| 2007-03-04 08:41:06 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN |
| | SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGE SIN THE FBC WHICH WILL |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE ALSO SEE ELECTRICAL CHANGES UNDER THE 2005 |
| | INCLUDING ANY SECTIONS OF CODES WHICH ARE REFLECTED ON |
| | PLANS FROM THE PREVIOUS 2002 NEC. |
| | PLEASE LIST THE FOLLOWING FOR THIS REVIEWER AT A |
| | MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS DO NOT |
| | CORRELATE WITH THE PLANS. PLEASE SEE THE LIGHTING, |
| | WATTAGE, NUMBER OF FIXTURES ETC. |
| | PLEASE BE SURE THE FIXTURE LEGEND STATES THE TYPE OF |
| | FIXTURE SPECIFIED AND COORDINATE THIS WITH THE ENERGY |
| | CALCULATIONS. |
| | THESE DO NOT CORRELATE AT ALL AT THIS TIME. |
| | PLEASE SEE MAXIMUM LIGHTING POWER DENSITIES WHICH HAS |
| | NOT BEEN STATED ON PLANS, OR CORRELATE IN ENERGY |
| | CALCULATIONS. |
| | PLEASE BE SURE THESES CONTAIN A RAISED SEAL, DATE AND |
| | SIGNATURE OF THE DESIGNER OF RECORD ON SHEET(S) WHICH |
| | CONTAIN THE TITLE BLOCKS FOR THE DESIGNER OF RECORD. |
| | THE SHEET CONTAINS THE LOCATION OF THE PRINTED NAME FOR |
| | THE DESIGNER HOWEVER THIS SHEET WAS NOT SIGNED, DATED |
| | OR SEALED. |
| | PLEASE BE SURE ONCE THE METHOD OF CONTROLS IS FIGURED |
| | FOR THE PLANS TO BE SURE TO CORRELATE CONTROL METHODS |
| | ON THE ENERGY CALCULATIONS. |
| | PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1, |
| | 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1, |
| | 13-415.2, 13-415.2.ABC.1.2 (3) FOR TRACK LIGHTING. |
| | |
| | 3) NOTE: PLEASE SEE THAT PLANS DO NOT INDICATE ANY |
| | METHODS FOR THE REQUIRED AUTOMATED CONTROLS PER FBC |
| | 2004 W/2006 REVISIONS. |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | 4) NOTE: PLEASE SEE THE ELECTRICAL PLANS DO NOT |
| | INDICATE A SCALE IN WHICH PLANS ARE UNDER, HOWEVER IT |
| | IS BEING ASSUMED THAT THE SCALE IS THAT OF THE |
| | ARCHITECTURAL PLANS AT 3/16THS. |
| | PLEASE SEE THE LOCATION AND MINIMUM CLEARANCES FOR THE |
| | ELECTRICAL PANEL *A* DO NOT SEEM TO MEET 110.26. PLEASE |
| | ALSO SEE 408.7 AND 240.24 FOR LOCATION OF EASILY |
| | IGNITABLE MATERIALS AND CLOSE PROXIMITY OF COMBUSTIBLES |
| | WITH OVER CURRENT PROTECTION DEVICES. |
| | PLEASE ADJUST PLANS. |
| | |
| | 5) NOTE: PLEASE PROVIDE THE ADDRESS ON THE PLANS FOR |
| | THE LOCATION OF THE SCOPE OF WORK. PLEASE ALSO KNOW |
| | THIS WILL BE SENT TO ADDRESSING FOR THE NEW SUITE |
| | NUMBER WHICH WILL BE ASSIGNED. |
| | |
| | 6) NOTE: PLEASE PROVIDE THE PHOTO-METRIC LEVELS FOR |
| | STAIRS PER NFPA-101 2003 7.8.1.3, 7.9.2.2. |
| | |
| | 7) NOTE: PLEASE SEE THAT NO INFORMATION IS BEING |
| | PROVIDED FOR THE NEW ELECTRICAL PANEL. WHERE IS IT FED |
| | FROM? FEEDERS? METER? MAIN? ETC. |
| | THIS IS A NEW BUILD OUT AND THE PANEL DOES NOT EXIST. |
| | 215.5, 310.16, 230.70, 240.4, 250.110, ETC. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 8) NOTE: PLEASE KNOW AS THIS BUILDING ISFULLY |
| | SPRINKLED AND CONTAINS A FIRE ALARM SYSTEM, PLEASE KNOW |
| | THE BASE PLANS SHALL INDICATE THE BASE PROTECTION EVEN |
| | THOUGH ANY FIRE SPRINKLER AND FIRE ALARM WORK WILL BE |
| | UNDER A SEPARATE PERMIT. FBC ADMIN SECTION 106.3.5.1.2 |
| | PLEASE PROVIDE THE MINIMUM LEVELS FOR ALL HORN AND |
| | STROBE DEVICES PER FBC 11-4.28.1, .2 AND .3(4). THIS IS |
| | REQUIRED ON THE PLANS AT THIS TIME. |
| | |
| | 9) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS |
| | FOR ENGINEERING FIRM FOR THE *S* SHEETS. PLEASE SEE THE |
| | FAC 61G15-23.002 AND FS 471.023. |
| | PLEASE KNOW THAT THE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER IS MISSING AT THIS TIME. **THIS IS |
| | REQUIRED FOR THESE SHEETS WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER TRADE(S)/REVIEWER(S). |
| | |
| | |
| | ***PLEASE KNOW AS THERE WAS MISSING INFORMATION WHICH |
| | IS REQUIRED FOR REVIEW AT THIS TIME FOR MANY ITEMS, |
| | THERE MAY BE COMMENTS ONCE INFORMATION IS PROVIDED THAT |
| | CAN NOT BE REVIEWED FOR CODE COMPLIANCE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |