2007-06-04 17:03:29** UNSAT **
  
  
 1) NOTE: PLEASE SEE THE COMMENTS FROM THE PREVIOUS
 REVIEW WHICH MENTIONS THE ENERGY CALCULATIONS CONTAIN A
 RAISED SEAL OVER A PHOTO-COPIED SIGNATURE WHICH IS NOT
 PERMITTED PER FLORIDA STATUTES 471.023, FAC
 61G15-23.002 AND FBC 13-103.1.1.1
 PLEASE SEE THE ENERGY CALCULATIONS ARE NOT COMPLETE AS
 NO INTERIOR LIGHTING IS FIGURED INTO THE CALCULATIONS.
 PLEASE COORDINATE ALL LIGHTING ON PLANS WITH ENERGY
 CALCULATIONS.
  
 2) NOTE: PLEASE SEE RISER INDICATES ONLY A 100AMP FEED
 TO PANEL *B* WHICH ACTUALLY CONTAINS A LOAD HIGHER THAN
 100AMPS.
 THIS EXCEEDS THE RATING OF CONDUCTORS AND BREAKER.
 240.4, 310.16, 408, ETC.
  
 3) NOTE: PLEASE SEE THE EXISTING PANEL FOR THE TWO
 TRAILERS IS BEING SHOWN A MLO WITH TWO BREAKERS FOR
 EACH TRAILER, PLEASE SEE 230.70/71 AS NO MORE THAN
 6SPACES IS PERMITTED IN SERVICE EQUIPMENT. PLEASE
 CLARIFY WHERE THE SINGLE MAIN IS LOCATED OR WILL A MCB
 BE INSTALLED IN THIS PANEL?
  
 4) NOTE: PLEASE SEE THE ENTIRE PACKAGE SUBMITTED
 APPEARS THAT ONE SET OF PLANS IS FOR AN OLDER
 TRAILER(3UNITS) WHICH IS NOT BEING BROUGHT UP TO CODE
 AND ONE (2 TRAILERS) WHICH IS BEING BROUGHT UP TO
 CODE?
 PLEASE SEE PREVIOUS REVIEW NOTES WHICH REQUESTED *ALL*
 OLD/ VOIDED SHEETS TO BE COMPLETELY REMOVED AND FOR
 ONLY NEW SHEETS TO BE INSERTED INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. HOWEVER THE OLD/VOIDED SHEETS
 WERE LEFT IN SETS.
 PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT TO
 THE SETS AND PERMITTING.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved