Plan Review Notes
Plan Review Notes For Permit 07020542
Permit Number 07020542
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-03-30 18:40:51*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE REMOVAL AND(OR) REPLACEMENT OF THE MODULAR
 BUILDINGS SHALL NOT INTERFERE OR HINDER EMERGENCY
 RESPONSE ACCESS TO OR EGRESS FROM THE PROPERTY OR
 VICINITY THEREOF (INCLUDING FIRE LANES).
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 4.ALL SUBMITTED PLAN SHEETS SHALL HAVE THE ADDRESS OF
 WHERE THE SCOPE OF WORK WILL BE CONDUCTED IN THE TITLE
 BLOCK.
  
 5.PLEASE PROVIDE A SITE PLAN SHOWING THE HOW THE
 STRUCTURES RELATES TO STREETS, HYDRANTS, BUILDINGS,
 ETC. IN THE IMMEDIATE AREA.
  
 6.DISPLAY 2A:10BC RATED FIRE EXTINGUISHER(S) LOCATION
 IN THE PROPOSED STRUCTURES.
  
 7.WILL THESE PROPOSED STRUCTURES HAVE A FIRE ALARM
 AND/OR FIRE SPRINKLER SYSTEM IN ITS MAKEUP?
  
 8. PLEASE BE ADVISED THAT IF IT IS DETERMINED THAT AN
 INDEPENDENT NUMERICAL ADDRESS IS REQUIRED, THOSE
 NUMBERS SHALL BE NO LESS THE 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  