIDED FOR THE NEW ELECTRICAL PANEL. WHERE IS IT FED
 FROM? FEEDERS? METER? MAIN? ETC.
 THIS IS A NEW BUILD OUT AND THE PANEL DOES NOT EXIST.
 215.5, 310.16, 230.70, 240.4, 250.110, ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 8) NOTE: PLEASE KNOW AS THIS BUILDING ISFULLY
 SPRINKLED AND CONTAINS A FIRE ALARM SYSTEM, PLEASE KNOW
 THE BASE PLANS SHALL INDICATE THE BASE PROTECTION EVEN
 THOUGH ANY FIRE SPRINKLER AND FIRE ALARM WORK WILL BE
 UNDER A SEPARATE PERMIT. FBC ADMIN SECTION 106.3.5.1.2
 PLEASE PROVIDE THE MINIMUM LEVELS FOR ALL HORN AND
 STROBE DEVICES PER FBC 11-4.28.1, .2 AND .3(4). THIS IS
 REQUIRED ON THE PLANS AT THIS TIME.
  
 9) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR ENGINEERING FIRM FOR THE *S* SHEETS. PLEASE SEE THE
 FAC 61G15-23.002 AND FS 471.023.
 PLEASE KNOW THAT THE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER IS MISSING AT THIS TIME. **THIS IS
 REQUIRED FOR THESE SHEETS WHETHER OR NOT COMMENT IS
 MADE BY OTHER TRADE(S)/REVIEWER(S).
  
  
 ***PLEASE KNOW AS THERE WAS MISSING INFORMATION WHICH
 IS REQUIRED FOR REVIEW AT THIS TIME FOR MANY ITEMS,
 THERE MAY BE COMMENTS ONCE INFORMATION IS PROVIDED THAT
 CAN NOT BE REVIEWED FOR CODE COMPLIANCE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  