| 2007-03-04 13:04:15 | ** UNSAT** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THAT THE SCOPE OF WORK IS NOT |
| | COMPLETELY CLEAR AT THIS TIME. THE PLANS APPEAR TO SHOW |
| | TWO BUILDINGS ALONG WITH PERMIT APPLICATION WHICH ALSO |
| | MENTIONS TWO BUILDINGS TO BE DONE. |
| | PLEASE SEE THE ONE SET OF TRAILERS TO MAKE ONE BUILDING |
| | DO NOT SEEM TO SHOW THESE AS STATE APPROVED. PLEASE |
| | ALSO SEE THE PLANS WHICH WERE SUBMITTED FOR THE OTHER |
| | BUILDING WITH THREE TRAILERS SHALL BEAR THE ORIGINAL |
| | STAMP FROM THE STATE. THESE PLANS ARE PHOTO-COPIES OF |
| | STATE STAMPED PLANS. THIS OFFICE IS AWARE THAT THE |
| | PLANS DO NOT REQUIRE AN ORIGINAL SIGNATURE, DATE AND |
| | SEAL FROM THE DESIGNER PROFESSIONAL. THE STATE STAMP IS |
| | REQUIRED FOR ALL SHEETS AND IS REQUIRED TO BE |
| | ORIGINAL. |
| | PLEASE SEE THE FLORIDA ENERGY CALCULATIONS WERE |
| | SUBMITTED FOR THE TWO TRAILER BUILDING CONTAIN RAISED |
| | SEALS OVER A PHOTO-COPIED SIGNATURE WHICH IS REQUIRED |
| | TO BE ORIGINAL. FS 471.025, FAC 61G15-23.002 |
| | PLEASE CLARIFY WHERE THE INTERIOR LIGHTING ALLOWANCES |
| | ARE SHOWN? ONLY EXTERIOR INPUT IS COULD BE LOCATED ON |
| | SHEETS SUBMITTED. PLEASE CLARIFY 13-415.2 |
| | THIS IS THE ONLY WAY THAT VERIFICATION CAN BE MADE THAT |
| | NO CHANGES HAVE BEEN MADE TO THE STATE APPROVED PLANS. |
| | FBC 106.1.2 ADMIN SECTION. |
| | FS 553.79 |
| | |
| | 2) NOTE: PLEASE CLARIFY THE ELECTRICAL RISER AND PLANS |
| | AS SUBMITTED FOR SHEET 1OF 2. PLEASE SEE PLANS INDICATE |
| | NEW METERS, YET PLANS DO NOT SHOW THIS? |
| | PLEASE VERIFY WHERE THE SERVICE COMES FROM? IS THIS |
| | FEED FROM FPL? MAIN DISCONNECT IS BEING SHOWN ON THE |
| | LINE SIDE OF METERING DEVICES. |
| | PLEASE SEE NO METERS ON RISER? |
| | PLEASE SEE PANELS ON RISER DO NOT INDICATE BEING MCB? |
| | PLEASE CLARIFY. |
| | PLEASE CLARIFY IF THE TWO PANELS WHICH ARE SHOWN AS |
| | EXISTING ON THE TWO TRAILER BUILDINGS CONTAIN |
| | DISCONNECTS? |
| | 250.32, 215.5, 225.31-39 ETC. |
| | |
| | 3) NOTE: PLEASE SEE THAT THE FOLLOWING CODES SHALL BE |
| | STATED ON PLANS. |
| | NFPA-70 2005. |
| | |
| | 4) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR ALL SERVICE |
| | EQUIPMENT. |
| | 110.9. |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE CLARIFY WHAT TYPE OF LIGHTING AND |
| | LEVELS ARE PROVIDED FOR EGRESS OF STAIRS AND PATHS OUT |
| | AND AWAY FROM THESE BUILDINGS. |
| | LS 101 7.8.1.3, 7.9.2.2 |
| | |
| | '* ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |