Plan Review Notes For Permit 07020506
Permit Number 07020506
Review Stop G
Sequence Number 2
Notes
Date Text
2007-04-17 15:52:12REVISION DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS REVISION PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. CLEARLY INDICATE ON THE RESUBMITTED REVISION THE
 EXISTING PIPING AND THE NEW PIPING.
  
 2. PLEASE INDICATE THE FOLLOWING FOR THE FUTURE
 GRILL:
  
 A} BTU LOAD FOR THE FUTURE GRILL.
 B} PIPE SIZES FOR THE FUTURE GRILL.
 C} PLEASE INDICATE THE PIPING FOR THE FUTURE GRILL AS
 NEW BECAUSE THERE IS NO INDICATION OF A GRILL ON THE
 PERMITTED FILE COPY PRINT.
  
 3. PLEASE CORRECT THE TOTAL BTU LOAD TO REFLECT THE
 ADDED BTU LOAD OF THE FUTURE GRILL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  