| Date |
Text |
| 2007-06-05 15:39:48 | *****DENIED***** |
| | |
| | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE |
| | PLAN REVIEW STILL NEED TO BE ADDRESSED: |
| | |
| | |
| | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 2.THE REMOVAL AND(OR) REPLACEMENT OF THE MODULAR |
| | BUILDINGS SHALL NOT INTERFERE OR HINDER EMERGENCY |
| | RESPONSE ACCESS TO OR EGRESS FROM THE PROPERTY OR |
| | VICINITY THEREOF (INCLUDING FIRE LANES). |
| | |
| | 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. FOR EXAMPLE SEE SHEET FD1 UNDER STATE |
| | CODES. |
| | |
| | 4.ALL SUBMITTED PLAN SHEETS SHALL HAVE THE ADDRESS OF |
| | WHERE THE SCOPE OF WORK WILL BE CONDUCTED IN THE TITLE |
| | BLOCK. |
| | |
| | 5.PLEASE PROVIDE A SITE PLAN SHOWING THE HOW THE |
| | STRUCTURES RELATES TO STREETS, HYDRANTS, BUILDINGS, |
| | ETC. IN THE IMMEDIATE AREA. |
| | |
| | 6.DISPLAY 2A:10BC RATED FIRE EXTINGUISHER(S) LOCATION |
| | IN THE PROPOSED STRUCTURES. |
| | |
| | 7.WILL THESE PROPOSED STRUCTURES HAVE A FIRE ALARM |
| | AND/OR FIRE SPRINKLER SYSTEM IN ITS MAKEUP? |
| | |
| | 8. PLEASE BE ADVISED THAT IF IT IS DETERMINED THAT AN |
| | INDEPENDENT NUMERICAL ADDRESS IS REQUIRED, THOSE |
| | NUMBERS SHALL BE NO LESS THE 6" IN HEIGHT AND NO LESS |
| | THAN 1" IN WIDTH. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |