Plan Review Notes
Plan Review Notes For Permit 07020594
Permit Number 07020594
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-28 07:30:56 
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT A FLOOR PLAN AND INDICATING THE
 LOCATION OF ALL EQUIPMENT AND DEVICES BEING INSTALLED
 UNDER THE SCOPE OF THIS APPLICATION.106.1.1 FBC.
  
 2} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. INDICATE
 SAME ON PLANS.
  
 3} THERE IS MENTION OF DEVICES IN THE BATHROOM. PROVIDE
 A FLOOR PLAN AND LOCATE THE DEVICES IN ALL AREAS OF
 WORK. BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1).
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC.
  
 5} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved