Plan Review Notes
Plan Review Notes For Permit 07020506
Permit Number 07020506
Review Stop G
Sequence Number 3
Notes
Date Text
2007-05-14 10:12:57REVISION: NEW LAYOUT WITH ALL NEW PIPING DUE TO DAMAGED
 EXISTING.
  
 ****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 A} PER FBC-2004 FUEL GAS, SECTION 404.13.3AN
 INSULATED COPPER TRACER WIRE SHALL BE INSTALLED
 ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE
 TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE
 INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
  
 B} FBC-2004 FUEL GAS SEC. 404.12 OUTLET
 CLOSURES: GAS OUTLETS THAT DO NOT CON-
 NECT TO APPLIANCES SHALL BE CAPPED GAS
 TIGHT.