| 2007-03-06 13:46:14 | *****DENIED***** |
| | |
| | |
| | 01.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE |
| | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. |
| | |
| | 02. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 04.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK |
| | WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH |
| | SUBMITTED PLAN SHEET. |
| | |
| | 05.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO |
| | THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SPACES. AS |
| | PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO |
| | LESS THAN 3" IN HEIGHT. |
| | |
| | 06.THE REAR DOOR SHOULD HAVE AN EXIT SIGN LIGHT. |
| | |
| | 07.WHAT IS INTERIOR FINISH CLASSIFICATION FOR THE |
| | WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, |
| | AND IN ALL OTHER AREAS? |
| | |
| | 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES |
| | THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS |
| | SHEET, INDICATE THE LOCATION OFFIRE EXTINGUISHER(S) |
| | AT DISTANCES TO SATISFY THE 75' TRAVEL DISTANCE |
| | REQUIREMENT. |
| | |
| | 09.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR |
| | THIS TENANT SPACE. |
| | |
| | 10.IF SO EQUIPPED WITH A FIRE ALARM SYSTEM, WILL IT |
| | BE INDEPENDENT OR WILL IT BE TIED INTO THE STRAND'S |
| | SYSTEM. |
| | |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH |
| | ITEM WAS ADDRESSED ON THE PLAN. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |