| 2007-06-04 17:03:29 | ** UNSAT ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE COMMENTS FROM THE PREVIOUS |
| | REVIEW WHICH MENTIONS THE ENERGY CALCULATIONS CONTAIN A |
| | RAISED SEAL OVER A PHOTO-COPIED SIGNATURE WHICH IS NOT |
| | PERMITTED PER FLORIDA STATUTES 471.023, FAC |
| | 61G15-23.002 AND FBC 13-103.1.1.1 |
| | PLEASE SEE THE ENERGY CALCULATIONS ARE NOT COMPLETE AS |
| | NO INTERIOR LIGHTING IS FIGURED INTO THE CALCULATIONS. |
| | PLEASE COORDINATE ALL LIGHTING ON PLANS WITH ENERGY |
| | CALCULATIONS. |
| | |
| | 2) NOTE: PLEASE SEE RISER INDICATES ONLY A 100AMP FEED |
| | TO PANEL *B* WHICH ACTUALLY CONTAINS A LOAD HIGHER THAN |
| | 100AMPS. |
| | THIS EXCEEDS THE RATING OF CONDUCTORS AND BREAKER. |
| | 240.4, 310.16, 408, ETC. |
| | |
| | 3) NOTE: PLEASE SEE THE EXISTING PANEL FOR THE TWO |
| | TRAILERS IS BEING SHOWN A MLO WITH TWO BREAKERS FOR |
| | EACH TRAILER, PLEASE SEE 230.70/71 AS NO MORE THAN |
| | 6SPACES IS PERMITTED IN SERVICE EQUIPMENT. PLEASE |
| | CLARIFY WHERE THE SINGLE MAIN IS LOCATED OR WILL A MCB |
| | BE INSTALLED IN THIS PANEL? |
| | |
| | 4) NOTE: PLEASE SEE THE ENTIRE PACKAGE SUBMITTED |
| | APPEARS THAT ONE SET OF PLANS IS FOR AN OLDER |
| | TRAILER(3UNITS) WHICH IS NOT BEING BROUGHT UP TO CODE |
| | AND ONE (2 TRAILERS) WHICH IS BEING BROUGHT UP TO |
| | CODE? |
| | PLEASE SEE PREVIOUS REVIEW NOTES WHICH REQUESTED *ALL* |
| | OLD/ VOIDED SHEETS TO BE COMPLETELY REMOVED AND FOR |
| | ONLY NEW SHEETS TO BE INSERTED INTO TWO COMPLETE SETS |
| | FOR REVIEW AND STAMPING. HOWEVER THE OLD/VOIDED SHEETS |
| | WERE LEFT IN SETS. |
| | PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT TO |
| | THE SETS AND PERMITTING. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |