Plan Review Notes
Plan Review Notes For Permit 07020542
Permit Number 07020542
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-04 13:04:15** UNSAT**
  
  
 1) NOTE: PLEASE SEE THAT THE SCOPE OF WORK IS NOT
 COMPLETELY CLEAR AT THIS TIME. THE PLANS APPEAR TO SHOW
 TWO BUILDINGS ALONG WITH PERMIT APPLICATION WHICH ALSO
 MENTIONS TWO BUILDINGS TO BE DONE.
 PLEASE SEE THE ONE SET OF TRAILERS TO MAKE ONE BUILDING
 DO NOT SEEM TO SHOW THESE AS STATE APPROVED. PLEASE
 ALSO SEE THE PLANS WHICH WERE SUBMITTED FOR THE OTHER
 BUILDING WITH THREE TRAILERS SHALL BEAR THE ORIGINAL
 STAMP FROM THE STATE. THESE PLANS ARE PHOTO-COPIES OF
 STATE STAMPED PLANS. THIS OFFICE IS AWARE THAT THE
 PLANS DO NOT REQUIRE AN ORIGINAL SIGNATURE, DATE AND
 SEAL FROM THE DESIGNER PROFESSIONAL. THE STATE STAMP IS
 REQUIRED FOR ALL SHEETS AND IS REQUIRED TO BE
 ORIGINAL.
 PLEASE SEE THE FLORIDA ENERGY CALCULATIONS WERE
 SUBMITTED FOR THE TWO TRAILER BUILDING CONTAIN RAISED
 SEALS OVER A PHOTO-COPIED SIGNATURE WHICH IS REQUIRED
 TO BE ORIGINAL. FS 471.025, FAC 61G15-23.002
 PLEASE CLARIFY WHERE THE INTERIOR LIGHTING ALLOWANCES
 ARE SHOWN? ONLY EXTERIOR INPUT IS COULD BE LOCATED ON
 SHEETS SUBMITTED. PLEASE CLARIFY 13-415.2
 THIS IS THE ONLY WAY THAT VERIFICATION CAN BE MADE THAT
 NO CHANGES HAVE BEEN MADE TO THE STATE APPROVED PLANS.
 FBC 106.1.2 ADMIN SECTION.
 FS 553.79
  
 2) NOTE: PLEASE CLARIFY THE ELECTRICAL RISER AND PLANS
 AS SUBMITTED FOR SHEET 1OF 2. PLEASE SEE PLANS INDICATE
 NEW METERS, YET PLANS DO NOT SHOW THIS?
 PLEASE VERIFY WHERE THE SERVICE COMES FROM? IS THIS
 FEED FROM FPL? MAIN DISCONNECT IS BEING SHOWN ON THE
 LINE SIDE OF METERING DEVICES.
 PLEASE SEE NO METERS ON RISER?
 PLEASE SEE PANELS ON RISER DO NOT INDICATE BEING MCB?
 PLEASE CLARIFY.
 PLEASE CLARIFY IF THE TWO PANELS WHICH ARE SHOWN AS
 EXISTING ON THE TWO TRAILER BUILDINGS CONTAIN
 DISCONNECTS?
 250.32, 215.5, 225.31-39 ETC.
  
 3) NOTE: PLEASE SEE THAT THE FOLLOWING CODES SHALL BE
 STATED ON PLANS.
 NFPA-70 2005.
  
 4) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR ALL SERVICE
 EQUIPMENT.
 110.9.
 FBC 106.1.2
  
 5) NOTE: PLEASE CLARIFY WHAT TYPE OF LIGHTING AND
 LEVELS ARE PROVIDED FOR EGRESS OF STAIRS AND PATHS OUT
 AND AWAY FROM THESE BUILDINGS.
 LS 101 7.8.1.3, 7.9.2.2
  
 '* ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved