| 2007-03-15 12:00:07 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS; THE CITY OF WEST PALM |
| | BEACH GAS PERMIT APPLICATION REQUIREMENTS; RESIDENTIAL |
| | GENERATOR PERMIT APPLICATION REQUIREMENTS; |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. UNTIL THE ZONING ISSUE IS RESOLVED GAS PERMIT CAN |
| | NOT BE ISSUED DUE TO THE FACT THAT THE GENERATORS |
| | PLACEMENT MIGHT CHANGE. |
| | |
| | 2. THE SUBMITTED MANUFACTURER SPECIFICATIONS HAVE |
| | PROPANE INDICATED AS THE FUEL SOURCE AND THE SUBMITTED |
| | GAS PERMIT APPLICATION AND PLANS ARE INDICATING NATURAL |
| | GAS AS THE FUEL SOURCE. PLEASE CORRELATE AND RESUBMIT. |
| | |
| | 3. THE SUBMITTED MANUFACTURER SPECIFICATIONS FOR THE |
| | GENERATOR ARE INDICATING THE NATURAL GAS BTU LOAD AS |
| | 560,000 AND THE SUBMITTED GAS DRAWINGS ARE INDICATING |
| | THE GENERATOR BTU LOAD AS 548,000. PLEASE CORRECT THE |
| | GAS DRAWINGS TO REFLECT THE GENERATOR MANUFACTURER |
| | SPECIFICATIONS AND CORRECT THE TOTAL BTU LOAD OF |
| | 1,197,000 ON THE RESUBMITTAL. |
| | |
| | 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | 5. THE SUBMITTED NOTICE OF COMMENCEMENT IS INCORRECT |
| | AND VOID. PLEASE PROVIDE A CURRENT NOTICE OF |
| | COMMENCEMENT RECORDED WITH THE CLERK OF THE COURT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |