Plan Review Notes
Plan Review Notes For Permit 07020609
Permit Number 07020609
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-26 12:29:39 
  
  
 DENIED/INCOMPLETE INFORMATION.
  
 1} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE
 SHOWN ON THE PLAN. SHEET #2 OF THE ENERGY GAUGE ONLY
 LISTS 1 FLUORESCENT, AND NOTE THAT ALTHOUGH A MANUAL
 CONTROL IS LISTED, IT MUST AUTOMATICALLY TURN LIGHTS
 OFF WITHIN 30 MINUTES OF ALL OCCUPANTS LEAVING THE
 SPACE. DESIGNATE WHICH MANUFACTURER AND MODELS ARE
 BEING SPECIFIED FOTR THIS PROJECT BY THE ENGINEER.
  
 2} INDICATE COMPLIANCE WITH 13-415.2ABC.1, PERFORMANCE
 CALCULATION PROCEDURES. SUBMIT FORMS WITH 13-415.2B OR
 13-415.2.C.1 TABLE DENSITIES.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718