| Plan Review Notes For Permit 07020557 |
| Permit Number |
07020557 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-25 14:36:06 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 W/2005, 2006 | | | AMEND | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FACFLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA | | | | | | FROM PREVIOUS LIST: | | | | | | 1.-2.)ADDRESSED. | | | | | | 3.)APPLICATION STATES INGROUND, PLANS ARE ABOVE | | | GROUND.APPLICATION TO BE CONSISTENT WITH THE PLANS. | | | | | | 4.)SEPARATE PERMITS REQUIRED. | | | | | | 5-7.)ADDRESSED. | | | | | | 8.)ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS TO | | | BE ON EACH SHEET. | | | | | | NEW COMMENT: | | | | | | 9.)SHEET 2 OF 2, ENGINEERING NOTES DECLARE AN | | | IMIPORTANCE FACTOR OF .87.PLESAE SEE FBC TABLE 1604.5 | | | AND CLARIFY HOW FAILURE OF A FUEL TANK IS "LOW HAZARD". | | | | | | |
|