| Plan Review Notes For Permit 07020506 |
| Permit Number |
07020506 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-04-17 15:52:12 | REVISION DENIED | | | REFERENCE: | | | ** FBC-2004 FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS REVISION PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. CLEARLY INDICATE ON THE RESUBMITTED REVISION THE | | | EXISTING PIPING AND THE NEW PIPING. | | | | | | 2. PLEASE INDICATE THE FOLLOWING FOR THE FUTURE | | | GRILL: | | | | | | A} BTU LOAD FOR THE FUTURE GRILL. | | | B} PIPE SIZES FOR THE FUTURE GRILL. | | | C} PLEASE INDICATE THE PIPING FOR THE FUTURE GRILL AS | | | NEW BECAUSE THERE IS NO INDICATION OF A GRILL ON THE | | | PERMITTED FILE COPY PRINT. | | | | | | 3. PLEASE CORRECT THE TOTAL BTU LOAD TO REFLECT THE | | | ADDED BTU LOAD OF THE FUTURE GRILL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | |
|